5.  Alarm Contract Wiring: 

Inputs 1 to 8 may be configured to use or not to use End-Of-Line (EOL) 
resistors, and for normally open or normally closed contacts.  Input TMP 
is  used  for  monitoring  cabinet  tamper  and  PFL  input  is  used  power 
failure  monitoring.    These  two  inputs  are  for  contact  closure  monitoring 
only.  They do not use EOL resistor(s).  Input configuration is set via host 
software. 

 

6.  Control Output Wiring: 

Six form-C contact relays  are provided for controlling door strikes or other  devices.  Load switching can 
cause  abnormal  contact  wear  and  premature  contact  failure.    Switching  of  inductive  loads  (strike)  also 
causes EMI (electromagnetic interference) which may interfere with normal operation of other equipment.  
To minimize premature contact failure and to increase system reliability, contact protection circuit must be 
used.  The following two circuits are recommended.  Locate the protection circuit as close to the load as 
possible (within 12  inches  [30cm]), as the effectiveness of the circuit  will  decrease if it  is located further 
away.  

Use sufficiently large gauge of wires for the load current as to avoid voltage loss. 

 

 

DIODE SELECTION:

 

 
DIODE CURRENT RATING > 1 X STRIKE CURRENT 

DIODE BREAK DOWN VOLTAGE: 4X STRIKE VOLTAGE 
FOR 12Vdc or 24Vdc STRIKE, DIODE 1N4002 (100V /1A) TYPICAL 

 

 
MOV SELECTION:

 

 
CLAMP VOLTAGE > 1.5 X Vac RMS 
FOR 24Vac STRIKE, PANASONIC ERZ-C07DK470 TYPICAL 

7.  Jumper and DIP Switch Usage: 

JUMPER 

DESCRIPTION 

J2 

Reader Power Select  

 

12V = 12Vdc at reader ports.  *** See note below *** 

 

PT =  VIN “Passed Through" to reader ports 

J3 

2-Wire/4-Wire Select, install in 2W position only 

J5 

RS-485 Termination, install in first and last units only 

J6 

Factory use only 

J7 

Factory use only 

J8 

Factory use only 

J9 

Factory use only 

J10 

Factory use only 

J11 

Factory use only 

J12 

Factory use only 

J13 

Factory use only 

J14 

Factory use only 

J15 

Factory use only 

NOTE:

 The input power (VIN) must be 20Vdc minimum if the 12Vdc selection is to be used. 

 

NC
C
NO
NC
C
NO





NC
C
NO
NC
C
NO



Summary of Contents for MR52

Page 1: ...ay be used for strike control or alarm signaling Eight supervised inputs are provided for monitoring the door contact exit push button and alarm contacts Communication to the MR52 is accomplished via...

Page 2: ...RS 485 interface Power to the reader is selectable 12Vdc or input voltage passed through PT 125mA maximum per reader port This selection is made via jumper J2 and is made for both reader ports For th...

Page 3: ...t be used The following two circuits are recommended Locate the protection circuit as close to the load as possible within 12 inches 30cm as the effectiveness of the circuit will decrease if it is loc...

Page 4: ...N OFF ON Address 13 OFF ON ON ON OFF Address 14 OFF ON ON ON ON Address 15 ON OFF OFF OFF OFF Address 16 ON OFF OFF OFF ON Address 17 ON OFF OFF ON OFF Address 18 ON OFF OFF ON ON Address 19 ON OFF ON...

Page 5: ...port 1 LED Input Status IN1 2 LED Input Status IN2 3 LED Input Status IN3 4 LED Input Status IN4 5 LED Input Status IN5 6 LED Input Status IN6 7 LED Input Status IN7 8 LED Input Status IN8 TMP Cabinet...

Page 6: ...ge passed through 125mA maximum each reader Reader LED output TTL compatible high 3V low 0 5V 5mA source sink maximum Reader buzzer output Open collector 5Vdc open circuit maximum 10mA sink maximum Re...

Page 7: ...other warranties or implied warranties and expressly excludes and disclaims all implied warranties of merchantability or fitness for a particular purpose Returned units are repaired or replaced from a...

Reviews: