Page 4

11

Once test begins to run for any resistance, following 
screen will appear:

Controls are as follows:

i)

 

Test Setup: allows changes to test parameters, which can be seen in step 4 above (and described in 

section 

iv

 below). This button is ‘greyed out’ once testing begins or MTO instrument connection is not 

established.

ii)

 

Test Mode: enables various testing to Start, Continue, Save Results etc. as testing is conducted. This 

button guides operator through testing, providing instruction for next steps.

iii)

 

Abort/Exit: allows disruption of test and/or exiting once test is concluded.

iv)

 

Results Graph: plots resistance results for diagnostic review. This is useful in determining that each 

past result is following an expected pattern. Different OLTC tap changers develop different shaped 
patterns such as V, Saw Tooth, Slope curves. Familiarity with these tap changers helps improve diagnostic 
capability.

v & vi)

 

Measured Resistance: result with color background changes using “Reading Sta Time 

for stable reading” setting as shown in section 

iv

 above. When condition is reached, background turns 

green. 

12

Once all tests are complete and this window closes, 
results will appear on test form:

Saving Results – once test is completed, form will prompt to save result.
After name is entered, results are automatically saved as each test is
completed.

13

Summary of Contents for MWA300 Series

Page 1: ...eturned to Megger for repair The safety precautions herein are not intended to replace your company s safety procedures Refer to IEEE 510 1983 IEEE Recommended Practices for Safety in High Voltage and High Power Testing for additional information Read the MWA300 manual before operating equipment This guide is not meant to replace manual Connect Leads Power Ground After INT EXT switch set to EXT PC...

Page 2: ...this form as an example Allow 30 60 seconds for PC to communicate with Instrument See manual for any PC connection issues Fill out Nameplate information minimum info listed below Input Desired Test Settings At this stage connect Test leads to transformer under test Note color coding and marking on leads Match to transformer bushing markings 2 Page 2 3 4 5 6 ...

Page 3: ...ighlighted box to begin testing individual phase For automated winding resistance testing MTO Test Wizard can be used if all critical nameplate information is filled in from step 4 above Select and start the Ratio TTR Test by depressing below Testing will follow Nameplate input from 4 above 7 8 9 10 Page 3 ...

Page 4: ... concluded iv Results Graph plots resistance results for diagnostic review This is useful in determining that each past result is following an expected pattern Different OLTC tap changers develop different shaped patterns such as V Saw Tooth Slope curves Familiarity with these tap changers helps improve diagnostic capability v vi Measured Resistance result with color background changes using Readi...

Reviews: