Mercury Security © 2015 

MR51e 

DOC  10107-0035  

REV 1.06 

 Page   2 

 

MR51e Terminal Blocks and Jumpers/Jacks: 

MR-51E CONNECTIONS 

TB1-1 

IN1 

Input 1 

TB1-2 

IN1 

 

TB1-3 

IN2 

Input 2 

TB1-4 

IN2 

 

TB2-1 

IN3 

Input 3  

TB2-2 

IN3 

 

TB2-3 

IN4 

Input 4 

TB2-4 

IN4 

 

TB3-1 

VO 

Reader 1 Power Output 

– 12 VDC 

TB3-2 

LED 

Reader 1 LED Output 

TB3-3 

BZR 

Reader 1 Buzzer Output 

TB3-4 

CLK 

Reader 1 CLK/Data 1/TR+ 

TB3-5 

DAT 

Reader 1 DAT/Data 0/TR- 

TB3-6 

GND 

Reader 1 Ground 

TB4-1 

LED 

Reader 2 LED Output 

TB4-2 

BZR 

Reader 2 Buzzer Output 

TB4-3 

CLK 

Reader 2 CLK/Data 1 Input 

TB4-4 

DAT 

Reader 2 DAT/Data 0 Input 

TB5-1 

VO 

Auxiliary Power Output 

– 12 Vdc 

TB5-2 

GND 

Auxiliary Power Output Ground 

TB5-3 

VIN 

Input Power 

– 12 Vdc (from local power supply) 

TB5-4 

GND 

Input Power Ground 

TB6-1 

NO 

Relay K1 

– Normally Open Contact 

TB6-2 

1-C 

Relay K1 

– Common Contact 

TB6-3 

NC 

Relay K1 

– Normally Closed Contact 

TB6-4 

NO 

Relay K2 

– Normally Open Contact 

TB6-5 

2-C 

Relay K2 

– Common Contact 

TB6-6 

NC 

Relay K2 

– Normally Closed Contact 

Jumpers: 

JUMPER 

SET AT 

DESCRIPTION 

J1 

N/A 

Factory Use Only 

J2 

N/A 

Factory Use Only 

J3 

N/A 

Factory Use Only 

J4 

N/A 

Factory Use Only 

J5 

PoE 

MR-51E powered from the Ethernet connection 

 

12V 

MR-51E  powered  from  an  external  12  Vdc  power 
source connected to TB5-3 (VIN), TB5-4 (GND) 

J6 

N/A 

Ethernet Connection with POE support 

J7 

N/A 

Factory Use Only 

 

 

 

Summary of Contents for MR51e

Page 1: ...ED mode only Reader port 2 can accommodate a reader that TTL D1 D0 Clock Data or F 2F signaling and also provides tri stated LED control and buzzer control one wire LED mode only Two Form C relay outputs may be used for door strike control or alarm signaling The relay contacts are rated at 5 A 30 Vac dc dry contact configuration Four inputs are provided that may be used for monitoring the door con...

Page 2: ...T Data 0 Input TB5 1 VO Auxiliary Power Output 12 Vdc TB5 2 GND Auxiliary Power Output Ground TB5 3 VIN Input Power 12 Vdc from local power supply TB5 4 GND Input Power Ground TB6 1 NO Relay K1 Normally Open Contact TB6 2 1 C Relay K1 Common Contact TB6 3 NC Relay K1 Normally Closed Contact TB6 4 NO Relay K2 Normally Open Contact TB6 5 2 C Relay K2 Common Contact TB6 6 NC Relay K2 Normally Closed ...

Page 3: ...e MR51e is Ethernet 10Base T 100Base TX It is not recommended to connect the MR51e to a public intranet 6 Reader Wiring Reader port 1 supports TTL D1 D0 Clock Data F 2F or 2 wire RS 485 device signaling Reader port 2 supports TTL D1 D0 Clock Data or F 2F signaling Power to reader port 1 is 12 Vdc at 180 mA maximum Reader port 2 may be powered from the auxiliary power supply output TB5 1 and TB5 2 ...

Page 4: ...TR FIRST READER PORT 12 Vdc D1 GROUND DO GREEN LED F 2F Reader 1 VO 12 Vdc GND LED BZR CLK D1 DAT D0 TB3 FIRST READER PORT TB4 1 BZR DAT D0 CLK D1 LED 1 TB5 GND VIN GND VO 12 Vdc D1 GROUND DO GREEN LED F 2F Reader SECOND READER PORT 1 TB3 VO 12 Vdc GND LED BZR CLK D1 DAT D0 12 Vdc D1 GROUND DO GREEN LED F 2F Reader NORMALLY CLOSED CONTACT DOOR MONITOR SWITCH REQUEST TO EXIT SWITCH NORMALLY OPEN CO...

Page 5: ...rated at 5 A 30 Vac dc dry contact configuration Each relay has a Common pole C a Normally Open pole NO and a Normally Closed pole NC When you are controlling the delivery of power to the door strike the Normally Open and Common poles are used When momentarily removing power to unlock the door as with a mag lock the Normally Closed and Common poles are used Check with local building codes for prop...

Page 6: ...e encryption disabled 0 8 second ON 0 2 second OFF 1 On line encryption enabled four pulses 0 1 second ON 0 1 second OFF per second Off line 0 2 second ON 0 8 second OFF static addressing mode only Waiting for application firmware to be downloaded 1 sec ON 1 sec OFF 2 Flashes when there is host communication approximately every 5 seconds 3 Flashes when data is received from either reader downstrea...

Page 7: ...above LED Output TTL compatible high 3 V low 0 5 V 5 mA source sink maximum Buzzer Output Open collector 12 Vdc open circuit maximum 40 mA sink maximum Data Inputs Reader port 1 TTL compatible F 2F or 2 wire RS 485 Reader port 2 TTL compatible or F 2F Cable Requirements Communication Ethernet Category 5 minimum Power 1 twisted pair 18 AWG Alarm Inputs 1 twisted pair per input 30 ohm maximum Reader...

Page 8: ...IC TAMPER SWITCH 11 Additional Mounting Information Sources for the optional items shown below 3 gang stainless steel blank cover Available from Leviton part number 84033 40 Graybar part number 88158404 Magnetic switch set G R I part number 505 Side View Mounting Plate Dimensions 3 85 97 8 2 35 59 7 5 50 139 7 3 63 92 1 3 30 83 8 3 63 92 1 Ø0 16 Ø4 0 MR50 MGT HOLES 4PL Ø0 16 Ø4 0 3 GANG MGT HOLES ...

Page 9: ...entative to make any other warranties or implied warranties and expressly excludes and disclaims all implied warranties of merchantability or fitness for a particular purpose All returns must be accompanied by a Return Material Authorization RMA number obtained from customer service and prepaid postage and insurance Liability The Interface should only be used to control exits from areas where an a...

Reviews: