4.Power Estination
MC200E main modules have an internal power supply module, give
priority to itself, the expansion module and other electric equipment
with power. The power performance index is as follows:
Project
Unit Min Rated Max Note
Input Voltage
Range
Vac
90
220
264
Normal operating range
and start machine
Input Current
A
/
/
1.5
90Vac Input
,
Loaded
with output
MC200E Lord module provides 5 V dc logic power supply (5 V/GND)
and 24 V dc logic power supply (24 V/GND) for self and all extension
module. At the same time MC200E Lord module can also provide 24 V
dc power supply (24 V/COM), the 24 VDC can input point or other
equipment for power supply, MC200E series provide active I/O
extension module, the 5 V/GND, 24 V/GND, 24 V/COM output can be
used as the subsequent passive extension module of power supply.
Model
5V/GND
To provide the
maximum capacity
expansion module
24V/GND
To provide the
maximum capacity
expansion module
24V/COM
Offer capacity
to foreign
MC200E-1616BTA
525 mA
600mA
460 mA
*5 V/GND (24 V/GND) for the maximum capacity is refers to, When 24
V/GND (5 V/GND) no load, which can provide the maximum output
capacity.
5. Connect the power cord and grounding lines
MC200E communication power input module and auxiliary power
connection examples below:
COM
+24V
N
L
POWER
S/S
Y0
COM0
Y1
COM1
Y2 Y3
Y4 Y5
Y6 Y7
COM2
Y10 Y11
COM5
X0 X1 X2 X3 X4
X16 X17
MC280-1616BTA
X0 X1
X7
+24V
Y0 Y1
COM0
Y2
MC200-0808ER
AC - L
AC - N
+24V
+5V
GND
传感器
编码器
+24V
VGND
COM3
The AC power and auxiliary power connection examples
6.
The User Terminals Introduction
MC200E-1616BTA Terminal definition
Pins
Identification
Fuction Declaration
L/N
220V AC power input
,
respectively firewire,zero line
Ground wire terminals PG
Pins
Identification
Fuction Declaration
+
24V
Auxiliary DC power for users’ external equipment, work with
COM
COM
Negative pole of +24V auxiliary power
S/S
Input mode selection: sink mode when connected with +24V,
or source mode when connected with COM
●
Null, for isolation. Leave it suspended
X0
~
X17
Switching signal inputs, work with COM to generate input
signal
Y0
、
Y1
、
COM0
Control
output
terminals, group 0
The COMx of different output
groups are isolated from each
other
Y2
、
Y3
、
COM1
Control
output
terminals, group 1
Y4
、
Y5
、
COM2
Control
output
terminals, group 2
Y6
、
Y7
、
COM3
Control output
terminals, group 3
Y10
~
Y13
、
COM4
Control output
terminals, group 4
Y14
~
Y17
、
COM5
Control output
terminals, group 5
7. Switch input and output characteristics
7.1 The switch quantity input X port specifications
Project
Specification
Signal Input Metherd
Source type/leak type way, the user can
choose through the S/S terminal.
Electrical
Specificatio
n
Detaction
Voltage
24Vdc
Input
Impedance
X0
~
X7 terminal
:
3.3k
Ω。Other port
4.3k
Ω
Input is
ON
External loop resistance is less than 400 Ω
Input is
OFF
External loop resistance is more than 24 kΩ
Filter
function
digital
filtering
X0 ~ X7 have digital filter function, filtering
time can be set by the user program
Hardwar
e filter
Input terminals other than X0 ~ X7 are
hardware filters. Filtering time is about 10ms
High-speed function
X0~X7: high-speed counting, interrupt, and
pulse catching .X0
~
X7 terminals are up to
10kHz Max.
Public terminal
S/S terminal,a public terminal
MC200E series PLC to provide a port "S/S", Used to select the input
signal is input source type way or leak type input methods.
The S/S terminals and + 24 V terminal connected, that is set to leak
type input methods, can connect NPN type sensor. Sink input
equivalent circuit of the internal and external wiring is shown below
Internal logic circuit work power
24V/5V /GND
24 V dc
auxiliary power
Sensor
+
24V
COM
24V
+
24V
-
Logic
Control
Circuit
PLC
AC equivalent circuit inside the main module
S/S
X0
X1
X2
Xn
Users can also input by source type to connect,
In this case, only the external switching power supply, you can connect
PNP sensors. Source-type input of the internal equivalent circuit and
external wiring as shown
: