Step  14.

Check the Status LEDs and confirm that all of the LEDs show status lights consistent 
with normal operation.

Step  15.

You can start connecting all of the cables to the switch.

Grounding the Switch

You must install an external ground to all IT components. To this purpose there are two threaded screw 
holes marked as grounds. Connect a  ground wire to one of these grounds and connect the other end to a 
valid ground.  Do not rely on the power connection ground. If you choose to not use the ground screw, 
make sure that there is a valid ground connection between the chassis of the switch and the grounded rack. 
Test the ground using an Ohm meter.

Note: Grounding wires, screws, and connectors for the ground are not supplied by Mellanox.

Configuring the Switch for the First Time

Note: Unmanaged (Externally managed) switches, that is the IS5025 switches, do not get configured. On 

unmanaged switches, the CONSOLE, Ethernet, and USB connectors are not found. Instead there is 
an I2C connector.

Step  1.

Connect the host PC RS232 connector to the CONSOLE  port of the switch using the supplied 
cable

Note: No remote IP connection is available at this stage.

Step  2.

Configure a serial terminal program (for example, HyperTerminal, Minicom, or Tera 
Term) on your host PC with the settings described in Table 3.

Table 3 - Serial Terminal Program Configuration

Parameter

Setting

Baud Rate

9600

Data bits

8

MGT

IS5030

CONSOLE

Connect the host 
PC to here

Summary of Contents for IS5025

Page 1: ...itch in a 19 rack whose vertical supports are between 50cm and 80cm apart Table 1 Switches and Rail Kits for Various Rack Depths Table 2 Mellanox Part Numbering Legend Place Field Decoder IS System Type InfiniScale Switch 50 Model Family FF Form factor 25 36 Ports Unmanaged 30 36 Ports and Chassis Management with limited Fabric Management 35 36 ports and Fabric Management C InfiniBand Port Config ...

Page 2: ...ou will be working and put on the ESD strap Make sure the ESD strap is touching your skin and that the other end is connected to a verified ground Step 2 Choose which side of the switch you want even with the vertical rack support Either the side with the power supply units or the side with the IB connectors can be even with the vertical rack support The other side of the switch will be further in...

Page 3: ... vertical support of the rack and the second option will recess the switch fur ther into the rack Note The side of the switch with these brackets will be the side that is even with the vertical rack support Step 4 Screw the rails onto the switch Use the 5 flat head screws to connect each rail to the switch The distance between the rack and the door can be as little as 4 cm on one side of the rack ...

Page 4: ...he bolts to 9 2 Nm or 81 5 pound inches Step 8 If the power cable is on this side of the switch feed the power cable into the slot in the rail slide before screwing it to the vertical support Step 9 Place the four bolts for the caged nuts within reach Step 10 Slide the switch into the rails Step 11 Put the switch into place and screw the bolts into the nuts from step 6 If the power cable is on thi...

Page 5: ...he grounded rack Test the ground using an Ohm meter Note Grounding wires screws and connectors for the ground are not supplied by Mellanox Configuring the Switch for the First Time Note Unmanaged Externally managed switches that is the IS5025 switches do not get configured On unmanaged switches the CONSOLE Ethernet and USB connectors are not found Instead there is an I2C connector Step 1 Connect t...

Page 6: ... press Enter Otherwise type a different host name and press Enter Step 2 Use DHCP on eth0 interface Yes Perform this step to obtain an IP address for the gateway eth0 is the management port of the gate way If you wish the DHCP server to assign the IP address type yes and press Enter If you type no no DHCP then you will be asked whether you wish to use the zeroconf config uration or not If you ente...

Page 7: ...o the wizard from the CLI enter the configuration jump start command from configuration mode Launching CLI bridge 1 The wizard displays a summary of your choices and then asks you to confirm the choices or to re edit them Either press Enter to save changes and exit or enter the configuration step number 1 2 or 3 that you wish to return to Note To run the command configura tion jump start you must ...

Page 8: ...Primary DNS server Step 6 Domain name Step 7 Admin password Enter to leave unchanged You have entered the following information 1 Hostname bridge 112428 2 Use DHCP on eth0 interface no 3 Use zeroconf on eth0 interface yes 4 Default gateway 192 168 10 1 5 Primary DNS server 6 Domain name 7 Admin password Enter to leave unchanged unchanged To change an answer enter the step number to return to Other...

Page 9: ...f on eth0 interface no Step 4 Primary IP address 192 168 10 4 Mask length may not be zero if address is not zero interface eth0 Step 5 Netmask 0 0 0 0 255 255 255 0 Step 6 Default gateway 192 168 10 1 Step 7 Primary DNS server Step 8 Domain name Step 9 Admin password Enter to leave unchanged You have entered the following information 1 Hostname bridge 112428 2 Use DHCP on eth0 interface no 3 Use z...

Page 10: ...X discards 0 RX errors 0 RX overruns 0 RX frame 0 TX bytes 122850 TX packets 1119 TX discards 0 TX errors 0 TX overruns 0 TX carrier 0 TX collisions 0 bridge 112428 Step 4 Before attempting a remote for example SSH connection to the switch check the eth0 interface configuration Specifically verify the existence of an IP address To check the current eth0 configuration enter the following commands s...

Page 11: ...use of FabricIT cluster management See the FabricIT EFM User Manual for instructions and commands available to manage the chassis switches and fabric Starting an SSH Connection to the Switch Note SSH connection also supports TelNet Step 1 Set up an Ethernet connection between the switch and a local network machine the remote machine henceforth using a standard RJ 45 connector Step 2 Connect to the...

Page 12: ...ch Step 5 Use admin for both the login Account and the password The MIS50XXSeries User Manual can be found at http www mellanox com Products Switches InfiniBand Switch Systems IS5025 IS5030 IS5035 Resetting the Switch On the connector side panel under the system LEDs is a reset button This reset button requires a tool to be pressed a paper clip will do Figure 3 Reset Button This button resets the ...

Reviews: