Manual Version 1.7, Issued: 18/02/2014
Instructions and Installation Guide for Meg 5.0 Stove / Sirius 600 Inset
This document is to be left with the householder after installation.
All Meg stoves exceed the safety and performance requirements of European Standards.
Independently tested by SGS (Notified Laboratory No: 0608) in 2012.
Intermittent wood burning roomheater for installation with a single dedicated chimney.
Meg 5.0 / Sirius 600
Fuel
Wood (Beech)
Test Standard
NEN EN 13229:2001 & NEN EN 13229-A2:2004
Test Cycle
1.20kg over 0.80hrs
Settings
Air Slide at 50%
Flue Draught Pa
12.2
Efficiency %
76.30%
Recommended Rating kW
4.9
Mean Flue Gas Temp Rise °K
276
Minimum air entry requirement
2500mm²
Minimum Clearance to combustibles
See table below
Weight
60kg
Flue outlet size
125mm
Emissions as if O2 = 13%
NOx mg/mᶟ
91
CO %
0.19
CxHy mg/mᶟ
148
Gas flow g/sec
5.1
Smoke Emission g/hr
0.7
This stove must be installed and commissioned by a fully qualified registered engineer, or the building inspector must be informed. For more details contact your local
authority.
This document, when completed by the installer, constitutes part of a ‘Hearth Notice’ for purposes of Building Law. It must be left with the householder and placed
where it can easily be found.
Installed at Location: .................................................................................................... By:........................................................................................................................
I definitively assert that this installation is safe, has been lit and demonstrated to the householder, conforms with current building regulations and with these
instructions.
Signed:............................................................................................................................. Date:.......................................................................................................................
Flue Draught measured on commissioning: .....................................................................
Fuel used on commissioning:.............................................................................................
Installers; Please return the transit skids to the retailer so they can be returned to the manufacturer for re-use.
The Clean Air Act 1993 and Smoke Control Areas
Under the Clean Air Act local authorities may declare the whole or part of the district of the authority to be a smoke control area. It is an offence to emit smoke from a chimney of a building, from a furnace or from any
fixed boiler if located in a designated smoke control area. It is also an offence to acquire an "unauthorised fuel" for use within a smoke control area unless it is used in an "exempt" appliance ("exempted" from the
controls which generally apply in the smoke control area).
The Secretary of State for Environment, Food and Rural Affairs has powers under the Act to authorise smokeless fuels or exempt appliances for use in smoke control areas in England. In Scotland and Wales this power
rests with Ministers in the devolved administrations for those countries. Separate legislation, the Clean Air (Northern Ireland) Order 1981, applies in Northern Ireland. Therefore it is a requirement that fuels burnt or
obtained for use in smoke control areas have been "authorised" in Regulations and that appliances used to burn solid fuel in those areas (other than "authorised" fuels) have been exempted by an Order made and
signed by the Secretary of State or Minister in the devolved administrations.
Further information on the requirements of the Clean Air Act can be found here: http://smokecontrol.defra.gov.uk/
Your local authority is responsible for implementing the Clean Air Act 1993 including designation and supervision of smoke control areas and you can contact them for details of Clean Air Act requirements
The Meg 5.0 / Sirius 600 Inset has been recommended as suitable for use in smoke control areas when burning wood.