5. Refrigerant Pipe Installation
5.1 Maximum length and drop height
Ensure that the length of the refrigerant pipe, the number
of bends, and the drop height between the indoor and
outdoor units meets the requirements shown in the
following table.
Capacity(k
Btu/h
)
Max. Length
(m/ft)
Max. Elevation
(m/ft)
12
25/82
10/33
18~24
30/98
20/66
caution:
• The capacity test is based on the standard length and
the maximum permissive length is based on the system
reliability.
• Oil traps
If the indoor unit is installed higher than the outdoor unit:
-If oil flows back into the outdoor unit’s compressor, this
might cause liquid compression or deterioration of oil
return. Oil traps in the rising gas piping can prevent this.
An oil trap should be installed every 10m(32.8ft) of vertical
suction line riser.
The indoor unit is installed higher than the outdoor unit
If the outdoor unit is installed higher than the indoor unit:
-It is recommended that vertical suction risers not be
upsized. Proper oil return to the compressor should be
maintained with suction gas velocity. If velocities drop
below 7.62m/s(1500fpm (feet per minute)), oil return
will be decreased. An oil trap should be installed every
6m(20ft) of vertical suction line riser.
The outdoor unit is installed higher than the indoor unit.
5.2 The procedure of connecting pipes
1. Choose the pipe size according to the specification
table.
2. Confirm the cross way of the pipes.
3. Measure the necessary pipe length.
4. Cut the selected pipe with pipe cutter
•
Make the section flat and smooth.
Oblique Rough Warped
90°
5. Insulate the copper pipe
•
Before test operation, the joint parts should not be
heat insulated.
6. Flare the pipe
•
Insert a flare nut into the pipe before flaring the
pipe
•
According to the following table to flare the pipe.
Summary of Contents for M0BA30-11CFN1-MQ0W
Page 1: ...TM_AB_R410A_INV_US_NA_2009 R410A INVERTER CONTROL TECHNICAL MANUAL...
Page 14: ...Specifications Page 14 MSABB 11CRFN1 BT0W MSABB 11CRFN1 MT0W MSABD 17CRFN1 MQ0W...
Page 15: ...Specifications Page 15 MSABE 22CRDN1 MS0W...
Page 17: ...Specifications Page 17 MOBA30 12CFN1 BP0W MOX130 11CFN1 MT0W...
Page 18: ...Specifications Page 18 MOX130 11CFN1 BT0W MOBA30 09CFN1 MQ0W M0BA30 11CFN1 MQ0W...
Page 19: ...Specifications Page 19 MOBA30 17CFN1 MR0W MOCA30 22CFN1 MR0W...
Page 47: ...Specifications Page 47 MOX130 11CFN1 MT0W MOBA30 17CFN1 MR0W MOCA30 22CFN1 MR0W...