HM500 DISPLAY PANEL OF GENERATOR CONTROLLER USER MANUAL
21
display error if password is wrong. The correct password should be put after
pressing any button.
5)Press
to turn the digit into upper position, press
to turn the digit into
lower position, press
to get into parameters setting page.
6)Press
to shift up the parameters, press
to shift down the parameters,
press
to get into parameter changing page.
7)Press
to add number 1, press
to reduce number 1, press
to turn the
digit into right and press
to turn the digit into left, press
once done. If the
parameters setting is in the valid setting range, then it can be saved, if not, it can’t
be saved.
8)Press
and
to save the parameters and exit from edition page.
9)Press
to revert back to last class if in any setting position.
Revert back to default: put password “97011” when coming into parameters
setting, then all the parameters can be set as defaults.
Note: the data can’t be saved if the user didn’t press OK and STOP to confirm
the setting.
Parameter list.
1)Basic setting
No Parameter
Range
(default)
Notes
0 Language
0-English
1-
简体中文
2-
繁体中文
3-español
4-русский
5-TURK DILI
Language option.
1 Gens poles
2/4/6/8
(4)
When the flywheel teeth are set as 0, the
RPM will be resulted by frequency.
Pole 2: 50Hz---3000RPM.
Pole 4: 50Hz---1500RPM.
Pole 6: 50Hz---1000RPM.
Pole 8: 50Hz---750RPM
2 Gens AC system
Disable
1 phase 2 wire
2 phase 3 wire
3 phase 3 wire
3 phase 4 wire
Gens phases:
No gens parameters can be displayed if
setting as disable, which is applied to
water pump genset.
3 CT rate
5-6000A/5A
(500A/5A)
Used for setting genset CT primary
current, secondary rated current 5A.