06/01

© MEDC 2003

SWITCH

TONE

Nom O/P

TONE FREQ/DESCRIPTION

SETTING

DESCRIPTION

(dB(A)

12345

@1M)

1 Alt Tones 800/970 Hz at 1/4 sec

11111

114

2 Sweeping 800/970 Hz at 7Hz

11110

Fast Sweep(LF)

114

3 Sweeping 800/970 Hz at 1 Hz

11101

Med Sweep(LF)

114

4 Continuous at 2850 Hz

11100

109

5 Sweeping 2400-2850 Hz at 7 Hz

11011

Fast Sweep

114

6 Sweeping 2400-2850 Hz at 1 Hz

11010

114

7 Slow Whoop

11001

Slow Whoop

115

8 Sweep 1200-500 Hz at 1 Hz

11000

Din Tone

115

9 Alt Tones 2400/2850 Hz at 2 Hz

10111

111

10 Int Tone of 970 Hz at 1 Hz

10110

Back-Up Alarm(LF)

114

11 Alt Tones 800/970 Hz at 7/8 Hz

10101

114

12 Int Tone at 2850 Hz at 1Hz

10100

Back Up Alarm(HF)

109

13 970Hz at 1/4 sec on 1 sec off

10011

114

14 Continuous at 970 Hz

10010

114

15 554Hz for 100mS / 440 Hz for 400mS

10001

French Fire Sound

101

16 Int 660 Hz 150 mS on 150 mS off

10000

Swedish Fire Alarm

106

17 Int 660 Hz 1.8 sec on 1.8 sec off

01111

Swedish Fire Alarm

106

18 Int 660 Hz 6.5 sec on 13 sec off

01110

Swedish Fire Alarm

104

19 Continuous 660 Hz

01101

Swedish Fire Alarm

106

20 Alt 554/440 Hz at 1 Hz

01100

Swedish Fire Alarm

100

21 Int 660 Hz at 7/8 Hz

01011

Swedish Fire Alarm

106

22 Int 2850 Hz 150 mS on 100 mS off

01010

Pelican Crossing

109

23 Sweep 800-970 Hz at 50 Hz

01001

Low Freq Buzz

113

24 Sweep 2400-2850 Hz at 50 Hz

01000

High Freq Buzz

112

25 3 970Hz pulses 0.5on/0.5off, 1.5 off

00111

113

26 3 2850Hz pulses 0.5on/0.5off, 1.5 off

00110

109

27 Int 3100 Hz 0.32s on / 0.68s off

00101

110

28 Spare/Customer Tone

00100

29 Spare/Customer Tone

00011

30 Spare/Customer Tone

00010

31 Spare/Customer Tone

00001

32 Spare/Customer Tone

00000

Summary of Contents for DB1 P UL

Page 1: ...as been taken to ensure the accuracy of our technical manual We do not however accept responsibility for damage loss or expense resulting from any error or omission We reserve the right to make altera...

Page 2: ...move the 4 off screws holding the cover assembly to the base Keep in a safe accessible location Twist the cover gently clockwise and anti clockwise whilst pulling it away from the unit Remove to gain...

Page 3: ...RANGEMENT 2 HOLES 5 16 8mm DIA 5 1 2 140mm FIXING CRS 3 1 8 79mm 6 7 8 175mm DIA 3 1 8 79mm 5 1 2 140mm FIXING CRS 6 3 4 171mm DIA 6 5 8 8 1 2 168mm 216mm 4 1 8 6 105mm 152mm 1 3 16 30mm ALL DIMENSION...

Page 4: ...inuous at 970 Hz 10010 114 15 554Hz for 100mS 440 Hz for 400mS 10001 French Fire Sound 101 16 Int 660 Hz 150 mS on 150 mS off 10000 Swedish Fire Alarm 106 17 Int 660 Hz 1 8 sec on 1 8 sec off 01111 Sw...

Page 5: ...black tone 1 will sound Reverse the voltage so that TB3 is ve and TB1 is ve tone 2 will sound 3 3 2 Common ve Set Up Connect input wires to TB1 ve and separate ve s to TB3 and TB5 When TB3 is ve tone...

Page 6: ...specific approval details UL listed for use in Class 1 Division 1 Groups C D USA USL Class 1 Zone 1 Groups IIA IIB UL Standards UL1203 UL464 Suitable for hazardous location fire alarm applications 6...