Electrical Specification
Continuity :
The built-in buzzer sounds when measuring
resistance less than 1.8 kΩ and up to 2.7 kΩ. LED
RX shows at the same time.
Continuity Indicator :
2.7 kHz Tone Buzzer and RX LED
Response Time of Buzzer :
< 100 ms
Output Voltage :
About 0.5 V
Overload Protection :
AC/DC 1,000 V
AC Currant :
Range
Resolution
Accuracy
200.0 A
0.1 A
±(3.0 % + 5D)
Frequency Response :
45 Hz to 65 Hz
Overload Protection :
AC/DC 200 A
Rotary Field Indication :
For 3 phase 4 wire system only
Sensitivity :
90 V to 1000 V (Phase-to-ground)
Frequency Range :
45 Hz to 65 Hz
“L” LED is on when the signal of L2 probe lead the signal of L1 probe; “R” LED is on
when the signal of L1 probe lead the signal L2 probe.
Single-Pole Phase Check
Sensitivity :
90 V to 1000 V (Phase-to-Earth)
Frequency Range :
45 Hz to 65 Hz
Indicator :
3 kHz Tone Buzzer and ELV LED