background image

!

3.0 OPERATION 

The operating voltage of the unit is stated on the label.

 

 

There are no exposed parts of the apparatus which produce excessive surface temperature, infrared, 
electro- magnetic, ionising radiation or non-electrical dangers.

 

 

Information regarding tone selection and installation is contained within each unit supplied.

 

 

The unit is fitted with a volume control which is situated adjacent to the tone selection switches. Maximum 
volume is obtained when this control is turned fully clockwise.

 

 

The product has been designed such that the protection afforded will not be reduced due to the corrosion 
of materials, electrical conductivity, impact strength, ageing resistance and the effects of temperature 
variation.

 

 

 

 

4.0

 

Safety Parameters 

 

The following parameters shall be taken into account during interconnection of the system:  

 
24V unit 
 

Ui

 

28V

 

Ii

 

150mA

 

Ci

 

Negligible

 

Li

 

20mH

 

Li/Ri

 

20uH/ 

!

 

 
 

Note – The DB5 sounder has internal resistance that limits the input current to a nominal 28mA when 
connected to a 28V source. With an Ii of 150mA and In=28mA, this allows five (5) DB5 sounders to be 
connected in Parallel. 
 

© MEDC 2017

01/17