Installation Manual
(
2
)
ICL for Three phase application
Note: ICL-16 series is not suggested for 3 phase application.
Application Manual
The maximum capacitive load and maximum possible rated current limit the number of power supplies that can be
connected. Often, it is the rated currents that represent the decisive factor, because the inrush current limiters can
handle capacitive loads as high as 2500uF/6000uF.
The input capacity of the power supplies is largely determined by primary-side storage capacitors. With MEANWELL,
these capacitors are marked with the position code C5, and their capacitance can be found in the test report on the
MEANWELL's website.
Regarding the q’ty of PSU can be connected behind ICL-16/28, you could quickly make an rough evaluation by
following process below.