background image

 

350.135UK User Manual

 

 

Installation: 

After finding an appropriate location, the wall bracket can be screwed onto the wall using the supplied 
hardware. Alternatively it can be stuck on using a pad sticker or just rested on top of a unit.  

To mount the bracket using hardware, use the mounting plate as a guide to mark the two holes. Drill 
these holes 6mmØ, 30mm deep. Insert the plugs into the 

hole and screw the bracket on, ensuring the raised side is 
facing outward and is pointing upward correctly as shown.   

 
Push the back of the alarm against the bracket and slide 

down until it clicks to lock in place. The battery 
compartment has latches that rise up to prevent the alarm 

being installed without batteries, therefore please ensure 
the batteries are inserted before installing the alarm.   

 

Operation: 

The LCD screen and LEDs on the front of the alarm give 
vital information of the working condition of the alarm and 

important ambient readings of the surroundings. 

 
When the alarm is powered, the green power LED will 

flash once every 45 seconds to indicate it is working. When the working voltage drops below 3.5V, the 
alarm will beep when the power LED flashes. This indicates the battery power is insufficient; please 

replace battery as soon as possible. On the LCD display, the battery status is also shown constantly: 
 

 Indicates batteries are at full capacity and alarm is working with sufficient power. 

 Indicates batteries have sufficient capacity and alarm is working with sufficient power. 
 Indicates batteries capacity is getting low but alarm still has sufficient power. 
 Indicates batteries are critically low and alarm is working on the minimum required power and 

requires replacement as soon as possible in order to keep the alarm functional. 

 
It is recommended to manually perform testing once a week. To perform a manual test, simply press the 

test button for 1 second and the alarm will enter test mode. All three LEDs will flash once and alarm will 
sound 4 times

. The LCD screen will read “

---

“ to indicate it’s testing.

 

 

 

 

All LEDs and the LCD display should resume back to normal after a few seconds. 

 
The alarm will perform self-checking of the sensor every 2 minutes. Under normal conditions no LEDs will 

flash. If the sensor fails, the amber fault LED will flash once every 2 minutes together with two long 
beeps. Also the LCD will display the error message as below, this indicates the alarm sensor or circuitry 

has failed. Please stop using the alarm immediately. 
 

Summary of Contents for SD102P

Page 1: ...de gas or smoke from a potential fire COD100B Product Specifications Apparatus Type B Batteries 3 x AA supplied Alarm level 85dB 1m Sensor Electromechanical Static working current 80uA Operating tempe...

Page 2: ...s rooms with a boiler fireplace or gas oven For optimum detection the alarm needs to be installed at least 1 5m above the ground 0 3m below the ceiling and 1 5m from the corner of the room DO NOT loca...

Page 3: ...hen the power LED flashes This indicates the battery power is insufficient please replace battery as soon as possible On the LCD display the battery status is also shown constantly Indicates batteries...

Page 4: ...the concentration of the carbon monoxide reaches above 550ppm the alarm will sound continuously with the LCD displaying Hco high carbon monoxide as below This indicates a dangerously high concentrati...

Page 5: ...ays remove alarm from the bracket before painting and wait for paint to be fully dry before reinstalling the alarm Avoid shock or impact on the alarm if accidentally dropped check if the battery conne...

Page 6: ...ows to allow fresh air to flow in and evacuate all persons from room or building Seek medical support immediately Contact the emergency gas service and allow them to inspect the building to ensure it...

Page 7: ...3 Align the 2 locating slots in the smoke detector with the 2 tags on the installation panel and rotate it clockwise until it locks into position Testing and usage 1 Turn the smoke detector anti clock...

Page 8: ...qualified personnel Please retain this manual for future reference Intended for Fire Safety and installed in buildings Essential characteristic 1 Pass 13 Essential characteristic 2 Pass 1134 Essential...

Reviews: