Technical Manual
Motion Detector/Automatic Switch 55/63
Series .02
MDT technologies GmbH •
51766 Engelskirchen • Papiermühle 1
Tel.: +49-2263-
880 • Fax: +49-2263-4588 • [email protected] • www.mdt.de
20
20
4.3.3 Forced guidance/Lock object
Light channel
HVAC channel
The following picture shows the possible settings:
Figure 7: Settings
–
Forced guidance/Lock object
The following table shows the possible settings:
ETS-Text
Dynamic range
[Default value]
Comment
Forced guidance or lock
object
•
force object (2Bit)
•
lock object
•
lock object und lock object ON
Selection of whether a forced
guidance object or a lock object is
to be used.
Action at locking
•
Lock motion (lock current
state)
•
switch ON
•
switch OFF
Defines the status that is to be
sent during locking.
Parameter only available if "Lock
object" is selected.
Fallback of forced
guidance/lock
(General settings)
•
not active
•
active
Setting whether the channel
should react to "Fallback forced
guidance/lock" in the menu
“General settings”.
Table 8: Settings
–
Forced guidance/Lock object
The presence detector can be overridden with the forced guidance/lock object and call up a certain
status.
The forced guidance object knows 3 possible states:
•
Force control ON (control = 1, value = 1)
The command for “ON” is sent unconditionally to the output object. The evaluation is then
stopped and the release time for force control begins. If nothing is received on the force
control object after the release time has expired, normal operation is resumed.
•
Force control OFF (control = 1, value = 0)
The command for "OFF" is sent unconditionally to the output object. The evaluation is then
stopped and the release time for force control begins. If nothing is received on the force
control object after the release time has expired, normal operation is resumed.
•
Force control AUTO (control = 0, value = 0)
After that the normal operation of the detector is continued