00253 

Main features

 

AGDS-M 

Connections to panel: marked on board 
 
1. 

Live & Neutral 230 volt supply from 3amp switched fuse spur 

2. 

 

3. 

Earth connection terminals 

4. 

AUX 1 BMS Relay 

5. 

AUX 2 BMS Relay 

6. 

 

7. 

Fire Alarm Panel connection, (requires N/C, volt free contact in the Fire Panel) 

8. 

Power connections for detectors, Methane, LPG, CO, CO2, Oxygen, Temperature 

9. 

Comms connections for detectors, Methane, LPG, CO, CO2, Oxygen, Temperature 

10. 

Panel Mode switches (factory set, do not alter) 

11. 

Internal tone on/off 

12. 

Spare 

13. 

Learn field device button, press once only when all detectors are connected and powered. 

14. 

Display detector information 1 & 2 on screen 

15. 

Display detector information 3 & 4 on screen 

16. 

BMS Relay setting (see page 4 for details) 

Power at 230 

volts from a 

3amp fused spur

 

16 

10 

11 

12 

13 

14 

15 

17 

18 

19 

Medem 

Gas detectors 

 

Multiple, 

connect in 

parallel  

Fire Alarm 

Requires a volt 

free NC contact 

Earth Connections not 

shown 

230v Supply 

3Amp Fused Spur 

BMS Relays 

See table on page 4 for 

settings. 

Summary of Contents for AGDS-M

Page 1: ... this safety system is installed and commissioned to the satisfaction of the manufacturer A commissioning certificate must be issued to the end user along with instructions for the operation of the equipment As the Manufacturer Medem UK should commission this safety system whereupon a commissioning report will be forwarded to the installing agent who should provide a copy to the end user At the po...

Page 2: ...h that they only require to be connected to the panel and functionally tested The system is designed to auto reset from a high alarm condition after the target gas has fallen below the alarm level In the event of a high alarm from one of the sensors the system will indicate locally and provides contacts for remote monitoring The system will automatically restart after a power failure Control Panel...

Page 3: ...ygen Temperature 10 Panel Mode switches factory set do not alter 11 Internal tone on off 12 Spare 13 Learn field device button press once only when all detectors are connected and powered 14 Display detector information 1 2 on screen 15 Display detector information 3 4 on screen 16 BMS Relay setting see page 4 for details Power at 230 volts from a 3amp fused spur 16 1 2 3 4 5 7 8 9 10 11 12 13 14 ...

Page 4: ...e commissioned a er installa on by Medem UK This will extend the warranty period from 5 years to 10 years and ensure the system is working as designed Please see warranty condi ons that came with the main panel 16 Learn Dets Any gas detectors connected to the system will require learning First ensure all detectors are set to a unique ID address using the selector switch on the detectors themselves...

Page 5: ...uctions for more guidance AGDS M Detector Information VE supply Comm s From either the main panel or an extender Detectors are wired in parallel and can be connected to one another daisy chain Address Selector Each detector must be set to its own address 1 4 and then learnt using button 13 see page 4 Connection and addressing Status LED All current wiring regulations must be followed with referenc...

Page 6: ...nd between 1m and 3m from the potential source Care should be taken so they are not located close to the edge of a canopy or in direct flow of the supply or extract ventilation For additional information or guidance on site specific requirements please don t hesitate to contact us Each detector has its own Bi Colour LED which is used to indicate the status of that detector Not Lit No power comm s ...

Page 7: ...ld be wired in series with the EM stop buttons To EM Stop connections in the panel Indicator bar shows when pressed Normal EM Stop Activated Multiple Stop Buttons Single Stop Buttons Resetting indicator bar The stop buttons supplied by Medem are of a Push Glass key resettable style when activated a yellow indicator bar will show and the unit will require resetting using the key provided Multiple s...

Page 8: ...ier Medem UK will exchange faulty valves for return to the manufacturer 5 Where a Medem UK engineer or another company appointed by Medem UK commission and installed system then that system will carry a ten year warranty This applies to the main panel and the sender unit At the time of commissioning a security label with a serial number will be attached to the main panel box photographs and a comp...

Page 9: ...in circuit board on the right hand side just over half way up the board pressing this once allows the panel to learn how many and which type of detectors are fitted 8 Press and keep pressed the display detectors1 2 or 3 4 button whilst checking on the display that all the detectors have been recognised by the panel 9 At this point press the reset button the panel will open the gas valve Checklist ...

Reviews: