85-03-01103
FV41 ARCH
Page
56
4.10
NATURAL GAS TO LPG CONVERSION
WARNING
This conversion kit shall be installed by a qualified service agency in accordance with the manufacturer’s
instructions and all applicable codes and requirements of the authority having jurisdiction. If the
information in these instructions is not followed exactly, a fire, explosion or production of carbon monoxide
may result causing property damage, personal injury or loss of life. The qualified service agency is
responsible for the proper installation of this kit. The installation is not proper and complete until the
operation of the converted appliance is checked as specified in the owner instructions supplied with the kit.
WARNING: Failure to position the parts in accordance with these diagrams or failure to use only parts
specifically approved with this appliance may result in property damage or personal injury.
General Conversion Information
WARNING: Failure to position the parts in accordance with these diagrams or failure to use only parts
specifically approved with this appliance may result in property damage or personal injury.
Kit # HA-92-00014 for Mendota Model FV41 ARCH
This conversion kit shall be installed by a qualified service agency in
accordance with the manufacturer’s instructions and all applicable codes
and requirements of the authority having jurisdiction. If the information
in these instructions is not followed exactly, a fire, explosion or
production of carbon monoxide may result causing property damage,
personal injury or loss of life. The qualified service agency is responsible
for the proper installation of this kit. The installation is not proper and
complete until the operation of the converted appliance is checked as
specified in the owner instructions supplied with the kit.
Caution: The electrical supply to the fireplace must be turned
off prior to performing the conversion. The gas supply must
be shut off prior to disconnecting the electrical power.
Orifice sizes requirement
A Natural Gas to LPG conversion kit #HA-92-00014 must be ordered and installed to convert the FV41 ARCH Fireplace to burn
LPG. LP Conversion Kit # HA-92-00014 contains the following parts: One motorized LP pressure regulator #907.012 and two cap
orifices (drill #54).
Procedure to Convert This Fireplace to Burn LPG
This Fireplace arrives from the factory ready to burn natural gas. If you intend to burn LPG, it is recommended that you convert
this fireplace and its pressure regulator, pilot orifice slider position and burner orifices prior to placing this fireplace in its
framed cavity. See diagrams, on this page, and follow these instructions to prepare this fireplace for conversion to LPG.
Figure 4-10 HA-92-00014 LP Kit Parts
Figure 4-11 Conversion Preparation
REMOVE SCREWS
FIRST.
REMOVE LOG GRATE