28
Chapter 5 • Commissioning
User Manual FSK700-2 / FSK700-2SX
5
Commissioning
The locking bolt supplied in the accessory kit must only be installed in the outer door after
both the Fire Brigade Key Safe and the connected controlling and monitoring device are
fully operational! Should the electrical unlocking device not be fully operational upon clos-
ing the outer door with installed locking bolt, the Key Safe can only be opened again by
means leading to the destruction of some of its componentry (e.g., outer door, Drill Protec-
tion Board). Additional advice can be found on page 29 and onwards in chapter 5.4: "Com-
missioning instructions".
5.1
General
Commissioning, inspection, and maintenance of the Series FSK700 Fire Brigade Key Safe is to be
performed by a specialist company trained and authorised by MEP-Gefahrenmeldetechnik GmbH
or their local representative (see page 7 and onwards in chapter 1.6: "Important advice for the oper-
ator and specialist installer").
All tasks performed are to be entered in the report book of the corresponding alarm system.
5.2
Notes on insurance protection
The keeping of keys in a Fire Brigade Key Safe results in an increased level of danger, which
the insurance company must be informed of.
If the key depot is not VdS-certified and/or is not installed, operated and maintained
according to the VdS-Richtlinien für Schlüsseldepots, Planung, Einbau und Instandhaltung
(VdS 2350), it is possible that no insurance protection is available for damages due to burg-
lary, in case the building has been opened using the (real) key taken from the key depot.
5.3
Configuration with jumpers
5.3.1
Activation temperature of the outer door heating device
The heating device for the outer door can be set to activate at a temperature of +10°C or +5°C, as
well as set to continuous operation by moving or removing the jumper on the Door Protection
Board, as pictured in Fig. 20 below. At factory default settings, the heating device is set to activate
at a temperature of +10°C.
Fig. 20:
Setting the activation temperature of the heating device on the Door Protection Board
To be able to move the jumper, the Door Protection Board must be removed from the outer
door. It is essential that the Key Safe is rendered currentless (e.g., by switching off the
voltage of the controlling and monitoring device and the heating device) prior to this!
5.3.2
Acoustic warning signal when missing master key
If the Series FSK700 Key Safe is closed after the fire alarm has been reset, and not all master keys
have been inserted correctly, the Key Safe's integrated buzzer will sound as warning.
This function is only available if the Key Safe is connected to the Key Safe Controlling and
Monitoring Device AD900-1 by MEP-Gefahrenmeldetechnik GmbH.
Should this function be undesired, Jumper JP1 must be removed from Connection Board APL-4
(see Fig. 13 on page 21).
HB_FSK700_1020_9161690_Englisch_D.odt / 1022 D / AN9161690
ZN62163/38/28
28