DCM300E Earth Leakage Clamp Meter

            Safety Warnings 

 

Do not

 take measurements beyond maximum selected range.

 

Take extreme care and keep hands behind the hand guard when  

 

taking measurements above 30 V RMS.

 

Do not

 operate the instrument with the battery cover removed.

 

 

Do not 

operate the instrument if any part of it is damaged.

 

Do not

 operate the instrument in environments subject to high  

 

temperature, damp, humidity or excessive vibration.

 

Safety Warnings must be read and understood before the 

 

instrument is used, and 

observed

 during use. 

Note: 

The instrument must only be used by suitably  

 

trained and competent persons

General Description 

The DCM300E is a rugged lightweight pocket size  clamp meter designed to 
measure a.c. earth leakage currents. This enables earth leakage faults to be 
detected and located without having to isolate and disconnect circuit wiring. 
Additionally, the DCM300E measures a.c. circuit currents up to 300 Amps. 
Powered by two LR44 or SR44 cells, the instrument design takes full advantage 
of microprocessor technology and features a clear 31⁄2 digit LCD combining 
digital and bar-graph analogue readings.
The two position mode switch provides 4 ranges; 30 mA, 300 mA, 30 A and 300 
A, with minimum resolution of 0,01 mA on the 30 mA range.
To conserve battery power, 

Auto shut

 

off

 operates after a period of 10 minutes 

of inactivity by the instrument. The instrument can be switched back on by 
selecting 

Off

 and then 

On

 again.

Measurement of Leakage Current   

     

Earth Conductors

1) Set the range selector switch to the  

30 /300 mA position.

2) Set the Power switch to 

On

.

3) Ensure that the Data hold switch is 

Off. 

 DH 

 is 

not

 displayed.

4) Clamp the jaws around the earth 

conductor.

5) If necessary, press the Data hold switch 

  

DH 

 is displayed.

6) Take the reading from the Digital and/

or Bar-graph display.

Single phase or 3 phase conductors

1) Set the range selector switch to the  

30 /300 mA position.

2) Set the Power switch to 

On

.

3) Ensure that the Data hold switch is 

Off

 

 DH 

 is  not displayed.

4) Clamp the jaws around both the 

phase and neutral conductors, or the  
3 phase conductors in the case of  
3 phase supplies

5) If necessary, press the Data hold switch 

 

DH 

 is displayed.

6) Take the reading from the Digital and/

or Bar-graph display.

Features and Controls 

 

     

Measurement of Line Current 

1) Set the range selector switch to the  

30 /300 mA position. 

2) Set the Power switch to On.

3) Ensure that the Data hold switch is Off 

 

DH 

 is not displayed.

4) Clamp the jaws around one 

 conductor of the circuit under test.

5) If necessary, press the Data hold switch 

  

DH 

 is displayed.

6) Take the reading from the Digital and/

or Bar-graph display.

Battery Replacement 

1) When the symbol 

 appears on 

the display, the two 1,5 V button cells 
must be replaced.

2) Switch the 

DCM300E

 Off.

3) Loosen the small cross head screw 

securing the battery cover, and remove 
the cover. 

Take care not to lose the 

small screw.

4) Remove both exhausted cells and 

carefully fit two new cells into the 
recess. Position both cells +ve side up.

5) Replace the battery compartment 

cover and re-secure with the small 
cross head. 

Battery cover screw:

  The correct size screw must be used and fitted to ensure battery cover security, and safe operation.

Wrist strap point

Transducer jaws

Mode selector switch (mA / A) 

On / Off switch

3

1

2

  Digit LCD display

Data hold switch 

Jaw opening lever

Jaw guard

Tactile handguard