background image

                           

Installation Manual

 

 

3

1

2

4

3

Use copper wire only, and recommended wires are shown as below. 

AWG 

18 

16 

14 

12 

10 

Rated Current of 
Equipment (Amp) 

6A 

6-10A 

13-16A 

16-25A 

25-32A 

Cross-section of 
Lead(mm

2

 ) 

0.75 

1.00 

1.5 

2.5 

Note: 1. Current each wire carries should be de-rated to 80% of the current suggested 

above when using 5 or more wires connected to the unit. 

          2. The maximum allowable wire cross-sectional area for the terminal of the 

SDR-75 is 12AWG/2.5 mm

Make sure that all strands of each stranded wire enter the terminal connection and the screw terminals are 
securely  fixed  to  prevent  poor  contact.  If  the  power  supply  possesses  multi-output  terminals,  please  make 
sure each contact is connected to wires to prevent too much current stress on a single contact.   

4

Use wires that can withstand temperatures of at least 80°C, such as UL1007. 

5

Recommended wire strapping length is 5mm (0.197

”)

6

Recommended screwdriver is 4mm, slotted type. 

7

The recommended torque setting for terminals is shown as below. 

Model 

I/P 

O/P 

SDR-75 

6.9 kgf-cm (6 Lb-in) 

6.9 kgf-cm (6 Lb-in) 

SDR-120 

6.3 kgf-cm (5.5 Lb-in) 

6.3 kgf-cm (5.5 Lb-in) 

SDR-240 

10 kgf-cm (9 Lb-in) 

10 kgf-cm (9 Lb-in) 

SDR-480/480P 

10 kgf-cm (9 Lb-in) 

8 kgf-cm (7 Lb-in) 

SDR-960 

10 kgf-cm (9 Lb-in) 

8 kgf-cm (7 Lb-in) 

8

Suggested fuse and maximum number of the SDR PSUs that can be connected to a circuit breaker at 230V are 

shown as below. 

Model 

Fuse 

Circuit breaker 

C16 

D16 

SDR-75 

T3.15A/L250V 

10 

12 

SDR-120 

T4A/L250V 

14 

SDR-240 

T5A/L250V 

SDR-480

 

T8A/L250V 

SDR-480P

 

T8A/L250V 

SDR-960 

F10A/H250V 

9

Mounting Instruction

 

Mount as shown in figure only, with input terminals down, or else sufficient cooling will not be possible. 
Admissible DIN rail

TS35/7.5 or TS35/15 

For rail fastening

 

 

a

Tilt the unit slightly rearwards. 

b

Fit the unit over top hat rail. 

c

Slide it downward until it hits the stop. 

d

Press against the bottom for locking. 

e

Shake the unit slightly to check the locking action. 

 
 
 
 
 
 
 
 

"Click" 

Summary of Contents for SDR Series

Page 1: ...VAC 5A 50 60Hz OUTPUT 48V 10A SDR 480P 24 INPUT 100 240VAC 5A 50 60Hz OUTPUT 24V 20A SDR 480P 48 INPUT 100 240VAC 5A 50 60Hz OUTPUT 48V 10A SDR 960 24 INPUT 200 240VAC 6A 50 60Hz OUTPUT 24V 40A SDR 960 48 INPUT 200 240VAC 6A 50 60Hz OUTPUT 48V 20A Introduction SDR is a DIN rail power supply series with a 150 peak load capability 3 seconds and high efficiency of up to 94 Like other Mean Well s DIN ...

Page 2: ...length is 5mm 0 197 6 Recommended screwdriver is 4mm slotted type 7 The recommended torque setting for terminals is shown as below Model I P O P SDR 75 6 9 kgf cm 6 Lb in 6 9 kgf cm 6 Lb in SDR 120 6 3 kgf cm 5 5 Lb in 6 3 kgf cm 5 5 Lb in SDR 240 10 kgf cm 9 Lb in 10 kgf cm 9 Lb in SDR 480 480P 10 kgf cm 9 Lb in 8 kgf cm 7 Lb in SDR 960 10 kgf cm 9 Lb in 8 kgf cm 7 Lb in 8 Suggested fuse and maxi...

Page 3: ... places with high moisture or near the water 7 The maximum operating temperature is 50 C for SDR 960 series and 60 C for SDR 75 120 240 480 480P series please do not install the unit in places with high ambient temperature or near fire source 8 The FG must be connected to PE Protective Earth 9 Output current and output wattage must not exceed the rated value on its specification 10 SDR 960 is a cl...

Page 4: ...GZHOU ENTERPRISES Co LTD 2F A Building Yuean lndustry Park Huangcun Dongpu Yown Tianhe District Gungzhou China Post Code 510660 Tel 86 20 2887 1200 Web www meanwell com cn U S A MEAN WELL USA INC 44030 Fremont Blvd Fremont CA 94538 U S A Tel 1 510 683 8886 Web www meanwellusa com Europe MEAN WELL EUROPE B V Langs de Werf 8 1185XT Amstelveen The Netherlands Tel 31 20 758 6000 Web www meanwell eu ...

Page 5: ...roducts Appendix B adopting table look up to verify the Environment Friendly Use Period Names and Contents of Hazardous Substances Lists Part Name Hazardous Substances Lead Pb Mercury Hg Cadmium Cd Hexavalent chromium Cr6 Polybrominated biphenyls PBB Polybrominated diphenyl ethers PBDE PCB and its components X O X O O O Metal structure parts X O O O O O Plastic structure parts O O O O O O Accessor...

Page 6: ... to China s Standardization Administration Releases VOC Standards Standard No Name of the Standard GB 30981 2020 Limit of harmful substances of industrial protective coatings GB 33372 2020 Limits for volatile organic compounds content in adhesive GB 38507 2020 Limits for volatile organic compounds VOCs In printing ink GB 38508 2020 Limits for volatile organic compounds content in cleaning agents ...

Page 7: ...reby confirms that MEAN WELL product series comply with Use and Risk Management for Five PBT Chemicals under TSCA section 6 h CAS No Substance Name 1163 19 5 Decabromodiphenyl ether DecaBDE 68937 41 7 Phenol isopropylated phosphate 3 1 PIP 3 1 732 26 3 2 4 6 Tris tert butyl phenol 2 4 6 TTBP 133 49 3 Pentachlorothiophenol PCTP 87 68 3 Hexachlorobutadiene HCBD ...