Megger VF5 User Manual Download Page 2

www.megger.com

Product Name

2

The Megger VF5 Voltage Detector is intended to check for 
the presence of AC voltage, indicated by a bright red LED 
situated within the white nylon tip and an audible sounder 
plus vibration alert. A small white LED work light is also 
mounted in the tip.

The detector has both low voltage (12 V - 1000 V) and 
medium voltage (100 V - 1000 V) ranges. 

The VF5 has the added advantage of a bright-white LED 
torch for use in poor light.

The Megger VF5 is useful for identifying live conductors, 
finding a break in a wire, verifying a blown fuse while in 
circuit, and detecting AC voltage at:

 

„

Socket outlets

 

„

Switches

 

„

Circuit breakers

 

„

Fuses

 

„

Wires and cables

 

„

Luminaires

Features

 

„

Non-contact detection of AC voltage

 

„

12 V ~ 1000 V AC and 100 V ~ 1000 V AC  50 Hz / 60 
Hz CAT IV 1000 V

 

„

Visual, audible and vibration warning of low and 
medium voltages

 

„

Durable rubber over-moulded body

 

„

Built-in bright-white LED torch

 

„

Low power consumption

 

„

Convenient pocket-size

Safety Warnings

Read, understand and follow Safety Warnings and 
Operating Instructions in the manual before using this 
product.

The detector’s safety features may not protect the 
user if not used in accordance with the manufacturer’s 
instructions.

Check on a known live source within the rated AC voltage 
range of the detector before use to ensure it is in working 
order.

Insulation type and thickness, distance from the voltage 
source, shielded wires, and other factors may affect reliable 
operation. 

The VF5 may help in the indication of live AC circuits only 
and must not be used as verification of a de-energised 
circuit. This is not a Safety Test Lamp.

Do not use if the detector appears damaged or if it is not 
operating property. If in doubt, replace the product.

Do not use on voltages that are higher than as marked on 
the VF5.

Use caution with voltages above 30 V AC as a shock 
hazard may exist.

Comply with all applicable safety codes. Use approved 
personal protective equipment when working near live 
electrical circuits -particularly with regard to arc-flash 
potential.

Do not operate detector if Low Battery warning occurs. 
Replace batteries immediately.

NOTE

: The VF5 is unable to detect voltage on armoured or 

sheathed cable, or on cable in conduit, behind panels or in 
metallic enclosures.

CATIV

Measurement category IV: Equipment connected between 
the origin of the low-voltage mains supply outside the 
building and the consumer unit.

CATIII

Measurement category III: Equipment connected between 
the consumer unit and the electrical outlets.

CATII

Measurement category II: Equipment connected between 
the electrical outlets and the user’s equipment.

International Safety Symbols

 

 

G

 

Potential danger. Indicates the user must refer  

 

to the manual for important safety information

Indicates hazardous voltages may be present 

t

  

Equipment is protected by double or reinforced  

 insulation

      Equipment complies with current EU directives

  

End of life disposal  