Document reference MAODS301/E
USER MANUAL
Edition 4 - May 2022
SpeedSys300 ODS301 overspeed detection system
F - 19
Parameters and configuration settings
APPENDIX F: SPEEDSYS300 ODS301 MODBUS REGISTER DEFINITIONS
F.2.7 Diagnostics configuration – factory
describes the SpeedSys300 ODS301 Modbus registers related to the module
diagnostics configuration – factory.
NOTE:
This data block is intended/reserved for factory use only and should not be
changed by end-users.
NOTE:
The Modbus registers in this data block are read/write.
Table F-12:
SpeedSys300 ODS301 Modbus registers – diagnostics configuration – factory
Address
Name
Data
type
Range
Access
Description
5000
slv_u_ref
single
2.4 to 2.6
Level 2
Reference voltage value (slave) [V]
5002
slv_vcc_max
single
3.3 to 3.8
Level 2
Slave Vcc voltage maximum limit
5004
slv_vcc_min
single
3.0 to 3.3
Level 2
Slave Vcc voltage minimum limit
5006
supl_sens_max
single
12 to 30
Level 2
Max. value of sensor supply voltage (slave)
5008
supl_sens_min
single
12 to 30
Level 2
Min. value of sensor supply voltage (slave)
5009
u_diff_thrs
uint16
0 to 4095
Level 2
Threshold voltage readback difference.
Abs. value in A/D readings digits (slave).
5011
Reserved
uint16
Level 2
5012
m_u_ref
single
2.4 to 2.6
Level 2
Master reference voltage
5014
m_vcc_max
single
3.3 to 3.8
Level 2
Master Vcc voltage maximum limit
5016
m_vcc_min
single
3.0 to 3.3
Level 2
Master Vcc voltage minimum limit
5018
rail_u_max
single
12 to 16
Level 2
Supply rail voltage maximum (master)
5020
rail_u_min
single
9 to 12
Level 2
Supply rail voltage minimum (master)
5022
u_24v_max
single
24 to 40
Level 2
24 V supply voltage maximum (master)
5024
u_24v_min
single
10 to 24
Level 2
24 V supply voltage minimum (master)