8.
When you release
1t1 will be displayed, press and hold
and use
to set to 1 and this is the
minimum on time in minutes. Release
9.
Press
until oAu is displayed. Press and hold
and use
until thr is displayed. Release
. Please
note that if you wish to use the controller as a single stage controller you can disable the second stage by
selecting ‘non’ at this point.
10.
Press
until 2SP is displayed, then press and hold
and use the
buttons to enter 55.0 for the set
point. When you release
2ch will be displayed.
11.
Press and hold
and use
to select ‘hEA’. When you release
2hy will be displayed.
12.
Press and hold
and use
to enter 5 for the hysteresis.
13.
When you release
2tO will be displayed, press and hold
and use
to set to 1 and this is the
minimum off time in minutes.
14.
When you release
2t1 will be displayed, press and hold
and use
to set to 1 and this is the
minimum off time in minutes.
15.
Press
to exit set up
16.
To change any of the settings press both
and
buttons for 5 seconds you can use
to scroll
through the various menus.
If the dehumidifier or the humidifier fails they will fail in the off position.
Turn the humidistats on both units to their maximum settings.
To control at a different set-point simply input different values by pressing the L1 and L2 buttons on the front of the
controller.
To change the hysteresis from ±5% simply change the values in stages 6 and 12.
Output 1 = Dehumidifier (Black plug)
Output 2 = Humidifier (White plug)
The alarm function is not used in this controller set up.
If you have any problems then call Meaco on 01782 565 917