SETPOINT ADJUSTMENT

1. Determine the setpoint pressure. The approximate actuation point can be set by 

turning the adjustment cap up or down, aligning the top of the O-ring, located above 

the cap, with the appropriate scale graduation.

2. Connect tubing or piping from the pressure port on bottom of switch to one leg 

of a tee. Connect the second leg to a pressure test gage of known accuracy and in 

an appropriate range. The third leg should be connected to a controllable source of 

pressure.

3. Connect a volt/ohm meter or other circuit tester to the snap action terminals to  

indicate when switching occurs.

4. Slowly apply pressure to the system and note the pressure at which switching 

occurs.

5. Operate the switch through several cycles to confirm proper actuation point.

6. Remove test apparatus and attach switch to pressure source and control circuit 

wiring. Place switch in service. 

Example of how to order:

A1F  -  O  -  SS  -  1  -  4 

    1      2       3       4     5

1.  Diaphragm Designation:

    F - Fluorocarbon

2.   Enclosure Designation:

    O - Open Construction No Enclosure

3.   Housing Material Designation:

    SS - 316SS

4.   Switch Designation:

    1 - SPDT Snap Action Switch

5.   Operating Pressure Range Designation:

    1 - 2 to 15 psig

    2 - 4 to 75 psig

    3 - 8 to 225 psig

    4 - 16 to 450 psig

MAINTENANCE

Upon final installation of the Series A1F Compact OEM Pressure Switch, no routine 

maintenance is required. A periodic check of the system calibration is recommended. 

The  Series A1F  is  not  field  serviceable  and  should  be  returned  if  repair  is  needed 

(field repair should not be attempted and may void warranty). Be sure to include a 

brief description of the problem plus any relevant application notes. Contact customer 

service to receive a return goods authorization number before shipping.

DEADBAND CHART-PSIG (BAR)

Range

Deadband at 

Minimum Range

Deadband at 

Maximum Range 

2 to 15 (0.14 to 1.03)

4 to 75 (0.28 to 5.17)

8 to 225 (0.55 to 15.5)

16 to 450 (1.1 to 31.0)

2 (0.14)

4 (0.27)

8 (0.55)

15 (1.0) 

3 (0.21)

15 (1.0)

25 (1.7)

50 (3.5)

MERCOID 

P.O. BOX 373 • MICHIGAN CITY, INDIANA 46360, U.S.A.

Phone: 219/879-8000
Fax: 219/872-9057

www.dwyer-inst.com
e-mail: [email protected]

A DIVISION OF

DWYER INSTRUMENTS, INC.

Reviews: