BCC2405 BATTERY CHARGER USER MANUAL
7
POWER indicator function description
Indicator Status
Mani function
Illuminated
The charger works normally.
Eliminated
The charger is not energized or failed.
CHARGING indicator function description
Indicator Status
Main function
Illuminated
The charger is in charging state, and the output current is >0.5A.
Eliminated
The charger is in floating charge state, and the output current is<0.5A.
Operation instruction
Charge voltage regulation:
When the charger is installed on site for voltage regulation, the battery must be
disconnected from the charger and the voltage potentiometer (VOLT) must be
adjusted at the same time as the output voltage of the charger is measured until the
appropriate value is reached.
Clockwise adjustment of the VOLT potentiometer can increase the output voltage
and reduce the output voltage by counterclockwise adjustment.
Charge current regulation:
When adjusting the current, please connect the charger output with the
accumulator group correctly, adjust when the charging voltage is not higher than
25.0V, adjust the current potentiometer (AMP) while measuring the charging current
to achieve the appropriate charging current.
Clockwise adjustment of the AMP potentiometer can increase output current and
counter clockwise adjustment to reduce output current.
Export insurance replacement:
This charger has the output anti-contact anti-insurance FUSE (10A), when the
output is connected back, the insurance will burn out, please connect the battery
correctly, replace the fuse, the charger will return to normal work. The replacement
steps are as follows:
1) Press hard on the slotted screwdriver, screw counter-clockwise and then take out
the fuse.
2) Put a new fuse into the block, press the slotted screwdriver and screw clockwise.
Note: In-proper operation or over tightening may damage the block.
Warning: When replacing the fuse, be sure to disconnect the input power
of the charger to avoid personal injury or equipment damage!
Note:
1) Because there is diode and current-limiting circuit inner the charger, it can be used
together with charging generator, and there is no need to disconnect the charger
when cranking.
2) During gen-set is running, high current will cause voltage drop in charging line, so
recommend separately connecting to battery terminal to avoid disturbance on
sampling precision.