Technical
Manual
Switch
Actuators
AMI/AMS
MDT technologies GmbH •
51766 Engelskirchen • Papiermühle 1
Tel.: +49-2263-880 • Fax: +49-2263-4588 • [email protected] • www.mdt.de
31
The
chart
shows
all
possible
settings
for
staircase
outputs:
ETS
‐
text
Dynamic
range
[default
value]
comment
Mode
normally
opened
normally
closed
Operation
mode
of
the
channel
Time
for
staircase
[s]
0…65535
sec
[120
sec]
Duration
of
the
switching
process
Prewarning
not
active
active
Activates
the
prewarning
function
Warning
time
[s]
0…65535
sec
[120
sec]
Duration
of
the
warning;
Only
available
when
warning
is
activated
Prewarning
time
[s]
0…65535
sec
[120
sec]
Adjustment,
how
long
the
light
shall
be
switched
on
after
the
warning;
Whole
duration
of
the
warning
process
is
the
sum
of
the
3
times:
Staircase
time,
warning
and
prewarning
Only
available
when
warning
is
activated
Manual
switching
off
not
active
active
Activation
of
the
manual
turn
off
of
the
staircase
Extend
staircase
time
not
active
active
Activation
of
the
extension
of
the
staircase
Central
function
not
active
active
Activates
the
central
function
for
this
channel
Behavior
when
locked
Off
On
no
change
Action
for
activating
the
blocking
process
Behavior
when
unlocked
Off
On
no
change
Action
for
deactivating
the
blocking
process
Behavior
at
bus
power
down
Off
On
no
change
Action
for
a
bus
power
breakdown
Behavior
at
bus
power
up
Off
On
no
change
Action
for
a
bus
power
return
Table
24:
Parameter
staircase