Suggested fuse and maximum number of the DRA that can be connected to a circuit breaker at 230V are shown 

as below. 

Model 

Fuse 

Circuit breaker 

C16 

D16 

DRA-40 

T2.5A/L250V 

11 

21 

DRA-60 

T2.5A/L250V 

16 

10

Mounting Instruction

 

Mount as shown in figure only, with input terminals down, or else sufficient cooling will not be possible. 
Admissible DIN rail

TS35/7.5 or TS35/15 

For rail fastening

 

 

a

Tilt the unit slightly rearwards. 

b

Fit the unit over top hat rail. 

c

Slide it downward until it hits the stop. 

d

Press against the bottom for locking. 

e

Shake the unit slightly to check the locking action. 

 
 
 
 
 
 
 

 
 

 

11

For other information about the products, please refer to www.meanwell.com for details. 

 

 

Warning / Caution !! 

1

Risk of electrical shock and energy hazard. All failure should be examined by a qualified technician. Please do 

not remove the case of the power supply by yourself! 

2

Risk of electric arcs and electric shock (danger to life). Connecting both the primary and the secondary sides 

together is not allowed. 

3

Risk of burn hazard. Do not touch the unit in operation and shortly after disconnection! 

4

Risk of fire and short circuit. The openings should be protected from foreign objects or dripping liquids. 

5

Only install the unit in a pollution degree 2 environment (Note.1).

 

6

Please do not install the unit in places with high moisture or near the water. 

7

The maximum operating temperature is 45°C for the DRA-60-12, 50°C for the DRA-60-24, DRC-60A and 

DRC-60B, 55°C for the DRA-40-12/24, DRC-40A and DRC-40B, please do not install the unit in places with high 
ambient temperature or near fire source. 

8

The FG (

     

) must be connected to PE (Protective Earth). 

9

Output current and output wattage must not exceed the rated value on its specification. 

 
 