Strider M4 V2
ME-PM-M4-5
MerCs Pty Ltd, 55 Pendlebury Rd, Cardiff, NSW, 2285, Australia | 2019 V1.1
Interfaces for External Monitoring
Three interfaces are provided:
•
RS485 communication channel that can be programmedfor Modbus RTU protocol
•
Relay output indicating real-time measured energy.(configurable)
•
Pulse output 3200imp/kWh (not configurable)
The Modbus configuration (baud rate etc.) and the pulse relay output assignments (kW/kVArh, import/export etc.) are configured through the set-up
screens.
Pulse Output
The pulse output can be set to generate pulses to represent kWh or kVArh.
Rate can be set to generate 1 pulse per:
0.01 = 10 Wh/VArh
0.1 = 100 Wh/VArh
1 = 1 kWh/kVArh
10 = 10 kWh/kVArh
100 = 100 kWh/kVArh
1000 = 1000 kWh/kVArh
Pulse width 200/100/60 ms.
Relay Rating 240V ac 50mA
RS485 Output for Modbus RTU
For Modbus RTU, the following RS485 communication parameters can be configured from the set-up menu:
Baud rate 2400, 4800, 9600, 19200, 38400
Parity none (default) / odd / even
Stop bits 1 or 2
RS485 network address nnn – 3-digit number, 1 to 247
Modbus
TM
Word order Hi/Lo byte order is set automatically to normal or reverse. It cannot be configured from the set-up menu.
Reference Conditions of Influence Quantities
Influence Quantities are variables that affect measurement errors to a minor degree. Accuracy is verified under nominal value (within the specified
tolerance) of these conditions.
Ambient temperature
23°C ±1°C
Input frequency
50 or 60Hz ±2%
Input waveform
Sinusoidal (distortion factor < 0·005)
Auxiliary supply voltage
Nominal ±1%
Auxiliary supply frequency
Nominal ±1%
Auxiliary supply waveform (if AC)
Sinusoidal (distortion factor < 0·05)
Magnetic field of external origin
Terrestrial flux