Enter technician settings mode
Adjust the set point temperature to 50°F
Press and hold the [Mode] button for 5 seconds to enter technician settings mode.
Temperature limit for cooling
“Cool” will flash.
Use the [+] and [-] buttons to adjust the temperature limit for cooling.
Range: 50...95°F, Default 50°F.
Temperature limit for heating
Press the [Mode] button again – “heat” will flash.
Use the [+] and [-] buttons to adjust the temperature limit for heating.
Range: 50...95°F, Default 95°F.
Offset for calibration of measured temperature
Press the [Mode] button again – the offset will appear on display.
Use the [+] and [-] buttons to adjust the offset.
Range: -6…+6°F, Default 0°F.
Limit Cool
Heat
°F
°F
Cool
Limit Heat
Offset
°F
°F
Temperature set-point for cooling in economy mode
Press the [Mode] button again - “Cool” and “Aux” will flash.
Use the [+] and [-] buttons to adjust the temperature limit for cooling in economy mode.
Range: 52...95°F, Default 95°F.
Temperature aet-point for heating in economy mode
Press the [Mode] button again – “heat” and “Aux” will flash.
Use the [+] and [-] buttons to adjust the temperature limit for heating in economy mode.
Range: 50...93°F, Default 50°F.
Limit Cool (EC)
Heat
°F
Cool
Limit Heat (EC)
°F
Time delay between cooling stages
Press the [Mode] button again – “Aux” will flash.
Use the [+] and [-] buttons to adjust the time delay between cooling stages (compressors).
Range: 1...10 Minutes, Default 1 Minute.
Cool/Heat Dead zone
Press the [Mode] button again – the temperature scale symbol will flash.
Use the [+] and [-] buttons to adjust the dead zone between cooling and heating.
Range: 2...10°F, Default 2°F.
Press the [Mode] button again to return to normal display.
Time delay
Aux
Dead zone
°F
Set point = 50
°F
Aux