2 Important Safety Information
AC Power Supply
DC Power Supply
•
The device is a device of protection
class 1 and may only be connected to a
grounded outlet (TN system).
•
For safe operation, the device must be
protected by an installation fuse of max.
16 A and equipped with a residual current
circuit breaker in accordance with the
applicable national standards.
•
The unit must always be disconnected from
the mains and not from the appliance.
•
Devices with mains plugs are equipped
with a safety-tested mains cable of the
country of use and may only be connected
to a grounded shockproof socket, otherwise
electric shock may occur.
•
Make sure that the mains socket on the
appliance or the mains socket of the house
installation is freely accessible to the user
so that the mains cable can be pulled out
of the socket in case of emergency.
•
Outside the assembly group the device must be
disconnectable from the power supply in
accordance with the provisions of IEC 60950-1
(e.g. by the primary line protection).
•
Installation and disassembly of the power supply
plug is only permitted if the assembly group is
switched off (e.g. by the primary line protection).
•
The supply lines must be adequately secured and
dimensioned.
Connection Cross Section:
1 mm
2
–
2.5 mm
2
17 AWG
–
13 AWG
•
The device must be supplied with a suitable
disconnector (switch). The separation device must
be easily accessible, placed near the device and
marked as a separation device for the unit.
LANTIME M300/TCR
Date: 3rd September 2019
7
Summary of Contents for LANTIME M300/TCR
Page 2: ......