„MERCOR” SA –
the Company reserves the right to make modifications and changes.
12/24
1. Fire damper
2. E.g. cement mortar
3. Wall
4. Ventilation duct
X – wall thickness
The minimum depth of filling with mortar for the length of the body of the device.
Installation of the mcr FID PRO fire damper with an electric mechanism
in masonry walls, brickwork walls or blockwork walls using mortar
1. Fire damper
2. Mineral wool with a density min. 150 kg/m3
3. mcr Polylack Elastic 1mm thick
4. Wall
5. Ventilation duct
X – wall thickness
The minimum depth of filling with mortar for the length of the body of the device.
Installation of the mcr FID PRO fire damper with an electric mechanism
in masonry walls, brickwork walls or blockwork walls using mineral wool