Weekly Program
The thermostat is 7-DAY PROGRAMMABLE.
It can be programmed with up to 7 different programs, 1 for each day, with start time and stop time
Enable/Disable/Override the weekly program
Press & Hold the [Prog] button (20 sec.) to enable/disable the program.
When enabled, the words “Start” or “Stop” will appear on display.
To exit programming mode, press the [On/Off] button until normal display is reached or wait 30 seconds.
Technician Settings
Adjust the set point temperature to 10°C. Wait until display stops flashing.
Press and hold the [Select] button (5 sec.) to
enter technician settings
.
Use the [Select] button to switch between different configurable parameters.
Use the [+] and [-] buttons to make adjustments or switch between options.
Set point temperature limit for cooling
Indication: “Cool” and the set point Temperature limit
for cooling. Range: 5...30°C, default 5°C.
Set point temperature limit for heating
Indication: “Heat” and the set point temperature limit
for heating. Range: 5...30°C, default 30°C.
Offset for calibration of the measured temperature
Indication: “Offs” and a number between (-6) and (+6).
Range: -6...+6°C, default 0°C.
Adjust the
Set-point
To 10
°C
Set point
limit for
cooling
Set point
limit for
heating
Offset for
temp.
readings
ºC
Set
ON
Select
Select
Tel: +972-3-9626462
Fax: +972-3-9626620
www.meitavtec.com | [email protected]
ETN24-SUPER-PROG-US-C-LOCK-7DAYS
Owner’s manual & Technician Settings
Press
And
Hold
Select
Select
Return
To normal
display
Note that the words “Start” or “Stop” on
display will indicate the current status of the
weekly program as follows:
Override the program (After hours timer):
The word “Stop” will flash when the occupant
manually turned the unit ON, during stop
event. Override period is 2 hours before
turning the unit back OFF.
“Start”
Hours
Minutes
Day
Start
time
Hours
Real time clock
Program - Monday
Repeat the
procedure for all the
other days
Wed
Tue
Prog
Prog
Prog
Prog
Prog
Prog
Start
time
Minutes
Stop
time
Hours
Prog
Prog
Stop
time
Minutes
“Stop”
Programmed
Stop time
”Stop”
& Unit OFF
Manual
Start
(Override)
“Stop” flashing
& Unit ON
2 Hours (After hours)
Programmed
Start time
(today)
Programmed
Stop time
(today)
Programmed
Start time
(next day)
Programmed
Stop time
(next day)
“Start”
”Stop”
& Unit OFF
“Stop”