Mercury Security MR16out Installations And Specifications Download Page 2

 

Mercury Security Corporation © 2009 

MR16out 

DOC 10107-0010 

REV 2.01 

 Page   2 

3.  Communication Wiring: 

The MR16out communicates to a controller via a 2-wire RS-485 interface.  The interface allows multi-drop 
communication on a single bus of up to 4,000 feet (1,200 m).   Use twisted pair (minimum 24 AWG) with 
shield for the communication line. 

Install the following jumpers for the RS-485 interface according to the selected configuration: 

4.  Inputs for Cabinet Tamper/Power Fault: 

Input  CT  and  input  BA  are  used  for  monitoring  cabinet  tamper  and  power  failure  with  normally  closed 
contacts.    These  two  inputs  are  for  contact  closure  monitoring  only,  and  do  not  use  EOL  resistor(s).    If 
these inputs are not used, install a short piece of wire at the input to indicate a safe condition. 

 

5.  Relay Outputs: 

The  following  diagrams  show  typical  use  of  the  relay.    A  DC  power  source  is  recommended  whenever 
possible.  Transient clamping must be provided to protect the contacts and to reduce EMI emission.   Use 
sufficiently large wires for the load current to avoid voltage loss. 

 

DIODE SELECTION:

 

 
DIODE CURRENT RATING > 1 X STRIKE CURRENT 

DIODE BREAK DOWN VOLTAGE: 4X STRIKE VOLTAGE 
FOR 12Vdc or 24Vdc STRIKE, DIODE 1N4002 (100V /1A) 
TYPICAL 

 

MOV SELECTION:

 

 
CLAMP VOLTAGE > 1.5 X Vac RMS 
FOR 24Vac STRIKE, PANASONIC ERZ-C07DK470 
TYPICAL 

CT

GND

BA

GND

CABINET

TAMPER

POWER

FAULT

TB9

 

NC
C
NO
NC
C
NO





NC
C
NO
NC
C
NO



 

 

TR+
TR-

R+
R-

GND

2W

4W

2-WIRE

TB10

(ONLY 2-WIRE RS-485 IS SUPPORTED)