background image

 

 

86 

 

Procedure 

1).  Confirm  that  both  the  2-way  and  3-way 

valves are open. 

Remove  the  valve  stem  caps  and  confirm  that 

the valve stems are open. 

Be sure to use a hexagonal wrench to operate 

the valve stems. 

2). Connect the charge hose with the push pin 

of  handle  lo  to  the  3-way  valves  gas  service 

port. 

3). Purge the air from the charge hose. 

Open the handle Lo valve of the manifold valve 

slightly to purge air from the charge hose for 5 

seconds and then close it quickly. 

4). Close the 2-way valve. 

5). Turn on the air conditioner in cooling mode. 

Turn  it  off  when  the  gauge  indicates 

-0.1MPa(14.5Psi). 

6).Immediately close the 3-way valve   

Do  this  quickly  so  that  the  gauge  displays  a 

value between 0.3 to 0.5 Mpa(43.5 to 72.5Psi). 

Disconnect  the  charge  set,  and  tighten  the 

2-way and 3-

way valves’ stem nuts. 

Use a torque wrench to tighten the 3-way valves 

service port cap to a torque of 18N.m. 

Be sure to check for gas leaks. 

 

2. Air Purging by the Refrigerant

 

 

Procedure: 

1).  Confirm  that  both  the  2-way  and  3-way 

valves are closed. 

2).  Connect  the  charge  set  and  a  charging 

cylinder to the service port of the 3-way valve 

Leave the valve on the charging cylinder closed. 

3). Purge the air from the charge hose. 

Open  the  valves  on  the  charging  cylinder  and 

the  charge  set.  Purge  the  air  by  loosening  the 

flare  nut  on  the  2-

way  valve  approximately  45’ 

for  3  seconds  and  then  closing  it  for  1  minute. 

Repeat 3 times. 

After  purging  the  air,  use  a  torque  wrench  to 

tighten the flare nut on the 2-way valve. 

4). Check for gas leaks 

Check the flare connections for gas leakage. 

5). Discharge the refrigerant. 

Close  the  valve  on  the  charging  cylinder  and 

discharge the refrigerant by loosening the flare 

nut  on  the  2-

way  valve  approximately  45’  until 

the  gauge  indicates  0.3  to  0.5  Mpa(43.5  to 

72.5Psi) 

6). Disconnect the charge set and the charging 

cylinder, and open the 2-way and 3-way valves 

Be sure to use a hexagonal wrench to operate 

the valve stems. 

7). Mount the valve stems nuts and the service 

port cap. 

Be  sure  to  use  a  torque  wrench  to  tighten  the 

service port cap to a torque 18N.m. 

Be sure to check for gas leakage. 

 

12.4.6  Re-Installation  When  the  Outdoor 

Unit Requires Repairs 

1. Evacuation for

 

the whole system 

Summary of Contents for CCA3U-09HRFN1-MC

Page 1: ...on 2 Part Names And Functions 3 Dimension 4 Service space 5 Refrigerant Cycle Diagram 6 Wiring Diagram 7 Static Pressure 8 Electric Characteristics 9 Sound Level 10 Accessories 11 The Specification of Power 12 Installation Details 13 Operation Characteristics 14 Electronic Function 15 Solar Panel 16 Troubleshooting 17 Disassembly Instructions WARNING Installation MUST conform with local building c...

Page 2: ...acteristics 63 9 Sound Level 64 9 1 Indoor unit 64 9 2 Outdoor unit 67 10 Accessories 68 11 The Specification of Power 70 12 Installation Details 72 12 1 Location selection 72 12 2 Indoor unit installation 72 12 3 Outdoor unit installation 82 12 4 Refrigerant pipe installation 83 12 5 Drainage pipe installation 87 12 6 Vacuum Drying and Leakage Checking 90 12 7 Additional refrigerant charge 91 12 ...

Page 3: ...Unit Error Display 105 16 2 Outdoor unit error display 106 For 9K 24K outdoor unit 106 For 36K 60K Outdoor Unit 107 Outdoor check function 107 16 3 Diagnosis and Solution 110 16 4 Main parts check 136 17 Disassembly Instructions 144 17 1 Indoor unit 144 17 2 Outdoor unit 165 ...

Page 4: ...ct Sharp edges could cause injury be especially careful of the case edges and the fins on the condenser and evaporator For installation always contact the dealer or an authorized service center Do not install the product on a defective installation stand Be sure the installation area does not deteriorate with age If the base collapses the air conditioner could fall with it causing property damage ...

Page 5: ...repair of product Low refrigerant levels may cause failure of product Install the drain hose to ensure that water is drained away properly A bad connection may cause water leakage Keep level even when installing the product It can avoid vibration of water leakage Do not install the product where the noise or hot air from the outdoor unit could damage the neighborhoods It may cause a problem for yo...

Page 6: ...al injury Replace the all batteries in the remote control with new ones of the same type Do not mix old and new batteries or different types of batteries There is risk of fire or explosion Do not recharge or disassemble the batteries Do not dispose of batteries in a fire They may burn of explode If the liquid from the batteries gets onto your skin or clothes wash it well with clean water Do not us...

Page 7: ...A31 18HFN1 MT0W A5 Duct CTBU 18HWFN1 M C Floor Ceiling MUEU 18HRFN1 M C A6 Duct MTI 18HWFN1 MT0W MOCA30 18HFN1 MT0W MOCA01 18HFN1 MT0W A6 Duct 24K MTIU 24HWFN1 MW MOD30 24HFN1 MT0W MOD01 23HFN1 MT0W Cassette MCDU 24HRFN1 M C MOD30 24HFN1 MT0W MOD01 23HFN1 MT0W MOD31 24HFN1 MT0W A6 Duct CTBU 24HWFN1 M C Floor Ceiling MUEU 24HRFN1 M C Cassette 36K MCD 36HRFN1 M C MOD30U 36HFN1 M A5 Duct CTB 36HWFN1 ...

Page 8: ...5 2 2 Part names of Indoor Outdoor units Cassette Units ...

Page 9: ...6 A5 Duct Units A6 Duct Units ...

Page 10: ...7 Console Units ...

Page 11: ...8 Ceiling floor Units ...

Page 12: ...9 HESP DUCT Units ...

Page 13: ...l The size of air inlet frame from rear and bottom is same it s very easy to move the cover from bottom to rear side or from rear to the bottom in order to matching the installation condition 2 3 1 3 Fresh Air Intake Function Install one duct from the reserved fresh air intake to outdoor Continually inhale the fresh air to improve the quality of the indoor air fulfills air quality more healthy and...

Page 14: ...ctly remove two bolts and then replace the motor or centrifugal fan easily 2 3 1 5 Reserved Remote On off and Central Control Ports Reserved remote on off ports and central control ports can connect the cable of an on off controller or a central controller to realize remote on off control function or group control function 2 3 1 6 Built in Drain Pump Optional Built in drain pump can lift the water...

Page 15: ...eceiver in the E box Move out the display and fix it in other place even in the distance of 2m The unit will realized remoter control The wired controller and the display board can display the error code or production code when the chips detect some failure Display 750mm upmost Wired Controller Standard Remote Controller Optional ...

Page 16: ... 3 Fire proof Controller Box Electrical control box adopts new design which can meet higher fire safety requirements 2 3 2 4 Fresh Air Fresh air intake function bring you fresh and comfortable air feeling 2 3 2 5 Wired Controller Optional Compared with infrared remote controller wired controller can be fixed on the wall and avoid mislaying It s mainly used for commercial zone and makes air conditi...

Page 17: ...o 750mm upmost It s convenient to install drainage piping under most space condition 2 3 2 7Terminals For Alarm Lamp and Long distance On off Controller Connection Are Standard Reserve terminals for the connection of alarm lamp and long distance on off controller more human control ...

Page 18: ...ck Cooling To maintain room temp Air outlet from top and bottom to make quick cooling When the A C is just switched on or room temp is still high cold air will be blown out from top and bottom air outlet to cool down the room quickly Air outlet from top to maintain room temp When the room has been cooled down or the A C has been opened over 1 hour cold air only from the top outlet to keep constant...

Page 19: ...wing only the upper louver is opened in a high position the lower louver closed 2 3 3 4 Four Air Inlets 2 3 3 5 Low Noise DC indoor fan motor which has five speeds Low noise and energy saving Advanced centrifugal fan technology makes a fast airflow and reduces the indoor noise 2 3 3 6 Golden fin is optional 2 3 3 7 Active carbon filter is standard ...

Page 20: ... air 2 3 4 2 Brief Design Brief design that is suitable for any interior will not only give you cooling and heating performance but also upgrade your lifestyle 2 3 4 3 3D Airflow Vertical air flow and horizontal airflow can be adjusted by remote controller the cooperation of the two airflow ways help to spread air comfortably throughout even a large room With these functions the whole room can be ...

Page 21: ... D Panel 2 3 4 5 Convenience Operating and Easy Maintenance Remote controller as standard wired controller for optional The filter without screw fixed can be took out easily 2 3 4 6 Easy Installation Save Working Time The pipes can be connected from bottom back and right side makes the installation more easily The wiring works can be finished before installation 2 3 4 7 Outside Water Pump for Opti...

Page 22: ...t 210mm 24K 36K unit 249mm 48K unit 300mm 2 3 5 3 Constant air volume control For ordinary duct when the static pressure exceeds the expected range it is fairly difficult even for an experienced installer to calculate and adjust the air volume precisely With constant air volume control technology the duct will automatically adjusts to perfect static pressure and keep constant air volume 2 3 5 4 In...

Page 23: ...ttom is the same It s very easy to switch to match different application 2 3 5 6 Communication wire connection A6 duct uses two wires without polarity connection way which almost has no mistake during the installation Air intake from rear Standard Air intake from bottom Optional Front Board Filter Panel ...

Page 24: ...tom side With a larger window design once the motor and the blower wheels have been detached heat exchanger and water receiver tray in behind can be seen very clearly Dust can be easily removed from the inside by vacuum 2 3 5 8 Easy maintenance A6 duct allows operators maintenance the motor from the bottom more easily compare with that on the top A6 duct has big space for maintenance at the side ...

Page 25: ...om the reserved fresh air intake to outdoor Continually inhale the fresh air to improve the quality of the indoor air fulfills air quality more healthy and comfortable A ventilation motor provided by the installer can be installed inside the fresh air duct to improve the fresh air volume There are reserved ports for this motor on main PCB Standard for 3D inverter units and only optional for DC inv...

Page 26: ... pressure of indoor unit is 200Pa The longest distance of air supply is 40m the max height of air supply is 6 5m Specially recommended for spacious and large rooms like large stores and factories 2 3 6 2 Easy maintenance The unit can be opened from top or bottom Max 750mm ...

Page 27: ... much easier when connecting duct 2 3 6 3 Flexible Installation Different solutions for any shape room by using kinds of air distribution ducts 2 3 6 4 Easy cleaning filter The filter can be easily removed or installed from the rear side for ease of cleaning L shaped area Areas far apart Y shaped area ...

Page 28: ... 5 63 3 74 5 91 12 mm 700 210 635 570 65 493 35 119 595 200 80 740 350 120 143 95 150 in 27 56 8 27 25 22 44 2 56 19 41 1 38 4 69 23 43 7 87 3 15 29 13 13 78 4 72 5 63 3 74 5 91 18 mm 920 210 635 570 65 713 35 119 815 200 80 960 350 120 143 95 150 in 36 22 8 27 25 00 22 44 2 56 28 07 1 38 4 69 32 09 7 87 3 15 37 80 13 78 4 72 5 63 3 74 5 91 24 mm 920 270 635 570 65 713 35 179 815 260 20 960 350 12...

Page 29: ...as side Liquid side 4 install hanger Body Drain pipe 25 Fresh air intake 65 647 647 50 Drain hole for Service 545 570 260 68 42 157 126 44 Wiring connection port 75 E parts box 4 Screw hole for install panel 523 570 Wiring connection port ...

Page 30: ... A B A B Service hole for draining pump Fresh air intake 75 55 80 80 4 install hanger Gas side Liquid side E parts box 135 90 Panel Body 92 92 92 92 D D 92 92 D D D D 92 92 92 92 92 92 92 92 D D Capacity Btu h A B C D 24K mm 160 75 205 50 inch 6 30 2 95 8 07 1 97 36K mm 160 95 245 60 inch 6 30 3 74 9 65 2 36 48K mm 160 95 287 60 inch 6 30 3 74 11 30 2 36 ...

Page 31: ...28 Console Units 16 Drain pipe 195 Hanging arm Unit mm 700 600 210 ...

Page 32: ...ction port 204 94 Fresh air intake Drain discharge port Refrigerant pipe hole Hanging arm D Capacity Btu h A B C D 18K 24K mm 1068 675 235 983 inch 42 05 26 57 9 25 38 70 36K mm 1285 675 235 1200 inch 50 59 26 57 9 25 47 24 48K 60K mm 1650 675 235 1565 inch 64 96 26 57 9 25 61 61 ...

Page 33: ... 175 1001 228 5 1140 598 80 150 130 155 inch 43 31 9 8 30 47 27 56 5 51 36 46 1 97 6 89 39 41 8 98 0 2 44 88 23 54 3 15 5 91 5 12 6 1 36 mm 1360 249 774 700 140 1186 50 175 1261 228 5 1400 598 80 150 130 155 inch 53 54 9 8 30 47 27 56 5 51 46 69 1 97 6 89 49 65 8 98 0 2 55 12 23 54 3 15 5 91 5 12 6 1 48 mm 1200 300 874 800 123 1044 50 227 1101 280 5 1240 697 80 150 185 210 inch 47 24 11 81 34 41 3...

Page 34: ...e of the air inlet flange 10 Φ 5 2 Φ 3 2 10 280 280 1000 500 1000 500 385 air inlet duct flange 385 air outlet duct flange 1188 air outlet duct flange 1188 air inlet duct flange 1436 suspension position 700 suspension position 770 1400 440 44 20 44 858 ...

Page 35: ... MV0W MOB30 12HFN1 MT0W MOB01 09HFN1 MW0W MOB01 12HFN1 MV0W mm 800 333 554 870 514 340 inch 31 5 13 1 21 8 34 3 20 2 13 4 MOCA01 18HFN1 MT0W MOCA30 18HFN1 MT0W MOCA31 18HFN1 MT0W mm 845 363 702 914 540 350 inch 33 3 14 3 27 6 36 0 21 3 13 8 MOD01 23HFN1 MT0W mm 946 420 810 1030 673 403 inch 37 2 16 5 31 9 40 6 26 5 15 9 MOD30 24HFN1 MT0W MOD31 24HFN1 MT0W MOD30U 36HFN1 M mm 946 410 810 1030 673 40...

Page 36: ...33 Model W D H W1 A B MOE30U 48HFN1 M MOE30U 60HFN1 M mm 952 415 1333 1045 634 404 inch 37 5 16 3 52 5 41 1 25 0 15 9 ...

Page 37: ...e enough space required for installation and maintenance 200mm 7 87in or more 300mm 11 81in or more 600mmx600mm 23 62inx23 62in Check orifice All the indoor units reserve the hole to connect the fresh air pipe The hole size as following Cassette Units Unit mm ...

Page 38: ...35 Console Units Ceiling floor Units ...

Page 39: ...11 81in More than 60cm 23 62in More than 200cm 78 74in Air inlet Air inlet More than 30cm 11 81in Air outlet Wall or obstacle Maintain channel More than 60cm 23 62in 500mm or more 600mm or more Indoor unit 600mmx600mm Maintenance and repair space ...

Page 40: ...or INDOOR OUTDOOR T2 Evaporator temp sensor middle Electronic expansion valve CAPILIARY TUBE MOB30 09HFN1 MX0W MOB01 09HFN1 MW0W MOB30 12HFN1 MV0W MOB01 12HFN1 MV0W MOBA30 09HFN1 MT0W MOB30 12HFN1 MT0W MOCA31 18HFN1 MT0W LIQUID SIDE GAS SIDE HEAT EXCHANGE EVAPORATOR HEAT EXCHANGE CONDENSER Compressor 2 WAY VALVE 3 WAY VALVE 4 WAY VALVE COOLING HEATING T2B Evaporator temp sensor outlet T1 Room temp...

Page 41: ... 3 WAY VALVE 4 WAY VALVE COOLING HEATING T2B Evaporator temp sensor outlet T1 Room temp sensor T3 Condenser temp sensor Accumulator T5 Discharge temp sensor High pressure switch T4 Ambient temp sensor Low pressure switch INDOOR OUTDOOR Oil return Capillary Oil separator T2 Evaporator temp sensor middle Electronic expansion valve CAPILIARY TUBE ...

Page 42: ...39 6 Wiring Diagram 6 1 Indoor Unit CCA3U 09HRFN1 M C CCA3U 12HRFN1 M C CCA3U 18HRFN1 M C MCD 24HRFN1 M C CTBU 09HWFN1 M C CTBU 12HWFN1 M C CTBU 18HWFN1 M C CTBU 24HWFN1 M C ...

Page 43: ...40 CFAU 09HRFN1 M C CFAU 12HRFN1 M C MCD 36HRFN1 M C MCD 48HRFN1 M D ...

Page 44: ...41 CTBU 36HWFN1 M C CTBU 48HWFN1 M C ...

Page 45: ...42 MUEU 18HRFN1 M C MUEU 24HRFN1 M C MUE 36HRFN1 M C ...

Page 46: ...43 MUE 48HRFN1 M C MUE 60HRFN1 MW ...

Page 47: ...44 MUE 36HRFN1 M C MUE 48HRFN1 M C ...

Page 48: ...45 MUE 60HRFN1 MW MTI 18HWFN1 MT0W MTIU 24HWFN1 MW ...

Page 49: ...46 MTIU 36HWFN1 MW MTIU 48HWFN1 MW MHG 60HWFN1 MW ...

Page 50: ...47 6 2 Outdoor Unit MOB30 09HFN1 MX0W MOB01 09HFN1 MW0W MOB30 12HFN1 MV0W MOB01 12HFN1 MV0W MOCA30 18HFN1 MT0W MOCA01 18HFN1 MT0W MOCA31 18HFN1 MT0W MOD31 24HFN1 MT0W ...

Page 51: ...48 MOBA30 09HFN1 MT0W MOB30 12HFN1 MT0W ...

Page 52: ...49 MOD30 24HFN1 MT0W MOD01 23HFN1 MT0W ...

Page 53: ...50 MOD30U 36HFN1 M ...

Page 54: ...R175 R178 C409 IC402 C403 IC11 E402 D401 C401 R403 C411 C40 C50 D403 R401 R405 R406 R404 E404 D402 D404 C408 C402 E403 R407 R408 C404 C110 E409 E401 R402 C405 10 9 7 6 5 4 3 1 T401 C406 C407 D13 D14 E406 E407 E408 E502 E503 E504 DZ503 CN25 R6 R9 CN60 IC406 IC407 C7 D1 R1 R137 IC2 PC851 IC1 PC817 R2 R126 R125 R123 R122 R119 R118 R117 R15 R14 C99 C98 C97 C96 C95 C94 C93 C66 D20 R17 CN17 CN10 CN1 C41...

Page 55: ...C25 C24 C23 C22 C21 C20 C19 C17 C16 C15 C14 C13 C12 C11 C10 C9 C8 C7 C6 C5 C4 C3 C2 C1 JP1 JP2 D29 D30 CN23 SSR1 CN7 CN13 P 1 L1 R82 R83 R84 R85 R86 R87 R97 R119 R122 R132 CN35 N CN37 FAN L Q3 Q6 Q7 Q8 Q9 CN36 FAN H E2 IC3 Q1 Q4 IC4 ZR4 RY4 CN32 CN38 L2 R135 SW1 CN21 Electric Expansion Value B Electric Expansion Value E Electric Expansion Value D Electric Expansion Value C Electric Expansion Value...

Page 56: ...28 R601 R603 R605 R607 R608 R610 R611 R612 R615 R616 R617 R618 R619 R620 R626 RY2 ZR1 CN6 D401 D404 Rdi IC102 D602 R171 C611 D101 C101 E106 C1 C520 ZR3 CN30 CN29 CN28 C307 C308 C309 C310 C311 R303 R304 R305 R306 R314 R426 C320 C321 C323 C511 C512 C513 IC301 R317 R318 R319 R320 R321 R322 R323 R517 R518 R519 R520 R521 R522 R523 CN50 E206 E605 C134 C314 C316 C318 CN25 D610 R196 RY3 C624 R602 R623 C11...

Page 57: ...C256 IC14 24C08 IC10 IC7 IC4 IC2 E34 E33 E27 E25 E24 E22 E21 E20 E17 E16 E15 E14 E13 E12 E10 E9 E8 E7 E6 E5 E4 E1 DZ9 DZ8 DZ7 DZ6 DZ1 D26 D14 D13 D12 D11 D10 D9 D8 D6 D5 D4 D3 D2 CN57 1 CN56 CN54 L IN2 CN53 N IN2 CN52 CN51 CN19 OUTFAN DC C124 C123 C122 C121 C120 C119 C118 C117 C116 C114 C111 C109 C108 C107 C106 C105 C104 C103 C102 C101 C100 C99 C97 C94 C82 C79 C78 C77 C76 C72 C71 C70 C69 C67 C66 C...

Page 58: ... 1 2 3 4 Model 12 0 02 5 0 04 10 0 08 20 0 12 30 0 16 40 0 0 18 0 45 Model 18 0 04 10 0 10 25 0 14 35 0 18 45 0 22 55 0 0 28 0 70 18 Model 24 0 04 10 0 10 25 0 16 40 0 22 55 0 28 70 0 0 40 0 100 24 Model 60 0 08 20 0 14 35 0 20 50 0 26 65 0 32 80 0 0 40 0 100 Factory Setting ...

Page 59: ...56 CTBU 09HWFN1 M C Code 0 Code 1 Code 2 Code 3 Code 4 ...

Page 60: ...57 CTBU 12HWFN1 M C Code 0 Code 1 Code 2 Code 3 Code 4 ...

Page 61: ...58 CTBU 18HWFN1 M C Code 0 Code 1 Code 2 Code 3 Code 4 ...

Page 62: ...59 CTBU 24HWFN1 M C Code 0 Code 1 Code 2 Code 3 Code 4 ...

Page 63: ...60 CTB 36HWFN1 M C Code 0 Code 1 Code 2 Code 3 Code 4 ...

Page 64: ...61 CTB 48HWFN1 M C Code 0 Code 1 Code 2 Code 3 Code 4 ...

Page 65: ... 2800 3300 3800 External static pressure Pa Air volume m3 h High Speed Minimum rpm switch 0 Maximum rpm switch 4 0 20 40 60 80 100 120 140 160 180 1800 2300 2800 3300 3800 External static pressure Pa Air volume m3 h Low Speed Minimum rpm switch 0 Maximum rpm switch 4 ...

Page 66: ...M C 60 208 230V 187V 253V MTI 18HWFN1 MT0W 60 208 230V 187V 253V MCD 24HRFN1 M C 60 208 230V 187V 253V CTBU 24HWFN1 M C 60 208 230V 187V 253V MUEU 24HRFN1 M C 60 208 230V 187V 253V MTIU 24HWFN1 MW 60 208 230V 187V 253V MCD 36HRFN1 M C 60 208 230V 187V 253V CTB 36HWFN1 M C 60 208 230V 187V 253V MUE 36HRFN1 M C 60 208 230V 187V 253V MTIU 36HWFN1 MW 60 208 230V 187V 253V MCD 48HRFN1 M D 60 208 230V 1...

Page 67: ... Noise level dB A H M L CTBU 09HWFN1 M C 37 34 31 CTBU 12HWFN1 M C 39 36 32 CTBU 18HWFN1 M C 35 33 31 CTBU 24HWFN1 M C 50 47 45 CTBU 36HWFN1 M C 53 49 45 CTBU 48HWFN1 M C 44 47 41 MTI 18HWFN1 MT0W 39 37 35 MTIU 24HWFN1 MW 44 40 35 MTIU 36HWFN1 MW 46 42 39 MTIU 48HWFN1 MW 52 49 46 MHG 60HWFN1 MW 57 54 51 ...

Page 68: ...5 1 4m Microphone Model Noise level dB A H M L CCA3U 09HRFN1 M C 41 39 37 CCA3U 12HRFN1 M C 41 38 35 CCA3U 18HRFN1 M C 46 43 41 MCD 24HRFN1 M C 51 47 43 MCD 36HRFN1 M C 52 47 44 MCD 48HRFN1 M C 53 49 45 ...

Page 69: ...U 09HRFN1 M C 45 41 35 CFAU 12HRFN1 M C 44 42 38 Microphone 1m 1m Air outlet side 1 5m 1m Microphone Model Noise level dB A H M L MUBU 18HRFN1 M C 47 44 38 MUEU 24HRFN1 M C 53 49 45 MUE 36HRFN1 M C 55 48 41 MUE 48HRFN1 M C 57 54 52 MUE 60HRFN1 MW 55 49 46 ...

Page 70: ...HFN1 MW0W 59 MOBA30 09HFN1 MT0W 56 MOB30 12HFN1 MT0W 57 MOB30 12HFN1 MV0W MOB01 12HFN1 MV0W 56 MOCA30 18HFN1 MT0W MOCA01 18HFN1 MT0W 59 MOCA31 18HFN1 MT0W 59 MOD30 24HFN1 MT0W MOD01 23HFN1 MT0W 61 MOD31 24HFN1 MT0W 61 MOD30U 36HFN1 M 65 MOE30U 48HFN1 M 63 MOE30U 60HFN1 M 64 H 1 0m Outdoor Unit Microphone ...

Page 71: ... manual 1 EMS It s fitting Magnetic ring twist the electric wires L and N around it to five circles 1 Cassette Units Name Shape Quantity Installation Fittings Installation paper board 1 Tubing Fittings Soundproof insulation sheath 1 Drainpipe Fittings Out let pipe sheath 1 Out let pipe clasp 1 Drain joint 1 Seal ring 1 Remote controller Its Frame The product you have might not be provided the foll...

Page 72: ...ole Units Name Shape Quantity Installation fittings Hook 2 Remote controller Its Frame Remote controller 1 Frame 1 Mounting screw ST2 9 10 C H 2 Alkaline dry batteries AM4 2 Others Installation manual 1 Owner s manual 1 Ceiling floor Units Name Shape Quantity Remote controller Its holder 1 Remote controller 1 2 Remote controller holder 1 3 Mounting screw ST2 9 10 C H 2 4 Alkaline dry batteries AM4...

Page 73: ... 14AWG Strong Electric Signal 4 core cable 16AWG 4 core cable 16AWG Weak Electric Signal Model 36K 48K 60k Power Phase 1 phase 1 phase Frequency and Voltage 208 230V 60Hz 208 230V 60Hz Circuit Breaker Fuse A 40 30 50 40 Indoor Unit Power Wiring Indoor Outdoor Connecting Wiring Outdoor Unit Power Wiring 3 core cable 12AWG 3 core cable 10AWG Strong Electric Signal 3 core cable 16AWG 3 core cable 14A...

Page 74: ...71 12 Field Wiring 36K 48K 60K ...

Page 75: ...lowable value The place where the noise vibration and outlet air do not disturb the neighbors There is enough room for installation and maintenance The air outlet and the air inlet are not impeded and not face the strong wind It is easy to install the connecting pipes and cables There is no danger of fire due to leakage of inflammable gas It should be a dry and well ventilation place The support s...

Page 76: ...4 After you select an installation location align the refrigerant pipes drain pipes as well as indoor and outdoor wires with their connection points before mounting the unit 5 Drill 4 holes 10cm 4 deep at the ceiling hook positions in the internal ceiling Be sure to hold the drill at a 90 angle to the ceiling 6 Secure the bolt using the washers and nuts provided 7 Install the four suspension bolts...

Page 77: ...capacity of the system and the network address of the air conditioner can be set by the switches on the indoor Main Control Board Before setting turn off the power After setting restart the unit Setting is not allowed when the unit is power on 1 Horsepower code setting The capacity of the indoor unit has been set in the factory according to the below table ENC1 Toggle switch Code Capacity kw Note ...

Page 78: ...blocks have been insert to the flange positional holes For A6 Duct units 1 Take off ventilation panel and flange cut off the staples at side rail 2 Change the mounting positions of ventilation panel and air return flange 3 When installing the filter mesh fit it into the flange as illustrated in the following figure NOTE All the figures in this manual are for demonstration purposes only The air con...

Page 79: ...e concave side of the installation hooks toward the expansible hooks Determine the length of the installation hooks from the height of ceiling then cut off the unnecessary part If the ceiling is extremely high please determine the length of the installation hook depending on the real situation 12 2 2 4 Install the main body Make the 4 suspender through the 4 hanger of the main body to suspend it A...

Page 80: ...ition well 12 2 2 5 Install the panel Remove the grille Hang the panel to the hooks on the mainbody Tighten the screws under the panel hooks till the panel closely stick on the ceiling to avoid condensate water Hang the air in grill to the panel then connect the lead terminator of the swing motor and that of the control box with corresponding terminators on the body respectively Note The panel sha...

Page 81: ...on Capacity Btu h D E 18K 24K mm 983 220 inch 38 70 8 66 36K mm 1200 220 inch 47 24 8 66 48K 60K mm 1565 220 inch 61 61 8 66 Wall mounted installation 12 2 4 3 Install the pendant bolt Ceiling installation Select the position of installation hooks according to the hook holes positions showed in upper picture Drill four holes of Ø12mm 45 50mm deep at the selected positions on the ceiling Then embed...

Page 82: ... the mounting bolts on the unit Put the side panels and grilles back Wall mounted installation Hang the indoor unit by insert the tapping screws into the hanging arms on the main unit The bottom of body can touch with floor or suspended but the body must install vertically 12 2 5 Slim cassette indoor unit installation 12 2 5 1 Service space for indoor unit Capacity Btu h A H 24K mm 205 235 inch 8 ...

Page 83: ...ger of the main body to suspend it Adjust the hexangular nuts on the four installation hooks evenly to ensure the balance of the body Use a leveling instrument to make sure the levelness of the main body is within 1 Adjust the position to ensure the gaps between the body and the four sides of ceiling are even The body s lower part should sink into the ceiling for 10 12 mm In general L is half of t...

Page 84: ...minators on the body respectively Install the 4 corner covers back Note The panel shall be installed after the wiring connected 12 2 6 HESP duct indoor unit installation 12 2 6 1 Service space for indoor unit 12 2 6 2 Bolt pitch Capacity KBtu Size of mounted lug D E 60 700 1436 12 2 6 3Install the pendant bolt Select the position of installation hooks according to the hook holes positions showed i...

Page 85: ... installation 12 3 1 Service space for outdoor unit More than 30cm 11 81in More than 60cm 23 62in More than 200cm 78 74in Air inlet Air inlet More than 30cm 11 81in Air outlet Wall or obstacle Maintain channel More than 60cm 23 62in 12 3 2 Bolt pitch For the value of A B and D please refer to the dimension part 14 3 3 Install the Unit Since the gravity center of the unit is not at its physical cen...

Page 86: ... specification table 2 Confirm the cross way of the pipes 3 Measure the necessary pipe length 4 Cut the selected pipe with pipe cutter Make the section flat and smooth 9 0 Lean Crude Burr o 5 Insulate the copper pipe Before test operation the joint parts should not be heat insulated 6 Flare the pipe Insert a flare nut into the pipe before flaring the pipe According to the following table to flare ...

Page 87: ...id neutral detergent on the connections with a soft brush to check for leakage in the pipe connecting points If bubbles emerge the pipes are leaking 1 Air Purging Using the Vacuum Pump 1 Completely tighten the flare nuts on the indoor and outdoor units Confirm that both the2 way and 3 way valves are set to the closed position 2 Connect the charge hose with the push pin of the Handle Lo to the 3 wa...

Page 88: ...e port cap to a torque of 18N m Be sure to check for gas leaks 12 4 4 Adding Refrigerant after Long Term System Operation Procedure 1 Connect the charge hose to the 3 way service port and open the 2 way and 3 way valve Connect the charge hose to the valve at the bottom of the cylinder If the refrigerant is R410A place the cylinder bottom up to ensure liquid charge 2 Purge the air from the charge h...

Page 89: ... way valves are closed 2 Connect the charge set and a charging cylinder to the service port of the 3 way valve Leave the valve on the charging cylinder closed 3 Purge the air from the charge hose Open the valves on the charging cylinder and the charge set Purge the air by loosening the flare nut on the 2 way valve approximately 45 for 3 seconds and then closing it for 1 minute Repeat 3 times After...

Page 90: ...frigerant If the system cannot be charged with the specified amount of refrigerant or can be charged with a only a small amount at a time approximately 150g each time turn the unit on in cooling mode however one time is not sufficient wait approximately 1 minute and then repeat the procedure 5 If the electronic scale displays the proper weight disconnect the charge hose from the 3 way valve s serv...

Page 91: ...rk PVC25 20 220 For branch pipe PVC32 25 410 PVC40 31 730 Could be used PVC50 40 1440 for confluence pipe PVC63 51 2760 PVC75 67 5710 PVC90 77 8280 Attention Adopt PVC40 or bigger pipe to be the main pipe 3 Individual design of drainage pipe system The drainage pipe of air conditioner shall be installed separately with other sewage pipe rainwater pipe and drainage pipe in building The drainage pip...

Page 92: ...pipe system there should design a blowhole at the highest point of main pipe to ensure the condensate water discharge smoothly The air outlet shall face down to prevent dirt entering pipe Each indoor unit of the system should be installed it The installation should be considering the convenience for future cleaning Blowhole Plug Indoor unit Plug Indoor unit 9 The end of drainage pipe shall not con...

Page 93: ...t shall cause shutdown of unit When this situation happens the normal startup only can be recovered by turning down power supply and eliminating accumulated water Note Drain plug at the main water containing plate is used for eliminating accumulated water in water containing plate when maintaining air conditioner fault During normal operation the plug shall be filled in to prevent leakage 12 5 4 I...

Page 94: ...g construction Procedures of special vacuum drying are as follows Vacuum drying for 1 hour Vacuum damage filling nitrogen to reach 0 5Kgf cm2 Because nitrogen is dry gas vacuum damage could achieve the effect of vacuum drying but this method could not achieve drying thoroughly when there is too much moisture Therefore special attention shall be drawn to prevent the entering of water and the format...

Page 95: ...If insulation is not enough it shall form dew and cause leakage Temperature of gas pipe is very high generally 50 100 during heating Insulation work must be carried out to prevent hurt by carelessness touching 3 Insulation material selection for refrigerant pipe The burning performance should over 120 According to the local law to choose insulation materials The thickness of insulation layer shall...

Page 96: ... date showing in the table Select different colors for different wire according to relevant regulations Do not use metal wire tube at the place with acid or alkali corrosion adopt plastic wire tube to replace it There must be not wire connect joint in the wire tube If joint is a must set a connection box at the place The wiring with different voltage should not be in one wire tube Ensure that the ...

Page 97: ...on or abnormal noise during operation Outdoor unit Whether there is vibration or abnormal noise during operation Whether the generated wind noise or condensed of by the air conditioner have influenced your neighborhood Whether any of the refrigerant is leaked ...

Page 98: ...re Hyper heat 30 50 22 122 30 50 22 122 CAUTION 1 If the air conditioner is used beyond the above conditions certain safety protection features may come into operation and cause the unit to operate abnormally 2 The room relative humidity should be less than 80 If the air conditioner operates beyond this figure the surface of the air conditioner may attract condensation Please set the vertical air ...

Page 99: ...rs 14 3 2 Temperature protection of compressor top The unit will stop working when the compressor top temp protector cut off and will restart after the compressor top temp protector restart 14 3 3 Temperature protection of compressor discharge When the compressor discharge temp is getting higher the running frequency will be limited as below rules Compressor discharge temp T5 115 239 F for 5s comp...

Page 100: ...le protection The Inverter module has a protection function about current voltage and temperature If these protections happen the corresponding code will display on indoor unit and the unit will stop working 14 3 6 Indoor fan delayed open function When the unit starts up the louver will be active immediately and the indoor fan will open 7s later If the unit runs in heating mode the indoor fan will...

Page 101: ...um low and auto The indoor fan is controlled as below Setting fan speed Actual fan speed H H H G A H H B C M M M Z D M M M E F L L L D G L L L H I T1 Td F L L L L D H H H H G M M M M Z 4 5 8 1 3 0 5 4 1 5 2 7 4 5 8 1 3 0 5 4 1 5 2 7 4 5 8 1 3 0 5 4 1 5 2 7 Auto fan in cooling mode acts as follow a b c d 6 0 C 10 8 F T1 Td e H H L 0 75 L H L 0 5 L H L 0 25 L L 5 0 C 9 0 F 4 0 C 7 2 F 2 5 C 4 5 F 1 ...

Page 102: ... has run for 10 minutes in defrosting mode Defrosting action Compressor Outdoor fan 4 Way valve X1 10S 10S no longer than 10min X2 14 4 3 5 Evaporator coil temperature protection TEstop T2 Resume Off Decrease TEdown TEH2 Hold Off Compressor stops Decrease Decrease the running frequency to the lower level Hold Keep the current frequency Resume No limitation for frequency 14 4 4 Auto mode This mode ...

Page 103: ...estart function which is carried out through an auto restart module In case of a sudden power failure the module memorizes the setting conditions before the power failure The unit will resume the previous operation setting not including sleep function automatically after 3 minutes when power returns 14 4 9 Follow me 1 If the indoor PCB receives the signal which results from pressing the FOLLOW ME ...

Page 104: ...humidifying and forced cooling mode the pump will start running immediately and continuously till stop cooling 2 Once the water level increase and up to the control point LED will alarm and the drain pump open and continue checking the water level If the water level fall down and LED disalarmed drain pump delay close 1 minute and operate with the last mode Otherwise the entire system stop operatin...

Page 105: ...quiry information Displaying code Meaning T1 T1 T1 temp T2 T2 T2 temp T3 T3 T3 temp T4 T4 T4 temp T2B Tb T2B temp TP TP TP temp TH TH TH temp Targeted Frequency FT Targeted Frequency Actual Frequency Fr Actual Frequency Indoor fan speed IF Indoor fan speed Outdoor fan speed OF Outdoor fan speed EXV opening angle LA EXV opening angle Compressor continuous running time CT Compressor continuous runni...

Page 106: ...31 139 E0 E1 E9 140 141 149 F0 F1 F9 150 151 159 Indoor fan speed Outdoor fan speed 0 OFF 1 2 3 4 Low speed Medium speed High speed Turbo For some big capacity motors 14 FF Actual fan speed Display value turns to decimal value and then multiply 10 The unit is RPM For some small capacity motors display value is from 14 FF hexadecimal the corresponding fan speed range is from 200 2550RPM EXV opening...

Page 107: ...ctrolytic Capacitors HIGH VOLTAGE CAUTION For other models For other models connect a discharge resistor approx 100Ω 40W or a soldering iron plug between the and terminals of the electrolytic capacitor on the opposite side of the outdoor printed circuit board PCB Note The picture above is for reference purposes only The design of the devices depicted may vary by model ...

Page 108: ...discharge temperature sensor T5 malfunction 5 times O F4 Outdoor unit EEPROM parameter error 6 times O F5 Outdoor fan speed malfunction 7 times O F6 Indoor coil outlet pipe sensor T2B malfunction for 36k 48k models 8 times O F7 Communication malfunction between Cassette optional lift panel and the unit 9 times O F8 Cassette optional lift panel malfunction 10 times O F9 Cassette optional lift panel...

Page 109: ...Operation normally X O 3 Compressor drive board EEPROM error O E5 4 IPM malfunction or IGBT over strong current protection X P0 5 Over voltage or too low voltage protection O O P1 6 Inverter compressor drive error X P4 7 Inverter compressor drive error O P4 8 Communication malfunction between main control board and driver board P4 ...

Page 110: ... board and IPM board J4 18 High pressure protection J5 19 Low pressure protection J6 20 Outdoor IPM module temperature sensor malfunction P7 21 AC voltage protection J8 Outdoor check function N Display Remark 00 Normal display Display running frequency running state or malfunction code 01 Indoor unit capacity demand code Actual data HP 10 If capacity demand code is higher than 99 the digital displ...

Page 111: ...it symbol Bit7 Frequency limit caused by IGBT radiator The display value is hex number For example the digital display tube show 2A then Bit5 1 Bit3 1 Bit1 1 It means frequency limit caused by T4 T3 and current Bit6 Frequency limit caused by PFC Bit5 Frequency limit caused by T4 Bit4 Frequency limit caused by T2 Bit3 Frequency limit caused by T3 Bit2 Frequency limit caused by T5 Bit1 Frequency lim...

Page 112: ...24 3 Indoor unit capacity demand code 25 Room temp T1 of 1 indoor unit If the temp is lower than 0 degree the digital display tube will show 0 If the temp is higher than 70 degree the digital display tube will show 70 If the indoor unit is not connected the digital display tube will show 26 Room temp T1 of 2 indoor unit 27 Average room temp T1 28 Reason of stop 29 Evaporator pipe temp T2B of 1 ind...

Page 113: ...tallation mistake Faulty PCB Trouble shooting Yes Replace the indoor outdoor main PCB Power off then restart the unit 2 minutes later Does a problem still remain EEPROM a type of read only memory The contents can be erased and reprogrammed using a pulsed voltage To locate the EEPROM chip Indoor PCB Outdoor PCB Note The two photos above are only for reference purposes only The design of the devices...

Page 114: ... Yes Power off then restart the unit 2 minutes later Power off then restart the unit 2 minutes later No Replace the outdoor main PCB Power on Is the error extinguished Replace the outdoor main PCB Power on Is the error extinguished Check the outdoor wiring connection Check the outdoor wiring connection Replace the indoor main PCB Power on Is the error extinguished Replace the indoor main PCB Power...

Page 115: ... 50V If the outdoor unit has malfunction the voltage will move alternately with positive value While if the indoor unit has malfunction the voltage will be a certain value Remark The old label is L1 L2 S L1 L2 The new label is 1 2 3 L1 L2 Remark Use a multimeter to test the resistance of the reactor which does not connect with capacitor The normal value should be around zero ohm Otherwise the reac...

Page 116: ...ence or add magnet ring on power wire Remove interference or add magnet ring on power wire Yes Replace the signal wire Replace the signal wire Yes Pull out and insert back Pull out and insert back No No Replace the indoor main PCB is the error resolved Replace the indoor main PCB is the error resolved Yes Replace the outdoor Main PCB Replace the outdoor Main PCB No Is there any interference such a...

Page 117: ...an motor Faulty PCB Trouble shooting Power off then restart the unit after 2 minutes Does a problem remain Shut off the power supply Rotate the fan by hand Does it turn easily The unit is operating normally Find the cause of the problem and resolve it Check the wiring of fan motor Is it improperly wired No Yes No Correct the connections No No Replace the fan motor Yes Yes Measure the voltage for t...

Page 118: ... well as between pin4 and pin3 in fan motor connector If the value of the voltage is not within the range shown in the following table the PCB may be experiencing problems and need to be replaced DC motor voltage input and output NO Color Signal Voltage 1 Red Vs Vm 200 380V 2 3 Black GND 0V 4 White Vcc 13 5 16 5V 5 Yellow Vsp 0 6 5V 6 Blue FG 13 5 16 5V ...

Page 119: ...an 0 06V or higher than 4 94V the LED displays a failure Potential causes Wiring mistake Faulty sensor Faulty PCB Trouble shooting Check the connection between temperature sensor and PCB Is it properly wired Ensure proper connection No Yes Replace indoor or outdoor main PCB Measure the resistance value of the sensor Is it within acceptable parameters Replace the sensor No Yes ...

Page 120: ...onds and compressor running frequency is not higher than 50Hz for 3 minutes Potential Causes Faulty T2 sensor Faulty indoor PCB System problems such as leakage or blockages Trouble shooting Is there cool air blowing out from indoor air outlet Yes Yes Check the T2 sensor Is it securely attached No Check system for leakages Are any leakages present No Power off then restart the unit 2 minutes later ...

Page 121: ...rt the water level switch well Insert the water level switch well If the water level switch is broken If the water level switch is broken Yes Replace the water level switch Replace the water level switch Replace the water pump If malfunction is still not solved Replace the water pump If malfunction is still not solved Yes No Yes Replace the indoor main PCB Replace the indoor main PCB Power off the...

Page 122: ...ty outdoor PCB Trouble shooting Check the wiring between main PCB and compressor Does an error exist Ensure a proper connection or replace the wires and connectors Yes No Check the IPM Is it in working order No Yes Replace the IPM board or replace the main PCB Check the outdoor fan and the outdoor unit ventilation Is it in working order No Please refer to the solution to the fan speed is out of co...

Page 123: ...120 P U P V ...

Page 124: ...121 P W P N ...

Page 125: ...k the connections and w i r e s Are they in working order Turn off the unit No Yes No Ensure proper connections or replace the wires Yes Replace the reactor Yes No Replace the IPM board Turn power on and while the unit is on standby check if the voltage between P and N is at DC 310V 340V or 380V Then start up the unit and measure the voltage between P and N Is it in now between 220V 400V Check the...

Page 126: ...outdoor units Does a problem exist Clear up the air inlet and outlet or the heat exchanger of the indoor and outdoor units Yes No Yes Yes Power off and then restart the unit 10 minutes afterwards Check compressor temperature Is it within acceptable parameters No Check the refrigerant system Is it functioning properly Yes Check the overload protector Is it properly wired Ensure a proper connection ...

Page 127: ...ronic control box is Installed good Check whether electronic control box is Installed good Check whether thermal grease is no coating or uneven coating Check whether thermal grease is no coating or uneven coating Yes Yes No Install the electronic control box correctly Install the electronic control box correctly Fix the radiator well Fix the radiator well Coat thermal grease again Coat thermal gre...

Page 128: ...r fan assembly Compressor malfunction Faulty outdoor PCB Trouble shooting Check the wiring between the main PCB and compressor Is it improperly wired Ensure proper connection or replace the wires and connectors Yes No Check the IPM Is it functioning properly No Yes Replace the IPM board or replace the main PCB Check the outdoor fan and the outdoor unit ventilation Is it functioning properly No Ple...

Page 129: ...0 06V or higher than 4 94V the LED displays a failure Potential causes Wiring mistake Faulty sensor Faulty PCB Trouble shooting Check the connection between temperature sensor and PCB Is it properly wired Ensure proper connection No Yes Replace outdoor main PCB Measure the resistance value of the sensor Is it within acceptable parameters Replace the sensor No Yes ...

Page 130: ...n between T2 and The PCB is in working order Have T2 and T2B been reversed Is the resistance of T2 normal according to Appendix 1 Is the resistance of T2 normal according to Appendix 1 Replace the temperature sensor Replace the temperature sensor No Yes Yes Stop the unit Stop the unit Yes Is the air outlet blocked Is the air outlet blocked Are the heat exchanger and filter dirty Are the heat excha...

Page 131: ... that the outdoor unit ventilate is functioning properly Ensure that the outdoor unit ventilate is functioning properly Is the heat exchanger dirty Is the heat exchanger dirty No Clean the heat exchanger Clean the heat exchanger Yes Check whether the refrigerant system is functioning normally Check whether the refrigerant system is functioning normally Replace outdoor main board Has the problem be...

Page 132: ...compressor discharge temperature sensor and PCB connected properly according to the wiring diagrams Measure the resistance value of compressor discharge temp sensor If the value is not normal refer to the Appendix 2 Does a problem stil exist Measure the resistance value of compressor discharge temp sensor If the value is not normal refer to the Appendix 2 Does a problem stil exist No Yes Yes No Co...

Page 133: ...he PFC module is connected tightly Check whether the connecting line between main board and the PFC module is connected tightly Yes Measure whether the voltage between P and N is normal refer to the Appendix 3 Measure whether the voltage between P and N is normal refer to the Appendix 3 No Check whether the inductance of PFC module is good If the inductance is good the resistance of the two ports ...

Page 134: ...eck the signal wire between the Compressor driven chip and the main board is it connected properly Reconnect and retry Is the error still displayed Reconnect and retry Is the error still displayed Replace Compressor driven Chip Is the system running normally Replace Compressor driven Chip Is the system running normally Replace the electric control box Replace the electric control box No No No No Y...

Page 135: ...ken Is the outdoor ambient temperature is higher than 50 Is the outdoor ambient temperature is higher than 50 No Stop the unit Stop the unit Yes Check if the outdoor unit ventilation is good Check if the outdoor unit ventilation is good Yes Ensure that the outdoor unit ventilation is functioning properly Ensure that the outdoor unit ventilation is functioning properly Is the heat exchanger dirty I...

Page 136: ...place low pressure protector Replace low pressure protector No Is the low pressure protector broken Is the low pressure protector broken Is the outdoor ambient temperature too low Is the outdoor ambient temperature too low No Stop the unit Stop the unit Yes Open the valve core of the high pressure valve Open the valve core of the high pressure valve No Is the valve core of the high pressure valve ...

Page 137: ...on Malfunction decision conditions An abnormal voltage rise or drop is detected by checking the specified voltage detection circuit Supposed causes Abnormal power supply Wiring mistake Faulty bridge rectifier Faulty IPM board ...

Page 138: ...dge rectifier is normal Measure whether input voltage of bridge rectifier is normal Yes No No Measure whether the voltage between P and N is normal refer to the Appendix 3 Measure whether the voltage between P and N is normal refer to the Appendix 3 Replace the bridge rectifier Replace the bridge rectifier No Check whether bridge rectifier is normal Check whether bridge rectifier is normal Check t...

Page 139: ...sor from PCB measure the resistance value with a tester Temperature Sensors Room temp T1 sensor Indoor coil temp T2 sensor Outdoor coil temp T3 sensor Outdoor ambient temp T4 sensor Compressor discharge temp T5 sensor Measure the resistance value of each winding by using the multi meter ...

Page 140: ...7 243 0 38991 2 28 39 8239 38 100 5 62961 78 172 1 25423 118 244 0 37956 1 30 37 1988 39 102 5 39689 79 174 1 2133 119 246 0 36954 0 32 35 2024 40 104 5 17519 80 176 1 17393 120 248 0 35982 1 34 33 3269 41 106 4 96392 81 178 1 13604 121 250 0 35042 2 36 31 5635 42 108 4 76253 82 180 1 09958 122 252 0 3413 3 37 29 9058 43 109 4 5705 83 181 1 06448 123 253 0 33246 4 39 28 3459 44 111 4 38736 84 183 ...

Page 141: ...138 ...

Page 142: ...4 25 222 8 36 97 34 32 76 169 7 82 116 241 2 357 3 27 211 4 37 99 32 94 77 171 7 566 117 243 2 294 2 28 200 7 38 100 31 62 78 172 7 321 118 244 2 233 1 30 190 5 39 102 30 36 79 174 7 086 119 246 2 174 0 32 180 9 40 104 29 15 80 176 6 859 120 248 2 117 1 34 171 9 41 106 28 81 178 6 641 121 250 2 061 2 36 163 3 42 108 26 9 82 180 6 43 122 252 2 007 3 37 155 2 43 109 25 86 83 181 6 228 123 253 1 955 ...

Page 143: ...140 Appendix 3 10 11 12 13 14 15 16 17 18 19 20 21 22 48 50 52 54 56 58 60 62 64 66 68 70 72 23 24 25 26 27 28 29 30 31 32 33 34 35 74 76 78 80 82 84 86 88 90 92 94 96 98 ...

Page 144: ...sistance value of each winding by using the tester Position Resistance Value ASN98D22UFZ ASM135D23UFZ ATF235D22UMT ATF250D22UMT ATF310D43UMT ATQ420D1UMU ATM115D43UFZ2 Blue Red 1 57Ω 1 75 Ω 0 75 Ω 0 75 Ω 0 65 Ω 0 38Ω 1 87Ω Blue Black Red Blue ...

Page 145: ...veral MΩ P N U N U V V W W Red 4 Pressure on Service Port Cooling chart COOLING MODE Indoor Temp Outdoor temp 75 23 89 85 29 44 95 35 105 40 56 115 46 11 BAR 70 8 2 7 8 8 1 8 6 10 1 BAR 75 8 6 8 3 8 7 9 1 10 7 BAR 80 9 3 8 9 9 1 9 6 11 2 PSI 70 119 113 117 125 147 PSI 75 124 120 126 132 155 PSI 80 135 129 132 140 162 MPA 70 0 82 0 78 0 81 0 86 1 01 MPA 75 0 86 0 83 0 87 0 91 1 07 MPA 80 0 93 0 89 ...

Page 146: ... 0 26 6 25 4 23 3 BAR 75 33 8 31 5 27 8 26 3 24 9 PSI 55 439 413 367 330 302 PSI 65 471 435 386 368 339 PSI 75 489 457 403 381 362 MPA 55 3 03 2 85 2 53 2 28 2 08 MPA 65 3 25 3 00 2 66 2 54 2 33 MPA 75 3 38 3 15 2 78 2 63 2 49 0 0 5 0 10 0 15 0 20 0 25 0 30 0 35 0 40 0 57 13 89 47 8 33 37 2 78 27 2 78 17 8 33 55 65 75 Pressure bar Outdoor temp ...

Page 147: ... Disconnect the fan motor wire fan capacity wire room temperature sensor wire and evaporator temperature sensor wire 3 Screw off the screws to remove electronic control box 2 Remove the display board 1 Remove the cover of electronic control box Repeat the operation of step1 of No1 2 Disconnect the display board wire connected to PCB 3 Remove the sticker Four screws Connector Sticker 2 screws Plug ...

Page 148: ...rs connected to the PCB and remove the ground wire after remove the screw 2 Remove the PCB from the electronic control box 4 Remove the fan capacitor 1 Remove the cover of electronic control box Repeat the operation of step1 of No1 2 Disconnect the fan capacity wire Repeat the operation of step2 of No1 3 Screw off the screw to remover it Press the four fixing holders from four corners to remove th...

Page 149: ...emble the fan motor fixing clamps to remove the fan motor assembly and fan wheel assembly 8 Disassemble the fan wheels then you can remove the fan motor Press the clips to take off the volute shell Press Press 5 screws Rear cover board Total four screws at the left side and right side The fan motor assembly and fan wheel assembly can be removed after took off the 2screws used to fix the fan motor ...

Page 150: ...1 of No 5 2 Screw off the screws to remove the water collector assembly 7 Remove the evaporator 1 Remove the water collector Repeat the operation of No 6 2 Remove the evaporator sensor 3 Remove the pipe clamp board 4 screws 3 screws 3 screws Evaporator sensor 2 screws 3 screws Water collector assembly ...

Page 151: ...148 4 Remove the evaporator support board 5 Screw off the fixing screws to remove the evaporator 4 screws 1 screw ...

Page 152: ...Screw off two screws Disconnect the display board wire and swing motor wire connected to the PCB Remove the grille 5 Loose the four screws and two wireropes then the panel can be disassembled 3 Remove the display board 1 Open the grille Repeat the operation of step1 of No 1 2 Remove the grille Repeat the operation of step2 of No 2 3 Disassemble the display board Remove the display Grill switch 2 s...

Page 153: ...f step1 2 3 of No 2 2 Screw off 3 screws to remove the swing motor assy 3 Screw off 1 screws to remove the swing motor 5 Remove the PCB 1 Open the grille Repeat the operation of step1 of No 1 No need to remove the panel 2 Disassemble the electronic control box cover after remove the 2 screws 2 screws 4 screws 3 screws 1 screw ...

Page 154: ...l 2 Remove the electronic control box cover Repeat the operation of step 2 of No 5 3 Pull out all the plugs or connectors connected to the electronic control box 4 Remove the electronic control box Remove the 2 screws to disassemble the electronic control box 7 Remover the fan wheel 1 Repeat the operation of No 5 2 Remove the ventilation ring Release the 4 screws to disassemble it 2 screws Pump RY...

Page 155: ... fan motor 1 Repeat the operation of No 6 2 Remove the fixing board of fan motor wire 3 Remove the 5 screws to disassemble the fan motor 9 Remove the water collecting 6 Remove the panel Repeat the operation of No 2 7 Remove the electronic control box Repeat the operation of No 6 3 nuts 5 screws ...

Page 156: ...er collecting assembly 10 Remove the draining pump 1 Remove the panel Repeat the operation of No 2 2 Remove the electronic control box Repeat the operation of No 6 3 Remove the water collecting assembly Repeat the operation of No 9 4 Disconnect the drain pipe 5 Release 2 screws to remove the pump supporter Be careful of the connection wires ...

Page 157: ...out of the supporter 11 Remove the evaporator 1 Remove the water collecting assembly Repeat the operation of No 9 2 Remove the seal board of evaporator 3 Remove the evaporator fixing board 4 Remove the evaporator fixing clamps to disassemble the evaporator 3 screws Fixing clamps 1 screw 4 screws ...

Page 158: ... filter 2 Remove the electronic control box 4 Remove the air front panel Open the front panel Repeat the operation of step1 of No 1 Remove the string Allowing the front panel to fall forward will enable you to remove it 5 Remove the filter Repeat the operation of step 2 of No 1 6 Remove four fixing screws to remove the panel frame assembly 4 screws push push ...

Page 159: ... wires evaporator coil temperature sensor T2 wire and two grounding wire yellow green to remove the electronic control box 3 Remove the PCB 6 Take out the electronic control box from the body and remove its cover Repeat the operation of step1 step6 of No2 T2 Louver motor connector DC motor connector Louver motor connector Screws of the grounding wire ...

Page 160: ... step1 step of No2 2 Remove the fixing glue to remove the display board 5 Remove the switch board 1 Remove the electronic control box Repeat the operation of step1 step of No2 2 Remove the fixing glue to remove the display board 7 Remove the air outlet grille assembly 1 Remove the front panel assembly and the panel frame assembly Repeat the operation of step1 step2 and step3 of No 2 2 screws ...

Page 161: ... 2 Screw off the screws to remove the motor 9 Remove the louver motor of the water collector 1 Remove the front panel assembly and the panel frame assembly Repeat the operation of step1 step2 and step3 of No 2 2 Remove the cover of louver motor 3 Screw off the screws to remove the motor 10 Remove the water collector 3 Remove the front panel assembly and the panel frame assembly Repeat the operatio...

Page 162: ...rator assembly 1 Remove the electronic control box Repeat the operation of No 2 to remove the electronic control box 2 Remove the air outlet grille assembly Repeat the operation of No 7 to remove the air outlet grille assembly 3 Remove the evaporator sensor and release the pipe strap 4 screws Louver motor connector ...

Page 163: ...ssembly Repeat the operation of No 7 to remove the air outlet grille assembly 3 Remove four fixing screws to remove the ventilation assembly 4 Remove the hex nut fixing the fan to remove the fan 13 Remove the fan motor 5 Remove the centrifugal fan Repeat the operation of No 12 to remove the centrifugal fan 6 Remove the fan motor after unfastening three fixing screws Each side has two screws 3 scre...

Page 164: ...r wire and evaporator temperature sensor wire 8 Screw off the screws to remove electronic control box 2 Remove the PCB 9 Remove the cover of electronic control box Repeat the operation of step1 of No1 2 Pull out all the plugs or connectors connected to the PCB and remove the ground wire after remove the screw Five screws Plug of room temperate sensor and evaporator temperature sensor Fan motor wir...

Page 165: ...ep1 of No1 7 Disconnect the reactance wire 8 Screw off the screw to remover it 4 Remove the drain pump 1 Remove the cover of electronic control box Repeat the operation of step1 of No1 2 Disconnect the drain pump wire 3 Screw off the screws to remover it Press the two fixing holders to remove the PCB 1 screw Reactance wire 4 screws Drain pump wire ...

Page 166: ...sassemble the fan wheels then you can remove the fan motor 6 Remove the water collector assembly 6 Remove the rear cover board Repeat the operation of step1 of No 5 7 Screw off the seven screws to remove the top cover then remove the water collector assembly 7 screws Press the clips to take off the volute shell Press 10 screws Rear cover board The fan motor assembly and fan wheel assembly can be r...

Page 167: ...n of No 6 11 Remove the evaporator sensor 12 Remove the pipe clamp board 13 Remove the evaporator support board 14 Screw off the fixing screws to remove the evaporator means there is no this part in some models Evaporator sensor 2 screws 4 screws 1 screw Water collector assembly ...

Page 168: ...onditioner and turn OFF the power breaker 2 Remove the big handle first then remove the top cover 3 screws 3 Remove the screws of front panel 6 screws 4 Remove the screws of the right side panel 6 screws 2 4 3 2 Fan ass y How to remove the fan ass y Screws of front panel 6 screws Screws of top panel 3 screws 1 screws is under the big handle 3 screw of big handle ...

Page 169: ...el plate following procedure 1 2 Remove the nut fixing the fan and remove the fan 3 Unfix the hooks and then open the electronic control box cover Fan ass y 2 3 Compressor and liquid gas separator Electronic control box reactor ...

Page 170: ...167 4 Disconnect the connector for fan motor from the electronic control board 5 Remove the four fixing screws of the fan motor then remove the motor 4 5 ...

Page 171: ...the two connectors for the compressor and the reactors 4 Pull out the two blue wires connected with the four way valve 3 Pull out connectors of the compressor top temp sensor condenser coil temp sensor T3 outdoor ambient temp sensor T4 and discharge temp sensor T5 4 Disconnect the Compressor crankcase 1 2 3 ...

Page 172: ...ctor 5 Disconnect the electronic expansion valve wire from the control board 6 Remove the ground wires 7 Remove the power supply wires old label L1 L2 S new label 1 2 3 8 Then remove the electronic control box 4 6 7 5 ...

Page 173: ...ts of four way valve and pipe 5 Then the four way valve ass y can be removed The picture of four way valve may be different from the one on your side 5 Compressor How to remove the compressor 1 After perform work of item1 2 3 2 Remove the discharge pipe and suction pipe with a burner 3 Remove the hex nuts and washers fixing the compressor on bottom plate 4 Lift the compressor from the base pan ass...

Page 174: ...peration of the air conditioner and turn OFF the power breaker 2 Remove the top panel 7 screws 3 Remove the screws of front panel 9 screws 4 Remove the screws of the right side panel 10 screws 2 4 3 2 Fan ass y How to remove the fan ass y 4 screws of top panel 9 screws of front panel 3 screws of big handle ...

Page 175: ... nut fixing the fan and then remove the fan 2 Unfix the hooks and then open the electronic control box cover 3 Disconnect the 1 2 T3 T4 T5 sensor wire Motor wire Electronic expansion valve Compressor wire 4 way valve wire Electric pipe heater and Crankcase electric heater ...

Page 176: ... the four fixing screws of the fan motor 5 Then remove the fan motor 3 Electrical parts How to remove the electrical parts 1 After finish work of item 1 and item 2 remove the connectors for the compressor and reactor 2 Pull out the two blue wires connected with the 1 4 2 ...

Page 177: ...ctors of the compressor top temp sensor condenser coil temp sensor T3 outdoor ambient temp sensor T4 and discharge temp sensor T5 4 disconnect the electronic expansion valve wire 5 remove the compressor Crankcase electric heater 3 3 4 5 ...

Page 178: ...175 6 Remove the grounding screw 7 Remove the power supply wires old label L1 L2 S new label 1 2 3 8 Then remove the electronic control box 错误 7 ...

Page 179: ...rts of four way valve and pipe 5 Then the four way valve ass y can be removed The picture of four way valve may be different from the one on your side 3 5 Compressor How to remove the compressor 1 After perform work of item1 2 3 2 Remove the discharge pipe and suction pipe with a burner 3 Remove the hex nuts and washers fixing the compressor on bottom plate 4 Lift the compressor from the base pan ...

Page 180: ...turn OFF the power breaker 2 Remove the big handle first then remove the top panel 7screws 3 Remove the screws of the front panel 11 screws 4 Remove the screws of the right side plate and remove the right side plate 12 screws 2 Fan ass y How to remove the fan ass y 3 screws of top panel 11 screws of front panel 4 screws of big handle 2 3 4 ...

Page 181: ... the fan 2 Unfix the hooks and screws then open the electronic control box cover 3 Disconnect the connector for fan motor from the electronic control board 1 2 Electric pipe heater and Crankcase electric Heater wire Motor wire Electronic expansion Valve wire 4 way valve T3 T4 T5 sensor wire Compressor wire ...

Page 182: ...s 1 After finish work of item 1 and item 2 remove the three connectors for the compressor and the compressor crankcase heater and the electric heater 2 Pull out the two blue wires connected with the four way valve 3 Pull out connectors of the compressor top temp sensor condenser coil temp sensor T3 outdoor ambient temp sensor T4 1 2 2 ...

Page 183: ...nsor T5 4 Disconnect the electronic expansion valve wire from the control board 5 Remove the grounding screw 6 Remove the power supply wires old label L1 L2 S old label 1 2 3 7 Then remove the electronic control box 3 4 5 4 6 5 ...

Page 184: ...ts of four way valve and pipe 5 Then the four way valve ass y can be removed The picture of four way valve may be different from the one on your side 3 4 5 Compressor How to remove the compressor 1 After perform work of item1 2 3 2 Remove the discharge pipe and suction pipe with a burner 3 Remove the hex nuts and washers fixing the compressor on bottom plate 4 Lift the compressor from the base pan...

Page 185: ...power breaker 2 Remove the big handle first then remove the top cover 3 screws 3 Remove the screws of front panel 7 screws 4 Remove the screws of the right side panel 11 screws 2 4 3 3 2 Fan ass y How to remove the fan ass y 1 After remove the Screws of front panel 7 screws Screws of top panel 3 screws 1 screws is under the big handle 3 screw of big handle ...

Page 186: ... fan and remove the fan 3 After remove the top cover Unfix the hooks and then open the electronic control box cover 4 Disconnect the connector for fan motor from the electronic control board 2 3 compressor T3 T4 T5 sensor Motor Electronic expansion valve 4 way valve ...

Page 187: ...184 5 Remove the four fixing screws of the fan motor then remove the motor 5 ...

Page 188: ...h work of item 1 and item 2 remove the connector for the compressor 6 Pull out the two blue wires connected with the four way valve 3 Pull out connectors of the condenser coil temp sensor T3 outdoor ambient temp sensor T4 and discharge temp sensor T5 4 Disconnect the 1 2 3 ...

Page 189: ...186 electronic expansion valve wire from the control board 5 Remove the ground wires 6 Remove the wires 1 2 3 7 Then remove the electronic control box 5 6 ...

Page 190: ...d pipe 5 Then the four way valve ass y can be removed The picture of four way valve may be different from the one on your side 5 Compressor How to remove the compressor 6 After perform work of item1 3 Recover refrigerant from the refrigerant circuit 7 Remove the discharge pipe and suction pipe with a burner 8 Remove the hex nuts and washers fixing the compressor on bottom plate 9 Lift the compress...

Page 191: ...conditioner and turn OFF the power breaker 1 Remove the big handle first and then remove the top panel 3 screws 3 Remove the screws of front panel 6 screws 4 Remove the screws of the right side panel 8 screws 2 4 3 2 Fan ass y How to remove the fan Screws of top panel 3 screws 1 screw is under the big handler 3 screws of the big handler 6 screws of front panel ...

Page 192: ...anel plate following procedure 1 remove the hex nut fixing the fan and then remove the fan 2 Unfix the hooks and then open the electronic control box cover 1 2 compressor T3 T4 T5 sensor Motor Electronic expansion valve 4 way valve ...

Page 193: ... Remove the four fixing screws of the fan motor Then remove the fan motor 3 Electrical parts How to remove the electrical parts 1 After finish work of item 1 and item 2 remove the connectors for the compressor 2 Pull out the two blue wires connected with the four way valve 1 3 4 2 ...

Page 194: ...ndenser coil temp sensor T3 outdoor ambient temp sensor T4 and discharge temp sensor T5 4 disconnect the electronic expansion valve wire 5 Remove the grounding screw 6 Remove the Wires 1 2 3 Then remove the electronic control box 3 4 5 6 ...

Page 195: ...pipe 10 Then the four way valve ass y can be removed The picture of four way valve may be different from the one on your side 3 4 5 Compressor How to remove the compressor 1 After perform work of item1 3 Recover refrigerant from the refrigerant circuit 2 Remove the discharge pipe and suction pipe with a burner 3 Remove the hex nuts and washers fixing the compressor on bottom plate 4 Lift the compr...

Page 196: ... 1 Stop operation of the air conditioner and turn OFF the power breaker 2 Remove the top panel 3 screws 3 Remove the screws of front panel 9 screws 4 Remove the screws of the right side panel 8 screws 2 4 3 2 Fan ass y How to remove the fan ass y 1 3 screws of top panel 9 screws of front panel 3 screws of big handle ...

Page 197: ...e fan 2 After remove the top cover Unfix the hooks and then open the electronic control box cover 3 Disconnect the connector for fan motor from the electronic control 2 T3 T4 T5 sensor wire Motor wire Electronic expansion valve Compressor wire 4 way valve wire Electric pipe heater and Crankcase electric heater ...

Page 198: ...n motor Then remove the fan motor 3 Electrical parts How to remove the electrical parts 1 After finish work of item 1 and item 2 remove the connectors for the compressor and reactor 2 Pull out the two blue wires connected with the four way valve 1 3 4 2 ...

Page 199: ...3 Pull out connectors of the condenser coil temp sensor T3 outdoor ambient temp sensor T4 and discharge temp sensor T5 4 disconnect the electronic expansion valve wire 6 remove the electric heaters 3 3 4 5 ...

Page 200: ...197 6 Remove the grounding screw 7 Remove the Wires 1 2 3 or L1 L2 S Then remove the electronic control box 7 ...

Page 201: ... pipe 11 Then the four way valve ass y can be removed The picture of four way valve may be different from the one on your side 3 5 Compressor How to remove the compressor 1 After perform work of item1 3 Recover refrigerant from the refrigerant circuit 2 Remove the discharge pipe and suction pipe with a burner 3 Remove the hex nuts and washers fixing the compressor on bottom plate 4 Lift the compre...

Page 202: ...ion of the air conditioner and turn OFF the power breaker 2 Remove the big handle first then remove the top cover 7 screws 3 Remove the screws of front panel 11 screws 4 Remove the screws of the right side panel 13 screws 2 4 3 2 Fan ass y How to remove the fan Screws of front panel 11 screws Screws of top panel 3screws 1screws is under the big handle 4 screws of big handle ...

Page 203: ...remove the panel plate following procedure 1 2 Remove the nut fixing the fan and remove the fan 3 Unfix the hooks and remove the screws then open the electronic control box cover 2 3 fan Electronic control box compressor ...

Page 204: ...nnector for fan motor from the electronic control board 5 Remove the four fixing screws of the fan motor then remove the motor 5 4 T3 T4 T5 sensor Pressure switch Compressor wire Electronic expansion 4 way valve Motor wire 5 ...

Page 205: ...m 1 and item 2 remove the connector for the compressor 2 Pull out the two blue wires connected with the four way valve 3 Pull out connectors of the condenser coil temp sensor T3 outdoor ambient temp sensor T4 and discharge temp sensor T5 4 Disconnect the pressure switch connector 1 2 3 ...

Page 206: ...203 5 Disconnect the electronic expansion valve wire from the control board 6 Remove the ground wires 7 Remove the wires 1 2 3 or L1 L2 S Then remove the electronic control box 6 7 5 4 ...

Page 207: ...d pipe 5 Then the four way valve ass y can be removed The picture of four way valve may be different from the one on your side 5 Compressor How to remove the compressor 1 After perform work of item1 3 Recover refrigerant from the refrigerant circuit 2 Remove the discharge pipe and suction pipe with a burner 3 Remove the hex nuts and washers fixing the compressor on bottom plate 4 Lift the compress...

Page 208: ...f the air conditioner and turn OFF the power breaker 2 Remove the screws of air outlet grille 8 screws 3 Remove the hex nut fixing the fan 4 Remove the fan 5 Remove the screws of top cover and remove the top cover 4 screws 6 Remove the screws of right front side panel and remove the right front side panel 1 Screws of top cover ...

Page 209: ...an motor after unfastening fixing screws 2 Panel plate How to remove the panel plate 1 Remove big handle 2 screws and water collector 2 screws 2 Remove two screws of terminal board and seven screws of right rear panel and remove the right rear panel Screws of Water collector Screws of big handle Screws of right rear panel ...

Page 210: ...orm work of item 1 step 5 6 and item 2 2 Disconnect the fan motor connector 5p white from the IPM board 3 Disconnect following 8 pieces of connection wires and connectors between IPM and other parts IPM board PCB board DC Fan Driver board Screws of right rear panel ...

Page 211: ...perature sensor 2p white CN12 Heatsink temperature sensor 2p red CN9 T3 T4 temperature sensor 2p 2p white CN15 Electronic expansion valve 6p red CN10 High and low pressure switch 2p 2p white Wires CN17 CN18 4 way valve blue blue CN19 CN20 connected to crankcase heating cable black red CN24 CN25 Electric heater of chassis orange orange CN1 L IN red or white CN3 N IN black 6 Disconnect the grounding...

Page 212: ... Extract refrigerant gas 3 Remove the sound insulation material and crankcase heating cable 4 Remove terminal cover of compressor and disconnect wires of crankcase electric heater and compressor from the terminal 5 Remove the discharge pipe and suction pipe with a burner 6 Remove the hex nuts and washers fixing the compressor to bottom plate 7 Lift the compressor ...

Page 213: ...ts from item 3 4 Remove fixing screw of the coil and remove the coil 5 Detach the welded parts of 4 way valve and pipe 6 The expansion valve How to remove the expansion valve 1 Perform work of item 1 2 2 Remove the electrical parts from item 3 3 Remove the coil 4 Detach the welded parts of expansion valves and pipes Coil Welded parts Expansion valves ...

Reviews: