4.4.3 Setpoint offset
The following settings are available at the ETS-Software:
Figure 11: Setpoint offset
The following chart shows the dynamic range for this parameter:
ETS-text
Dynamic range
[default value]
comment
Max setpoint offset
0K
–
10,0K
[3,0K]
indicates the maximal offset
Set point value offset via 2 Byte
object
inactive
active
Activation of the setpoint offset via 2
Byte object; a temperature difference in
Kelvin is sent
Set point value offset via 1 Bit
object
inactive
active
Activation of the setpoint offset via 1 Bit
object; sending a 1 increases the
setpoint by the adjusted step range,
sending a 0 decreases the setpoint by
the adjusted step range
Step range
0,1K-1K
0,5K]
Adjustment of the step range for the
setpoint offset via 1 Bit object
Max setpoint offset valid for
Comfort
Comfort/Night/Standby
scope of the setpoint offset
Reset setpoint offset after
change of mode
No
Yes
Adjustment, whether a setpoint offset is
still valid after change of operating
mode or not
Send setpoint change
No
Yes
Adjustment, whether a change of mode
should be send or not
Table 24: Setpoint offset
The setpoint can be changed manual by the setpoint offset without a new parameterization by the
ETS-Software. Therefore, 2 variants are available. On the one hand a new setpoint can be pretended
by the
o
u i atio o je t “etpoi t o fo t . O the othe ha d the adjusted setpoi t a e
i
eased o de eased a ual the o
u i atio o je t a ual setpoi t alue offset .