BDIR – Technician Settings

Meitav-tec Ltd (Contel group)
Tel: +972 (3) 962 6462   Fax: +972 (3) 962 6620
www.meitavtec.com - [email protected]

It is recommended to mount the thermostat between 1.5 & 1.8 
meters from the floor where possible.
Separate the base from the cover by pressing the tongue (pic.1).
Gently disconnect the quick connector between cover and base 
(pic.2) 
Line the back panel up against the wall and drill the appropriate 
fixing holes (pic.3).
Insert screws so they extend approx. 3/16" (3 mm) from the wall. 
Align the back panel against these screws, pushing it forward, 
allowing it to slide downwards to lock into position.
Make electrical connections to terminals on the back panel. Refer 
to the “Wiring Connections” section. 
Reconnect the quick connector.
Change the JUMPERS position according to the system 
configuration. Refer to the “Jumper Configuration” section.
Attach the cover to the base, first the two shafts and then the 
spring.
Connect 24Vac to the thermostat; verify that LCD display is ON. 

Do not install battery before power is applied.

Remove battery from back panel by sliding it to the left and out from 
its white retaining clip and mount it in black holder on front panel; 
insert it from the top, gently pressing downwards until it snaps into 
place and is held under the top clip of the holder.
The '+' engraved on battery should be visible (pic. 4).

Be careful - the top clip of the battery holder is fragile.

Reassemble front and back cover.
Connect at top first then at bottom.

Installation Instructions 

Pic.3

Battery Holder

Back panel

Front panel

+

Pic.4

Quick connector

Shafts

Pic.2

Spring tongue

Spring tongue

Pic.1

 

Wiring Connections

Terminal

Function

HC11 HC22 HC32

HP22 HP32

T0,T0

T1,T1

AUX

Y1

Y2

W1

W2

W3

G1

G2

AL,AL

Rc

Rh

C

14,15,16

Not in use

External sensor (option)

Not in use

Compressor 1

Compressor 2

Heat Element 1 / Heat Pump

Heat Element 2

Heat Element 3

Fan

Not in use

Not in use

24Vac Phase (red)

24Vac (jumpered to 

Rc

 terminal)

24Vac Common

Another IR Receiver (option)

-

-

+

-

H.E 1

-
-

+

-
-

+

+
+

-

-

+
+

H.E 1

+

-

+

-
-

+

+
+

-

-

+
+

H.E 1

+
+
+

-
-

+

+
+

-

-

+

H.P

-

+

-
-

+

+
+

-

-

+
+

H.P

+

-
-

+

+
+

OPT

-

Not 
in use

+

Connect

Heat 
element 1

H.E 1

Heat 
Pump

H.P

Option

OPT

Jumpers Configuration

Disconnect power, 
remove battery and 
wait 5 minutes* before 
changing the jumpers 
position.
*No need to wait if the 
unit wasn’t connected 
to power (1

st

 Install).

Important:

When 

changing the jumpers 
configuration, all 
information stored in 
the memory will be lost 
including the weekly 
program.

HC Electric

JP6

JP7

OPEN

SHORT

HC Oil/Gas

HP energized in HEAT

HP energized in COOL

OPEN

OPEN

SHORT

OPEN

SHORT

SHORT

Internal sensor

JP1

A Position

External sensor

B Position

4 minutes  delay 

JP3

OPEN

No delay (for test only !)

SHORT

HC / HP Configuration

Temperature Sensor

Compressor Delay

24 Hours

JP4

OPEN

12 Hours (AM/PM)

SHORT

Clock Mode

Celsius

JP5

OPEN

Fahrenheit

SHORT

Temperature Scale

Default from 
factory

JP3

JP4

JP5

JP6

JP7

JP1

A

B

External Sensor Connection

Installation Procedure

Disconnect power to the thermostat.
Move JP1 to “B” position and connect the sensor to “T1” terminals.
Reconnect power.

Important:

The sensor must be MEITAV-TEC type.

NTC Sensor: Temperature ~ Resistance Characteristics

Temperature (

o

C)

Resistance (K

)

7.2 10.0 12.8 15.6 18.3 21.1 23.9 26.7 29.4 32.2

115.8 100.9 88.1 77.1 67.7 59.6 52.5 46.4 41.2 36.6

-

-

+

+

OPT

OPT

OPT

OPT

OPT

OPT

OPT

OPT

OPT

HP11

-

-

+

H.P

-

+

-
-

+

+
+

-

OPT

OPT

-

File: bdir-operating maual.vsd | Date: February 1, 2007 | Rev. 3