Strider M72
ME-PM-M72
Image
Set primary current input the meter
Options: 1~9999
Default CT1: 5A
Long press to enter the CT1 routine. Press for 2s, the CT1 setting will flash. Use and
to choose CT1 with 1~9999.
And long press for confirmation.
Example shows :
Set CT1 100A
And press for confirmation. Press to return the CT set up menu.
•
CT1
PT
Image
The PT option sets the secondary voltage of the voltage transformer (PT) that give into the meter and
the PT rate between the primary voltage to the secondary voltage.
For example: if the PT connect to the meter is 10000/100V (Primary voltage is 10000V, secondary
voltage is 100V), then the PT rate is 100.
Long press to enter the PT2 routine. Press , the PT2 setting will flash. Use and ,
to choose PT2 with 174~480.
Set secondary voltage input the meter
Range: 100V ~ 480V
Default: 230V
And long press for confirmation.
Set primary voltage input the meter
Range: 100V ~ 500000V
Default: 230V
Then press to enter the PT2 routine. press for 2s, the PT2 setting will flash. Use and
, to select PT2. And long press for confirmation. Press to return the PT set
up menu.
•
PT2
•
PT1