mcr WIP type multi-blade fire dampers 

 

 

 

“MERCOR” S.A. – 

the Company reserves the right to make modifications and changes. 

 

3/15 

 

 

 
 
 
 

 
 

 

 

NOTICE

 

As at the date of issue of this Operation and Maintenance Manual, previous revisions 

become invalid. The Operation and Maintenance Manual does not apply to fire 

dampers manufactured before the date of its issue

.

 

 

1.  INTRODUCTION    

The  aim  of  this  Operation  and  Maintenance  Manual  is  to  make  the  user  familiar  with  the  intended  use,  design, 
operating principle, correct installation and operation of the product. 
The OMM also contains additional information on the conditions of use, maintenance and warranty of the product. 

 

2.  THE SUBJECT OF THE MANUAL  

 

This OMM applies to a whole group of mcr WIP type multi-blade fire dampers. Complying with the recommendations 
included in the OMM will ensure proper functioning of the fire damper in its purpose of being a fire protection system 
used in interior spaces as well as the safety of its users. 

 

3.  INTENDED USE OF THE FIRE DAMPER  

 

Use

 

 

 

The mcr WIP type multi-blade (multi-plane) fire dampers may be used as: 

the mcr WIP/S type fire dampers 

   

 the mcr WIP/V type fire dampers for fire ventilation systems 

   

 the mcr WIP/M type fire dampers for mixed-mode fire ventilation systems 

   

 the mcr WIP/T type transfer dampers 

   

 the WIP/T-G type pressure relief dampers 

 

Fire dampers are not designed to work in ventilation systems where there is a risk of them coming into contact with 
dust-laden air unless they have been covered by a special, tailor-made service and technical inspections programme. 

 

Fire resistance

 

 

 

The fire resistance ratings of the mcr WIP type fire dampers are as follows: 

 

The fire ratings depend on the application as well as the manner and place of fire damper installation. 

 

Manufacturing versions

 

 

 

The mcr WIP type fire dampers may be manufactured as: 

rectangular fire dampers 
rectangular fire dampers with circular connections 
round fire dampers 

 

Series of types of dimensions

 

 

 

The mcr WIP type fire dampers are manufactured in the following dimensions: 

width: from 120 to 1,000 mm 
height: from 160 to 1,000 mm 
rectangular fire dampers’ width: 140 mm width of fire 
dampers with circular connections: 220 mm 

Apart from the standard dimensions, there is a possibility to manufacture fire dampers with any dimensions within 
the above ranges. The maximum surface area of the mcr WIP type fire damper is 1 m

2

. The minimum surface area 

of a fire damper is 0.019 m

2

4.

  DESIGN AND OPERATING PRINCIPLE OF THE FIRE DAMPER 

 

Design  

 

The mcr WIP type fire dampers consist of a housing with a rectangular cross section, movable partition made of an 
assembly of blades rotating on their axes as well as a release and control mechanism, which is started remotely or 
automatically  (after  a  thermal  release  has  been  actuated).  Fire  dampers’  housings  are  made  of  galvanised  steel 
sheet, stainless steel sheet or acid-proof sheet. An integral part of the housing is a flange made of a fire-resistant 
plate.  Each  damper  blade  is  made  of  galvanised  steel  sheet,  stainless  steel  sheet  or  acid-proof  sheet  with  a 
plasterboard inside. On inside of the housing, along the partition axis, an intumescent seal and ventilation seals have 
been installed. The partition’s blades rotate on their axes which are made of steel pins. On the blades, ventilation 
seals have also been installed. The blades are connected by means of a steel slat that provides the drive. Square 
and rectangular fire dampers have been equipped with flanged frames allowing to install them in ducts. In the case 
of a round duct, a square fire damper is manufactured and equipped with a circular flanged connection or a spigot 
is used. 

Summary of Contents for mcr WIP Series

Page 1: ...Ul Grzegorza z Sanoka 2 80 408 Gdańsk Phone 0 58 341 42 45 OPERATION AND MAINTENANCE MANUAL OMM mcr WIP fire damper Rev WIP 18 11 14 15 FIRE VENTILATION SYSTEMS DEPARTMENT ...

Page 2: ...NG PRINCIPLE OF THE FIRE DAMPER 4 5 MANUFACTURER S DESIGNATION OF THE FIRE DAMPER 5 6 INSTALLATION OF THE FIRE DAMPER 6 6 1 PRE INSTALLATION INSPECTION 6 6 2 INSTALLATION OPENING 6 6 3 BUILDING IN THE FIRE DAMPER 7 6 4 ELECTRICAL CONNECTIONS 12 7 TRANSPORT AND STORAGE CONDITIONS 16 8 MAINTENANCE AND SERVICE REPAIRS 16 9 WARRANTY TERMS AND CONDITIONS 16 Markings used in the OMM Option available Opt...

Page 3: ...ce of fire damper installation Manufacturing versions The mcr WIP type fire dampers may be manufactured as rectangular fire dampers rectangular fire dampers with circular connections round fire dampers Series of types of dimensions The mcr WIP type fire dampers are manufactured in the following dimensions width from 120 to 1 000 mm height from 160 to 1 000 mm rectangular fire dampers width 140 mm ...

Page 4: ...thout a return spring after applying voltage to the appropriate contact After widespread of the fire the damper closes after activation by the building fire protection system by applying voltage to the appropriate contact of the damper If dampers remain open during normal operation safety position air transfer closing them takes places automatically by actuation of the thermoelectric release manua...

Page 5: ...le conducting finishing work you should allow for the possibility of later access to the fire damper and removal of the release and control mechanism in order to carry out possible service work and technical inspections The mcr WIP fire dampers may be installed in the following space dividing elements walls or structural floors masonry concrete walls with a thickness of 120 mm brickwork walls or c...

Page 6: ...ially in a space dividing element a wall or structural floor that divides separate fire compartments i e in a previously prepared opening Next level and secure the fire damper so that it does not move For fire dampers with dimensions greater than 700 x 700 a strut should be used Once the above have been completed start manually the fire damper s partition blades assembly checking if it rotates cor...

Page 7: ...ectly When installing the mcr WIP type fire dampers ensure in particular that the thermal release fusible component is not damaged It should not be exposed to high temperature fire welders soldering irons which causes its actuation it is a component that has been designed to be used once only and will not be replaced under warranty Similarly the intumescent seals installed in the housing of the fi...

Page 8: ...nstallation of the protective grid for the mcr WIP type fire damper Protective grid thickness G shown in the figures should have 30 50mm depending on the thickness of the wall in 1 Grid blades 2 Internal frame 3 External frame 4 4 8 diameter rivet Modular protective grid for the mcr WIP type fire damper A modular protective grid may be supplied by the manufacturer of the fire damper or made by the...

Page 9: ...ations of the mcr WIP dampers modules can be made consisting of two or more dampers while maintaining the minimum distances between the dampers according to the drawing above 6 4 ELECTRICAL CONNECTIONS Once a fire damper has been correctly installed it is necessary to connect it to the electrical wiring system using the wiring system s cables if the fire damper is equipped with controls or other c...

Page 10: ...rating IP 54 IP 54 IP 54 IP 54 auxiliary switch activation point degrees 2 x PDT 3 0 5 A AC 250V 2 x PDT 3 0 5 A AC 250V 2 x SPDT 3 0 5 A 250 V 2 x SPDT 3 0 5 A 250 V 5 80 5 80 5 80 5 80 Torque motor spring 4 Nm 3 Nm 4 Nm 3 Nm 9 Nm 7 Nm 9 Nm 7 Nm Wire connection motor length 0 9 m auxiliary switch 2 x 0 75 mm2 6 x 0 75 mm2 2 x 0 75 mm2 6 x 0 75 mm2 2 x 0 75 mm2 6 x 0 75 mm2 2 x 0 75 mm2 6 x 0 75 m...

Page 11: ... T actuators Wiring diagram for BFL24 T BFL230 T BFN24 T and BFN230 T actuators Notice 24 V connection through a safety transformer Several actuators may be connected in parallel Power consumption should be monitored Notice 24 V connection through a safety transformer Several actuators may be connected in parallel Power consumption should be monitored ...

Page 12: ...d by the warranty conditions Technical data actuators EXBF 24 EXBF 230 Power supply 24 V AC 20 50 60 Hz 24 VDC 10 20 230 V AC 14 50 60 Hz Power demand when putting the spring under tension when in standby 7 W 2 W 8 W 3 W Apparent power 10 VA 12 5 VA IP rating IP 66 IP 66 Auxiliary switch activation point 2 x SPDT 6 A 3 max 250 V AC 5 80 2 x SPDT 6 A 3 max 250 V AC 5 80 Torque motor spring 18 Nm 12...

Page 13: ... NC type normally closed Wire no 7 8 NC type normally closed Warning Location of limit switches of the mechanism was shown for the damper safety position For proper operation of a device equipped with electrical actuators it is recommended that the rated voltage housed tolerance of 24V 2 or 230V 2 Power supply devices other than listed above may cause malfunction and will not be covered by the war...

Page 14: ...1 42 45 extension number 170 fax 058 341 39 85 8 am 4 pm Mon Fri 9 WARRANTY TERMS AND CONDITIONS 1 MERCOR S A gives a 12 month quality warranty for the products and unless an agreement provides otherwise the warranty period begins on the day of purchase 2 Should physical defects be identified in the warranty period MERCOR S A undertakes to rectify them no later than 21 days from the receipt of a w...

Page 15: ... in the following cases If the buyer warranty holder makes any modifications to the original design on their own i e without consulting MERCOR S A beforehand If the periodic technical inspections and maintenance are not carried out in time or are carried out by unauthorised persons or personnel of service stations not authorised by MERCOR S A or if the product have been used improperly If any tamp...

Reviews: