Technical Manual Switch Actuator 3-fold, FanCoil
MDT technologies GmbH
•
51766 Engelskirchen
•
Papiermühle 1
Tel.: +49-2263-
880 • Fax: +49
-2263-4588
• [email protected] • www.m
dt.de
55
The following table shows the available settings:
ETS-text
Dynamic range
[default value]
comment
Block Object 1/2
not active
active
Activates/Deactivates the blocking
object
Action at Activation Blocking of
1/2
no reaction
switch off valves and
ventilation
switch to step 1
switch to step 2
switch to step 3
no reaction
: The FanCoil is blocked for
further control and stays in the current
step.
Switch off valves and ventilation:
The
FanCoil and the valve is switched off.
Switch to step 1-3:
The FanCoil is
switched to the adjusted step.
Action at Deactivation Blocking
of 1/2
no reaction
switch to step 1
switch to step 2
switch to step 3
restore previous step
(Memory function)
no reaction
: The FanCoil is blocked for
further control and stays in the current
step.
Switch to step 1-3:
The FanCoil is
switched to the adjusted step.
Memory function:
The FanCoil restores
the step which was active before
blocking.
Table 46: Blocking function - FanCoil
The blocking objects 1 and 2 works independent of each other. Blocking object 1 has a higher priority
than blocking object 2.
The following table shows the available communication objects:
Number
Name
Length
Usage
25
Block object 1
1 Bit
Blocking the FanCoil
26
Block object 2
1 Bit
Blocking the FanCoil
Table 47: Communication objects - Blocking Function
6.1.4 Activation of further submenus
For activating the menus of additional ventilation, automatic mode, direct mode and state functions,
the following settings must be set to active:
Figure 44: Activation of the submenus