Operating instructions

ON-OFF

Press the [Mode] button to switch between modes:

“Cool”………………… Cooling 
“Heat”………………… Heating 
“Cool” & “Heat”……… Auto mode
“Fan”…………………. Fan only

Notes: 

1. During demand for cooling or heating, the active mode will flash.
2. Heat and Auto modes are not available in cool only configuration.

Press the [On/Off] button to turn the thermostat ON or OFF.

Modes

Set point

Press the [+] or [-] buttons once to view the set point temperature. 
Press again to adjust the set point.

Cool

Heat

Cool
Heat

Fan

Cool

Heat

Auto

mode

Fan only

Tel: (856) 2882882

Tel: +972-3-9626462

Fax: +972-3-9626620

support@meitavtec

.

com

File: ETN24-SUPER-SH-F_operating manual.vsd

ETN24-SUPER-SH-F

Owner’s manual & Technnician Settings

Pg. 1

For 3 speed configuration:

Press and hold the [Fan] button (5 sec.) to turn Auto fan ON or OFF.
When ON, the fan will work on demand for cooling or heating,
When OFF, the fan will work continuously.

Note: Auto fan cannot be selected in Fan only mode.

For 1 speed configuration:

Press the [Fan] button to turn Auto fan ON or OFF.
When ON, the fan will work on demand for cooling or heating,
When OFF, the fan will work continuously.

Note: Auto fan cannot be selected in Fan only mode.

Note: in Oil/Gas systems, with Auto Fan ON, the fan will never be activated.

Auto fan (fan on demand)

Auto fan

OFF

Auto fan

ON

Auto Fan

         Fan

Press the [Fan] button to switch between fan speeds:

“Lo”…………………… Low speed 
“Me”……………...……Medium speed
“Hi”………………….…High speed
“Auto”………………….Auto speed

Note: In Auto speed, the active fan speed will flash.

Fan speeds (for 3 speed configuration only)

Low

speed

Medium

speed

High

speed

Auto

speed

Lo

Hi
Me
Lo

Hi

Me

F

o

Aux

Summary of Contents for ETN24-SUPER-SH-F

Page 1: ... 1 For 3 speed configuration Press and hold the Fan button 5 sec to turn Auto fan ON or OFF When ON the fan will work on demand for cooling or heating When OFF the fan will work continuously Note Auto fan cannot be selected in Fan only mode For 1 speed configuration Press the Fan button to turn Auto fan ON or OFF When ON the fan will work on demand for cooling or heating When OFF the fan will work...

Page 2: ...main board before installing the unit The standard height to install this unit is 1 5 meter 5 feet from the floor Installation procedure A Separate the front panel from back panel by pressing the tongue located in the top of the unit and pull the back panel out B Line the back panel up against the wall or flat surface Install three screws as required C Make electrical connections as shown on enclo...

Page 3: ... stg Comp 2 2nd stg Fan low Fan high Comp 1 External sensor option Y1 G G1 0 Y2 T Y3 G3 IN 0 W2 G2 C R W1 Cool and heat configurations with 1 or 3 fan speeds Fan Terminals Terminals Select your configuration set by DIP switches S1 2 and S2 4 Y1 G G1 0 Y2 T Y3 G3 IN 0 W2 G2 C R W1 Note If only one compressor is being used connect it to Y1 1st stage cool If two compressors are being used connect the...

Page 4: ...al sensor S2 1 S2 3 OFF S2 2 ON ON 1 2 3 4 5 6 ON 1 2 3 4 5 6 ON 1 2 3 4 5 6 Internal sensor External sensor ON 1 2 3 4 5 6 Cool only without heaters or Cool and heat Heaters and compressors configuration Use DIP Switch S2 4 to select cool heat configuration Cool only S2 4 OFF Cool and heat S2 4 ON ON 1 2 3 4 5 6 Cool only Cool and Heat ON 1 2 3 4 5 6 Temperature display ON 1 2 3 4 5 6 Set point o...

Page 5: ...pressor time delay Use DIP Switches S1 3 to enable disable the 3 minutes compressor time delay as follows 3 Minutes delay S1 3 OFF No delay S1 3 ON ON 1 2 3 4 5 6 3 Minutes delay No delay ON 1 2 3 4 5 6 Important Switches 4 and 6 are not in use and must remain OFF S1 S1 Heater type Use DIP Switches S1 5 to select heater type as follows Electrical heater S1 4 OFF Oil Gas heater S1 4 ON Note In Heat...

Page 6: ... Cool Heat F F Cool Limit Heat Offset F F Temperature set point for cooling in economy mode Press the Mode button again Cool and Aux will flash Use the and buttons to adjust the temperature limit for cooling in economy mode Range 52 95 F Default 95 F Temperature aet point for heating in economy mode Press the Mode button again heat and Aux will flash Use the and buttons to adjust the temperature l...

Page 7: ...ee technician settings In Economy mode the thermostat will use predefined set point temperatures selected by technician instead of the set point selected by the occupant If OFF was selected the thermostat will turn off and EC and Off will appear on display Fault input alarm Lock thermostat buttons Make sure the set point temperature is not 50 F Press and hold the Mode button for 5 seconds to lock ...

Page 8: ...Tel 856 2882882 Tel 972 3 9626462 Fax 972 3 9626620 support meitavtec com www meitavtec com ...

Reviews: