Technical Manual
Glass Push-button II Smart & Push-button Smart 86 [Series .02]
MDT technologies GmbH •
51766 Engelskirchen • Papiermühle 1 • Germany
Phone: +49-2263-
880 • [email protected] • www.mdt.de
91
91
The following table shows the available settings:
ETS-Text
Dynamic range
[Default value]
Comment
Setting Logic 1-4
▪
not active
▪
AND
▪
OR
Activates the logic function and
set the logical operation.
Behaviour on bus
power return
▪
do not request external logic
objects
▪
request external logic objects
Defines whether the external
objects are to be requested
automatically after bus voltage
recovery.
Object type 1-4
▪
1 Bit DPT 1.001 Switch
▪
2 Bit DPT 2.001 Forcible control
▪
1 Byte DPT 5.005 Decimal value
(0…255)
▪
1 Byte DPT 17.001 Scene number
Setting of the object type for
sending a value when the logic
operation is fulfilled.
Forcible control/
1 Byte value/
Scene number
if output = 0 / 1
any value according to DPT
Setting of the value that is sent
when the logic operation is
fulfilled. Values to be sent
depend on the sending
condition.
Only for object types: Scene/
Decimal number/ Forcible
control.
Sending condition
▪
not automatic
▪
on input telegram
▪
on change of output
▪
on change of output (send only 0)
▪
on change of output (send only 1)
The sending condition can be
specified and a sending filter
can be set
Output inverted
▪
not active
▪
active
Only for object type "Switch".
Determines whether the output
signal should be inverted.
Table 74: Settings
–
Logic 1-4
Depending on the object type of the logic operation, the corresponding communication object is
shown:
Number
Name/Object Function
Length
Usage
93
Logic 1
–
Output: Switch, Value, Scene
Output of the logic operation.
DPT depending on the parameter setting
Table 75: Communication object
–
Logic 1-4
If a logic operation is fulfilled, a value or a scene can be sent according to the selected
object type
.
The
sending condition
for the output can be defined. The logic operation can, for example, send with
every input telegram, only send when the output of the logic operation changes, or a send filter can
be activated. In this case, only a "1" or "0" is sent for the "Switch" object type. With the object types
"Forcible control, scene, decimal value", it can be specified that only the set value or scene for the
output value "0" or "1" of the logic operation is sent. With the "not automatic" setting, no output
value is sent, but this can be queried.
In addition, with the "Switch" object type, the
output can be inverted
and thus a "0" can be made
into a "1" and a "1" into a "0".