mcr WIP PRO
multi-blade fire damper
„
MERCOR” S.A. –
All rights reserved to modifications without prior notice
22/25
Connection diagram for the BEE24, BEN24, BEE230 and BEN230 actuators
Note:
The BE and BLE actuator operating control requires a three-wire system. The actuator sense of rotation is switched
by applying the supply voltage to terminal 2 or 3, depending on the desired sense.
The location of the limit switches for all types of actuators is shown for the position without voltage.
For proper operation of a device equipped with electrical actuators, it is recommended that the rated voltage housed
tolerance of 24V±10% or 230V±10%. Power supply devices other than listed above may cause malfunction and will
not be covered by the warranty conditions.
EXBF actuators
Technical specifications
EXBF 24
EXBF 230
Zone
1, 2, 21, 22
ATEX classification
II 2 GD EEx d IIC T6
Power supply
24 V AC ±20% 50/60 Hz / 24 VDC-10/+20%
230 V AC ±14% 50/60 Hz
Power demand:
- for spring tensioning
7 W
8 W
- for spring holding
2 W
3 W
Sizing (apparent power)
10 VA
12.5 VA
Ingress protection rating
IP 66
IP 66
Auxiliary circuit breaker:
2 x SPDT 6A (3) max 250 V AC
2 x SPDT 6A (3) max 250 V AC
- activation position
5
, 80
5
, 80
Torque:
- motor
18 Nm
18 Nm
- spring
12 Nm
12 Nm
Movement time: (90°)
- motor
150 s
150 s
- return spring
20s
20s
Ambient temperature
- 20 ...+50°C
- 20 ...+50°C
EX zone
EEx-e rated installation box
Thermal
trigger