Step width
1 – 100% / 1 – 255
[10%/10]
Sets the step width between two
sending commands
Repeated sending at
pressed key
not active
active
Activation of the sending repetition
while pressing the button
Repetition time
200 ms – 3 s
[1 s]
Repetition time between two
telegrams while pressing the button
Switching considers status
object
Yes
No
Setting whether the value should be
moved according to the current
status
Table 36: Settings – Send values: - Subfunction: Shift values
Principle of operation:
The function "shift value" moves the set datapoint type within the set limits. When the "Down"
button is pressed, the set step width is subtracted from the last value and sent. When the "Up"
button is pressed, the set step width is added to the last value and sent.
Lower/Upper limit:
Within these limits, the value is shifted. The function never falls below the lower limit value and does
not exceed the upper limit value.
Step width:
The step width indicates the difference between two transmitted telegrams. Example: step witdth is
set to 10%. If the value 10% was sent with the previous transmission, the value 20% is sent with the
next "up" command..
Repeated sending at pressed key:
Repeated transmission while holding down the key allows the function to increase/decrease the
value until the upper/lower limit is reached.
Switching considers status object:
If the status value is taken into account, the key function sends the next value depending on the last
received status value. If a status value of 15% and a step size of 10% were selected, then the value of
25% would be sent with the next "up" command. If the status value is not taken into account, the
push button memorizes the last value that was sent and sends the next value regardless of the status
value.
The following table shows the available communication objects:
Number Name
Length Usage
0
Push buttons 1/2 –
Percent value, Decimal value…
1 Byte
Sending the switching value.
DPT depending on the parameter setting
1
Push buttons 1/2 –
State for display
1 Byte
Receiving the status.
DPT depending on the parameter setting
Table 37: Communitcation objects – Send values: - Subfunction: Shift values