Additional refrigerant charge
180
Installation
8. Additional refrigerant charge
After the vacuum drying process is carried out, the additional refrigerant charge process need to be
performed.
The outdoor unit is factory charged with refrigerant. The additional refrigerant charge volume is decided
by the diameter and length of the liquid pipe between indoor and outdoor unit. Refer the following
formula to calculate the charge volume.
Diameter of liquid pipe (mm)
Φ
6.35
Φ
9.52
Formula V=15g/m×(L-5)
V=30g/m×(L-5)
V:
Additional refrigerant charge volume (g).
L :
The length of the liquid pipe (m).
Note:
Refrigerant may only be charged after performed the vacuum drying process.
Always use gloves and glasses to protect your hands and eyes during the charge work.
Use electronic scale or fluid infusion apparatus to weight refrigerant to be recharged. Be sure to avoid
extra refrigerant charged, it may cause liquid hammer of the compressor or protections.
Use supplementing flexible pipe to connect refrigerant cylinder, pressure gauge and outdoor unit. And
The refrigerant should be charged in liquid state. Before recharging, The air in the flexible pipe and
manifold gauge should be exhausted.
After finished refrigerant recharge process, check whether there is refrigerant leakage at the connection
joint part.(Using gas leakage detector or soap water to detect).
Summary of Contents for MDCA3-12HRDN1
Page 1: ...DC INVERTER SERIES Service Manual 2014 LIS B 1411...
Page 5: ...Features 11...
Page 7: ...S 14 3 ervice Space 4 Service 3 e Space...
Page 8: ...MDCA3 12HRDN1 MDCA3 18HRDN1 Wiring Diagrams 16 4 Wiring 4 Diagram ms...
Page 12: ...MDCA3 12HRDN1 MDCA3 18HRDN1 Field Wiring 21 1 Field 0 Wiring...
Page 19: ...Service Space Super Slim Cassette Type 33 3 Service Space 1000mm 1000mm 1000mm 1000m m...
Page 26: ...Field Wiring 40 Super Slim Cassette Type 10 Field Wiring...
Page 33: ...MDTB1 12HWDN1 MDTB1 12HWDN1 B Duct Type Duct Type 47 4 Wiring Diagrams...
Page 34: ...MDTB 18HWDN1 MDTB 24HWDN1 MDTB 36HWDN1 MDTB 48HWDN1 MDTB 60HWDN1 Duct Type 48 Duct Type...
Page 41: ...Duct Type 56 Duct Type For model 18 60 10 Field Wiring...
Page 50: ...MDOU 12HDN1 Wiring Diagrams Outdoor Units 131 4 Wiring Diagrams...
Page 51: ...MDOZU 12HDN1 MDOU 18HDN1 Wiring Diagrams 132 Outdoor Units...
Page 52: ...MDOU 18HFN1 Wiring Diagrams Outdoor Units 133...
Page 53: ...MDOU 24HDN1 220075301400 MDOU 24HDN1 220075302030 Wiring Diagrams 134 Outdoor Units...
Page 54: ...MDOU 36HDN1 Wiring Diagrams Outdoor Units 137...
Page 55: ...MDOU 48HDN1 MDOU 60HDN1 MDOU 48HDN1 MDOU 60HDN1 New Body Wiring Diagrams 138 Outdoor Units...
Page 91: ...Refrigerant pipe installation 174 Installation...
Page 129: ...Troubleshooting 220 Electrical Control System 2 4 4 5 E3 malfunction...
Page 131: ...Troubleshooting 222 Electrical Control System 2 4 4 7 E5 malfunction...
Page 133: ...Troubleshooting 224 Electrical Control System 2 4 4 9 P0 malfunction...
Page 134: ...Troubleshooting Electrical Control System 225 2 4 4 10 P1 malfunction Only for 30K 60K...
Page 140: ...Troubleshooting Electrical Control System 231 2 4 4 16 P7 malfunction...