Technician Settings

Tel: +972-3-9626462

Fax: +972-3-9626620

support@meitavtec

.

com

FMT24-SUPER

Owner’s manual & Technnician Settings

Pg. 6

Enter technician settings mode

Adjust the set point temperature to 10°C (50°F)
Press and hold the [SELECT] button for 5 seconds to enter technician 
settings mode.

Temperature limit for cooling

“Cool” will flash.
Use the [+] and [-] buttons to adjust the temperature limit for cooling.
Range: 10...30°C (50...88°F), Default 10°C (50°F).

Limit Cool (°C)

Limit Cool (°F)

Cool

Cool

Cool

Cool

Enter tech. 

settings

Enter tech. 

settings

°C

°F

Temperature limit for heating

Press the [SELECT] button again – “Heat” will flash.
Use the [+] and [-] buttons to adjust the temperature limit for heating.
Range: 10...30°C (50...88°F), Default 30°C (88°F).

Temperature scale

Heat

Heat

Limit Heat (°C)

Limit Heat (°F)

Press the [SELECT] button again – “C” or “F” will appear on display.
Use the [+] and [-] buttons to select between:

“C”…….… Celsius
“F”…...….. Fahrenheit 

Celsius

Fahrenheit 

Offset for calibration of measured temperature

Press the [Mode] button again – the offset will appear on display.
Use the [+] and [-] buttons to adjust the offset.
Range: -6…+6°C (-6…+6°F), Default 0°C (0°F).

Offset(°C)

Offset (°F)

Terminal “W1” configuration - Heat pump or heat element

Press the [SELECT] button again – “HC” or “HP” will appear on display.
Use the [+] and [-] buttons to select between:

“HC”…….…Heat element connected to “W1”
“HP”…...…..Heat pump connected to “W1” 

Heat element

Heat pump