DIP switch S2 settings
Tel: +972-3-9626462
Fax: +972-3-9626620
support@meitavtec.com
ETNC24-SUPER-MDB-01
Owner’s manual & Technician Settings
Pg. 9
Selecting temperature display –
1- Normal display shows room temp. and [+] or [-] buttons shows the set point.
2- Normal display shows the set point. Room temp. cannot be displayed.
Display both room and set point temp. (default)….…... S2.1 On
Display set point temperature only…….…………….…. S2.1 Off
ON
1 2 3 4 5 6
ON
1 2 3 4 5 6
Set point & Room
Set point only
Fan speeds configuration
One Fan speed (default)………...…...…….. S2.2 Off S2.3 Off
Two Fan speeds…………….……..….…….. S2.2 On S2.3 Off
Three Fan speeds…………….……….……..S2.2 On S2.3 On
Enabling or disabling Auto change over mode
Enable the use of Auto mode (default)…………….……S2.4 On
Disable Auto mode……………………...…………...……S2.4 Off
Enabling or disabling the 3 minutes compressor delay
3 Minutes compressor delay (default)….………...….….S2.6 Off
No compressor delay….………………...…………..……S2.6 On
Temperature scale
Fahrenheit (default)…………………….……...…….……S2.5 On
Celsius………………….………………...…...……...…… S2.5 Off
ON
1 2 3 4 5 6
ON
1 2 3 4 5 6
ON
1 2 3 4 5 6
One speed
Two speeds
Three speeds
ON
1 2 3 4 5 6
ON
1 2 3 4 5 6
Enable Auto
mode
Disable Auto
mode
ON
1 2 3 4 5 6
ON
1 2 3 4 5 6
Fahrenheit
Celsius
ON
1 2 3 4 5 6
ON
1 2 3 4 5 6
3 Minutes delay
No delay
Important: Disconnect power to the unit before changing the
configuration of the DIP switches.
On
1 2 3 4 5 6
Default position:
S2
ON
123456
ON
123456
S2
S1