MC200E Series PLC Main Module

Quick Start User Manual

Thank you for using Megmeet programmable logic controller (PLC).

Before using the MC200E series PLC product, please carefully read

this booklet so as to better understand it, fully use it, and ensure safety.
This quick start manual is to offer you a quick guide to the design,

installation, connection and maintenance of MC200E series PLC,

convenient for on-site reference.

This manual MC200E series for the following members: MC200E-

1616BTA

Version

V1.0

Revision date

July 26, 2010

BOM

R33010006

For detailed product information, please refer to our MC200E Series

PLC User Manual, ControlStar Programming Software User Manual,

and MC100 /MC200 Series PLC Programming Manual. For ordering

the above user manuals, contact your Megmeet distributor or sales

office.

1. Appearance And Part Names

2.Module Description

MC 200E -16 16 B T A

Special functions added

Start from 1 by time

sequence, like 1, 2, 3 and so on. When

empty, it implies no special function.

Power input mode (A: 220ac input; D:

24Vdc input); N: no external power

input.
Output mode. R: relay output; T:

transistor output; N: no output

Module type.

B: Basic module. E: Extension module

Output points. In this example,16.
Input points. In this example,16.
Sub-version number, indicating functional

or structural change, changing by the order

of A, B, C

Z. When empty, it indicates

no sub-version change.
Version number.
Series number. 10: mini; 20: small;

30: mid; 40: large.

Megmeet Controller module

3.Installatin Location

3.1 Environmental Tempetature

PLC use ambient temperature range:

5

55

. Ambient

temperature for a long time when over 55

,Should choose a

well-ventilated place.

3.2 Installation Site

Non-corrosive, flammable gases and liquids place.

Strong vibration-free place.

This PLC for the installation environment design II standards,

pollution level 2 applications.

3.3 Installation Position

Mount the PLC onto the cabinet backboard horizontally. You must

provide a clearance of at least 20cm, both above and below the unit, for

proper cooling. Never mount them to the floor or ceiling of an enclosure

or other directions. See the following figure. No heat generating

equipment should be around the PLC.

3.4 Installation Methord

DIN rail mounting
Generally you can mount the PLC onto a 35mm-wide rail (DIN), Open

the module at the bottom of the DIN card buckled

The bottom of the

module onto the DIN rail;

Rotating module close to the DIN guide rail, Close the DIN card clasp;

Double-check the module and DIN rail snap on DIN is closely fixed, as

the following figure

Screw fixing

Fixing the PLC with screws can stand greater shock than DIN rail

mounting. Use M3 screws through the mounting holes on PLC

enclosure to fix the PLC onto the backboard of the electric cabinet, as

the following figure.

Main Module Size

3.5 Cable Connection And Specifications

Cable specifications

When wiring a PLC, use multi-strand copper wire and ready-made

insulated terminals to ensure the quality. The recommended model and

the cross-sectional area of the cable are shown in the following table.

Cable

Recommended Wire NO.

Conductor Cross-Section

AC power line(L、N)

AWG12、18

1.0~2.0mm²

Ground wire(

AWG12

2.0mm²

Input signal wire(X)

AWG18、20

0.8~1.0mm²

Outout signal wire(Y)

AWG18、20

0.8~1.0mm²

Fix the prepared cable head onto the PLC terminals with screws.

Fastening torque: 0.5~0.8Nm.

In order to safety (to prevent electric shocks and fire accident) and

reduce noise, PLC grounding terminals should be in strict accordance

with the national electrical code requirements grounding, grounding

resistance should be less than 100 Ω. Multiple PLC ground, should be

single-point grounding, ground loops can not form. As below: