Start TEST.
7.
The readings for phases A, B, and C should be:
RATIO: 1.0000 ±0.0020
PHASE(min): 0 ±5
Iexc (mA): 0.0 to 0.5
8.
If needed, (as identified on the Preference screen), perform the test
according to steps 1 through 7 for all the excitation voltages of 8V, 40 V,
and/or 80V. The readings should be the same as shown in Step 7.