689 994B - 15/10/94
11
MERLIN GERIN
Masterpact
MP-MC circuit breaker
TM
1
control wiring
Each terminal may be connected by one
stranded copper wire 18 to 14 AWG (0.6 to
2.5 mm
2
)
Cable strip length : 3/8" /
9mm
fixed mounting
1 install the connector
2 remove the transparent shield
3 connect the control wires according to
the wiring diagrams shown on the label and
using a small screwdriver
4 replace the transparent cover
warning : do not route the control wires
close to the arc chutes
3
4
2
10