Installation Manual

 

 

 

 

Type

DRA DIN rail power supply

Series

DRA-40, DRA-60

 

DRA-40-12 

INPUT: 100-240VAC 0.8A 50/60Hz  

OUTPUT: 12V 3.34A 

DRA-40-24 

INPUT: 100-240VAC 0.8A 50/60Hz  

OUTPUT: 24V 1.7A 

DRA-60-12 

INPUT: 100-240VAC 1.3A 50/60Hz  

OUTPUT: 12V 5A 

DRA-60-24 

INPUT: 100-240VAC 1.3A 50/60Hz  

OUTPUT: 24V 2.5A 

 

 

Introduction 

DRA is a DIN rail power supply series featuring adjustable output current. Users are able to set its output current to 
a range of 10% - 100% of rated current via 1-10Vdc, PWM signal or resistance. Like other Mean Well’s DIN series, 
they can be mounted on a TS35 Standard DIN rail. 

 

 

Installation 

1

Always allow good ventilation clearances, 5mm left and right, 40mm above and 20mm below, around the unit 

in use to prevent it from overheating. Also a 10-15 cm clearance must be kept when the adjacent device is a 
heat source. 

2

The appropriate mounting orientation for the unit is vertical, the input terminals at the bottom and output on 

the top. Mounting orientations other than that, such as upside down, horizontal, or table-top mounting, is not 
allowed. 

 
 
 
 
 
 
 

3

Use copper wire only, and recommended wires are shown as below. 

AWG 

18 

16 

14 

12 

Rated Current of 
Equipment (Amp) 

10 

15 

20 

Cross-section of 
Lead(mm

2

 ) 

0.8 

1.3 

2.1 

3.3 

Note

Current each wire carries should be de-rated to 80% of the current suggested 

above when using 4-6 wires connected to the unit. 

Make sure that all strands of each stranded wire enter the terminal connection and the screw terminals are 
securely  fixed  to  prevent  poor  contact.  If  the  power  supply  possesses  multi-output  terminals,  please  make 
sure each contact is connected to wires to prevent too much current stress on a single contact.   

4

Use wires that can withstand temperatures of at least 80°C, such as UL1007. 

5

Recommended wire strapping length is 5mm (0.197”). 

6

Recommended screwdriver is 

3mm, slotted type.

 

7

The recommended torque setting for terminals(TB1) is 5 kgf‐cm (4.4 Lb‐in),   

terminals(TB2) is 5.8 kgf‐cm (5 Lb‐in). 

8

Each  unit  requires  0.15mA  when  dimming  function  is  used.  Please  make  sure  your  controller  is  capable  of 

driving the units. 

 
 