8. TYPICAL VELOCITY FACTORS

These values of velocity factor are typical and may be used in the 
absence of known values of cables.

These values may need changing after verifying on a specific cable.

Five output impedances are available (25, 50, 75, 100, 140 ohms) and 
an auto impedance matching feature. The velocity factor can be set 
between 0.2 and 0.99 to meet any cable test requirements.

Material

Cross section

mm

2

V.F

m/μS

m/uS

XLPE

35

0.52

156

78

XLPE

50

0.52

156

78

XLPE

70

0.53

160

80

XLPE

95

0.53

160

80

XLPE

185

0.55

165

81.5

XLPE

240

0.56

168

82

XLPE

300

0.56

170

82

XLPE

500

0.56

173

82.5

XLPE

630

0.57

173

82.5

PILC

70

0.52

156

78

PILC

185

0.52

156

78.5

PILC

240

0.53

156

79

PILC

300

0.55

165

80

PILC

0.1 in

2

0.52

156

78

PILC

0.3 in

2

0.52

156

78.5

PILC

0.4 in

2

0.53

156

79

PILC

0.5 in

2

0.55

165

80

Megger Instruments Limited, Archcliffe Road, Dover, Kent, CT17 9EN, England 

T +44 (0)1 304 502101 F +44 (0)1 304 207342  

Part No.  1005-021 

Megger is a registered trademark

TDR2050_QS_EN_V01

Printed in England   www.megger.com 
This instrument is manufactured in the United Kingdom. The company reserves the right to change the specification or design without prior notice.

 

Summary of Contents for TDR2050

Page 1: ...sed test leads Ensure that the test leads are in good condition and working order TDR2050 Quick Start Guide 2 SELECT TEST MODE a Press to select Hold TDR2050 OK Hold TDR2050 OK 1 POWER UP Press and hold to turn TDR on Hold TDR2050 OK c Press OK key to select b Use cursor keys to select test mode required choose T1 ...

Page 2: ...ess when set Hold TDR2050 OK VF 0 54R Z 140 6 40ns 100m AUTO MAN f Cable distance Adjust to a distance greater than the known cable length e Set output pulse width Set at mid point and toggle up down until fault becomes clear Press when set Set at low pulse width for near end faults Set at high pulse width for distant faults and concentric cables Hold TDR2050 OK VF 0 54R Z 140 6 40ns 100m AUTO MAN...

Page 3: ... C2 buttons to select cursor to move c Use left right arrows to move d Cursor position on trace Move cursor e Delta measurement TDR shows total selected cursor C1 to end of test leads about 1 5 m distance to cursor C2 and difference Move C2 to the end of the cable between C1 and C2 first significant reflection ...

Page 4: ...0 80 XLPE 95 0 53 160 80 XLPE 185 0 55 165 81 5 XLPE 240 0 56 168 82 XLPE 300 0 56 170 82 XLPE 500 0 56 173 82 5 XLPE 630 0 57 173 82 5 PILC 70 0 52 156 78 PILC 185 0 52 156 78 5 PILC 240 0 53 156 79 PILC 300 0 55 165 80 PILC 0 1 in2 0 52 156 78 PILC 0 3 in2 0 52 156 78 5 PILC 0 4 in2 0 53 156 79 PILC 0 5 in2 0 55 165 80 Megger Instruments Limited Archcliffe Road Dover Kent CT17 9EN England T 44 0...

Reviews: